Dual-Fuel Conversion for Diesel Generator Sets

How diesel generators are converted to dual fuel: diesel for ignition, gas for part of the energy, controller fallback, suitability, benefits, limits, safety and the checks before conversion.

In short. In a dual-fuel set, gas supplies part of the energy while a reduced diesel injection still ignites the charge. If gas pressure or quality falls, the controller returns to full diesel, so backup is not lost. The share of diesel replaced depends on the engine, the load and the gas supply. It is highest at steady, moderate-to-high load and low at light load. Dual fuel suits sets with long running hours and a reliable gas supply.

Who this page is for: For owners of prime or long-hour diesel generators with access to pipeline gas, compressed gas or biogas.

Key facts

  • Diesel still ignites the mixture; gas supplies part of the energy.
  • Loss of gas means automatic return to full diesel.
  • Substitution is lower at light load and on fast load changes.
  • Savings scale with running hours; standby sets gain little.
  • Gas brings leak and ventilation hazards that must be engineered.
  • Plan on a conservative substitution figure, proved by a trial.
  • Dual fuel usually cuts smoke and particulate but can raise carbon monoxide and unburnt methane; measure emissions after conversion and allow for an oxidation catalyst if needed.

Worked example: diesel replaced on a 500 kVA prime set (illustrative)

ItemWorkingResult
Energy generated400 kW × 60% × 3000 h720,000 kWh a year
Diesel used today, about 0.27 litres per kWh720,000 × 0.27about 194,000 litres
Weighted substitution over the real load profilePlanned conservatively35%
Diesel replaced194,000 × 0.35about 68,000 litres a year
Gas neededSame energy, plus a few percent for efficiency changeConfirm with the conversion supplier’s data

Compare the litres saved and the gas needed at your own current tariffs. The same conversion on a standby set running 50 hours a year would save at most about 1100 litres at the same load and substitution, and usually far less, because standby runs are short and lightly loaded. See compatibility assessment and fuel consumption chart.

Do not plan savings on the highest substitution figure quoted. It applies to steady, well-loaded running; the figure over a real load profile is lower.

Safety essentials

  • Gas detection with automatic shut-off.
  • Ventilation of the generator room.
  • Review of electrical equipment near gas parts.
  • Purging, leak testing and trained staff.

See dual-fuel engineering.

Dual-fuel screening sheet

ItemValue
Running hours per year 
Typical load 
Gas source and pressure 
Diesel used per year 

Substitution rate: what the number means, and why the annual average is lower

Every dual-fuel conversion is sold on a substitution rate, and the figure quoted is almost always the best one the system can reach. It is not wrong, but it is a peak and not an average, and the difference between the two decides whether the conversion pays.

Substitution is the share of the engine’s energy supplied by gas rather than diesel at a given moment. A well-set-up system on a steady load at three-quarters of rating will reach 65 to 70%. The same system averaged over a year of real duty lands between 50 and 60%, and the gap is not a fault — it is the sum of four conditions in which the engine deliberately takes less gas or none at all.

  • Starting and the first minutes. The engine starts on diesel alone and gas is introduced only once it is running and warm. Every start therefore begins at zero substitution, and on a set with many short runs that is a material share of the year.
  • Low load. Below roughly a third of rating the combustion margin for gas narrows and the control reduces or withdraws it. A set that spends its evenings at 20% load spends them on diesel.
  • Load steps and transients. Gas responds more slowly than diesel, so a step change is met by the diesel side while the gas control catches up. A site with large motors starting against the set loses substitution every time one starts.
  • Knock margin on a hot day or a poor gas. The control backs gas off to protect the engine when ambient temperature rises or gas quality falls. That is the system working correctly, and it happens most in the season a set runs hardest.

So the honest planning figure is an annual average, taken from the duty rather than the datasheet. Set B of the fleet described across this section runs 3000 hours a year at 300 kW and burns 243,000 litres of diesel. The table shows what that becomes at three different annual averages, and the spread between them is the whole commercial risk of the project.

Annual average substitutionDiesel still burntDiesel displacedWhen this figure is realistic
70% — the headline figure72,900 L170,100 LSteady base load, long runs, good gas, moderate ambient. Rare as an annual average
60%97,200 L145,800 LMostly steady duty with few starts and modest load steps
55% — the planning figure for this set109,350 L133,650 L3000 hours with real starts, evening part load and motors starting against the set
50%121,500 L121,500 LMany short runs, frequent low load, or gas quality that varies

The difference between the headline 70% and a realistic 55% is 36,450 litres of diesel a year on this one set — and it is the difference between a project that performs as promised and one that disappoints without anything being broken. Specify the conversion against the annual average the duty supports, write that figure into the acceptance criteria, and measure it over a season rather than on a commissioning day. A system accepted on a single steady-load test has been accepted against its peak.

How to measure the rate you actually got

Substitution is the one performance figure a site can verify for itself, and it needs only a diesel figure, a gas figure and the discipline to read them on the same date.

Diesel is measured as it always was — day tank dips or a transfer meter, booked to the set. Gas is measured at the gas train. Both are converted to energy and the ratio is the substitution. The conversion factors come from the fuel supplier for the gas and are standard for diesel, and they belong in the site’s own record so the sum can be repeated rather than re-derived each time.

The check that makes the figure trustworthy is the same cross-check that validates any generator record: total energy in should match the energy the set produced. Take the kWh the set generated from the controller, divide the combined fuel energy by it, and compare that against the set’s known efficiency before conversion. A figure close to the original means the measurement is sound. A figure materially better means something is unmetered — usually gas — and a figure materially worse means the engine is not converting the gas it is being given, which is a tuning problem rather than an accounting one.

Read monthly, that single ratio also becomes the system’s health trend. Substitution drifting down over a season points at gas quality, filter condition or a drifting control map, and it points at it long before anybody notices the diesel bill. Sites that measure substitution once, at commissioning, have a number. Sites that measure it monthly have an instrument.

What the conversion changes on site, beyond the engine

A conversion is often scoped as engine work, and three of its consequences sit outside the engine entirely.

The emission position has to be re-established. The set’s existing emission evidence describes a diesel engine, and after conversion it describes nothing. A fresh test after conversion, at the set’s real operating load, is what puts the file back on a footing — and it is worth doing after the system has settled rather than in the first week, because a map still being tuned will not represent the year.

Operators now run two fuel systems. That means two sets of isolation points, two leak scenarios and a shutdown sequence that has to make the gas side safe before the engine stops being able to burn it. The competence requirement is real and it is the part most often left to a handover conversation rather than written down.

The fuel supply chain doubles. Diesel can be bought from anybody at short notice; gas arrives on a connection or a contract with a lead time. A set whose substitution the site now depends on has acquired a second single point of failure, and the mitigation is the ordinary one — the engine must still be able to run on diesel alone at full output, and that capability must be tested occasionally rather than assumed.

One exception worth stating plainly: a set that cannot reach a sensible annual average is better left alone. The four conditions above are properties of the duty, not of the conversion kit, so a set that starts often, runs lightly and faces large load steps will sit at the bottom of that table whatever is fitted to it. For that set the money does more good spent on the duty — a battery to remove the short runs, or load management to lift the running load — and the conversion reconsidered afterwards.

The acceptance test, written so it can be failed

A conversion that cannot be failed at acceptance will not be fixed afterwards, and most acceptance tests as written cannot be failed, because they ask for a substitution figure without saying at what load, for how long or in what weather. Four clauses close that gap, and they fit on one page.

  • At the duty load, not the convenient one. The figure is demonstrated at the load the set actually carries — 300 kW for set B — and separately at a third of rating, so the low-load behaviour is on record rather than discovered in service.
  • Over a period, not a moment. A continuous run of at least four hours with the load varied as the site varies it, and the fuel figures taken across the whole run. A spot reading at a steady point is a measurement of the best minute of the day.
  • Including starts. The test includes the number of starts a normal day contains, because starting on diesel is one of the four conditions that pulls the average down and the site is buying an average.
  • With the diesel-only capability proved at the end. The gas is isolated and the set is taken to full output on diesel alone, because that capability is the fallback the whole arrangement rests on and it is the one thing nobody checks once the gas is working.

Written that way the acceptance figure and the planning figure are the same number, which is the point. A conversion accepted at 70% on a steady four-hour run and then planned at 70% will under-deliver every year of its life, and nobody will be able to say when it started.

Common mistakes

  • Converting standby sets.
  • Planning on peak substitution.
  • Gas safety treated as an afterthought.
  • No trial before a fleet decision.

What to send us

Send running hours, load profile and gas availability. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative.

Questions engineers ask

What substitution rate does dual fuel actually achieve?

A well-set-up system on steady load reaches 65 to 70% at the moment of measurement, but the annual average lands between 50 and 60%. The gap is four conditions in which the engine takes less gas or none: starting and the first minutes, running below about a third of rating, load steps, and the control backing gas off for knock margin on a hot day or poor gas.

Why does the annual average matter more than the headline figure?

Because the diesel bill follows the average. A set burning 243,000 litres a year still burns 72,900 at 70% substitution but 109,350 at a realistic 55%, a difference of 36,450 litres a year on one set. That is the difference between a project that performs as promised and one that disappoints with nothing broken, so the planning figure and the acceptance figure should be the same number.

What does a dual fuel conversion change beyond the engine?

Three things outside it. The emission evidence has to be re-established, because the existing test describes a diesel engine. Operators now run two fuel systems, with two sets of isolation points and a shutdown sequence that makes the gas side safe first. And the fuel supply chain doubles, so the set must still reach full output on diesel alone and that capability has to be tested rather than assumed.

Can any diesel set be converted?

No. The engine is assessed first: model and kit approval, compression, oil consumption, injectors, turbocharger and exhaust temperature balance. A worn engine misfires and knocks more readily on gas, so it is repaired first or given another route, and the duty must have enough hours at good load to repay the conversion.

What if gas runs out?

The controller closes the gas valves and the engine returns to diesel only, carrying the load on its original fuel. The change is designed to be quick, but it is proved by closing the gas supply at the highest load band during commissioning, and the test is repeated each year.

Which gases?

Natural gas, biogas, Bio-CNG and LPG are commonly considered, subject to quality. Each gas has its own heating value, knock resistance and supply requirements, so the kit and its settings must be approved for the gas actually used, and biogas is cleaned of moisture and hydrogen sulphide first.

Is it safe?

Yes, with proper design, gas detection and trained staff. The gas train has double shut-off valves and pressure switches, detectors are placed for the gas in use, ventilation is monitored, and emergency stop removes gas as well as diesel. Every safety function is proved at commissioning and tested regularly.

General guidance only. Substitution rates vary; verify per engine.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.