Dual-Fuel Compatibility & Conversion Assessment

How to assess whether a diesel generator suits dual-fuel conversion: engine condition, duty profile, gas supply, space and safety, approvals, economics and a structured go or no-go review.

In short. A dual-fuel assessment checks four things: whether the engine can take it, whether the duty will give enough substitution, whether gas can be supplied safely and reliably, and whether the savings justify the cost. Running hours and typical load matter most. A trial on one set with measured fuel use is the best way to replace assumptions with data before converting a fleet.

Who this page is for: For owners and consultants deciding whether particular sets should be converted to dual fuel.

Key facts

  • Engine: model, condition, compression and injection system.
  • Duty: hours per year and typical load.
  • Gas: source, pressure, quality and reliability.
  • Site: space, ventilation and distance from ignition sources.
  • Commercial: gas contract, warranty and insurance effects.
  • Record the decision and its assumptions.

Worked example: two 500 kVA sets (illustrative)

ItemSet ASet B
DutyPrime, 3000 h at 60%Standby, 50 h at 40%
Diesel used per year (about 0.27 litres per kWh)about 194,000 litresabout 2200 litres
Realistic weighted substitutionabout 35%about 15%
Diesel replaced per yearabout 68,000 litresabout 320 litres
Gas supplyPipeline at site boundaryNone
DecisionTrial, then convertNot worthwhile

The same conversion cost buys two hundred times more diesel saving on set A. See dual-fuel overview and other routes.

Do not convert a worn engine. Dual fuel makes misfire and knock more likely on an engine in poor condition; overhaul first or choose another route.

Assessment factors

FactorFavourableUnfavourable
Running hoursThousands a yearStandby only
LoadSteady, moderate to highLight and variable
GasPipeline or reliable deliveryUncertain
EngineGood condition; maker supportWorn

See dual-fuel engineering.

Assessment sheet

FactorFindingFavourable?
Engine condition  
Hours and load  
Gas supply  
Site safety  
Diesel replaced per year  

Checking the engine

The engine assessment decides whether a conversion is possible at all. A converted engine runs hotter in parts of its load range and is more sensitive to poor combustion, so faults that a diesel engine tolerates become problems on dual fuel.

CheckWhy it matters
Engine model and kit approvalThe conversion kit must be approved for that model
Running hours since overhaulA worn engine misfires and knocks more readily
Compression testLow or uneven compression gives poor combustion of the gas mixture
Oil consumption and blow-byHigh values mean worn rings and liners
Injector conditionA poor pilot spray limits the gas the engine can burn
Turbocharger and charge coolingIntake temperature sets the knock margin
Exhaust temperatures per cylinderBaseline balance before conversion

An engine that fails these checks is overhauled first or given another route; converting it adds cost to a set that will not deliver the expected substitution.

Screening the duty

The diesel saving is roughly the diesel used in a year multiplied by the realistic weighted substitution. Diesel used can be estimated from rating, power factor, average load, hours and specific consumption, as in the worked example, but a measured figure from fuel records is better. For set A, 500 kVA × 0.8 × 0.6 × 3000 hours × 0.27 litres per kWh gives about 194,000 litres, and 35% of that is about 68,000 litres a year. For set B the same method gives about 2200 litres and about 320 litres saved, which no conversion repays.

Two duty features push the result down: hours at light load, where substitution is close to zero, and frequent large load steps, during which the controller cuts gas. A load histogram from the controller log, or a few weeks of logging, shows both before any decision.

Checking the gas supply

  • Source: pipeline, compressed gas delivered to site, or biogas from a process on site.
  • Pressure and flow: enough to supply the highest gas flow at the high load band, with the pressure still above the low-pressure setting during a load step.
  • Quality: composition and heating value, and for biogas the methane content, moisture and hydrogen sulphide.
  • Reliability: how often the supply is interrupted, since every interruption returns the set to diesel.
  • Contract: the terms of supply and any minimum offtake, which affect the saving.

Site safety review

Bringing gas to a generator brings new hazards to the room or enclosure. The review covers the route of the gas pipework and its protection, the ventilation of the room for both combustion air and dilution of a leak, gas detection placed for the gas in use, the separation of the gas train from ignition sources, the emergency isolation point outside the room, and the electrical equipment near the gas train. The arrangements are agreed with the bodies whose approval the site requires before work starts.

Designing the trial

A trial on one set replaces assumptions with measurements before a fleet is converted. A useful trial runs long enough to cover the normal duty, usually several weeks, and records:

  1. Diesel use in litres per hour in each load band, before conversion and during the trial.
  2. Gas use in each band, corrected to standard conditions.
  3. Exhaust temperature spread, knock events and the number of returns to diesel.
  4. The frequency dip and recovery for the largest load step in both modes.
  5. Emissions in each load band, measured by the applicable method.

The trial result, not the brochure figure, is what the fleet decision uses.

Ranking a fleet

SetHours a yearTypical loadGas availableEngine conditionPriority
A300060%YesGoodTrial first
C200070%YesGoodConvert after the trial
D250030%YesGoodLow; light load limits substitution
E180065%YesWornOverhaul before deciding
B5040%NoGoodNot worthwhile

The ranking is illustrative. It shows that hours and load matter most, and that a worn engine is repaired before it is converted.

Warranty, insurance and records

A conversion can affect the engine warranty, the insurance of the plant and any service agreement. Each is settled in writing before conversion. The decision record lists the assumptions used, the trial results, the approvals obtained and the settings applied, so that the decision can be reviewed after a year of operation against the diesel actually bought.

When the answer is no

An assessment that rejects dual fuel is still useful. For a standby set, the better route is usually an emission control device where its approval covers the engine, or replacement with a set type-approved to current norms. For a long-running set without gas, it may be an overhaul with injector and turbocharger work to bring fuel consumption back to the maker figure, or a hybrid arrangement with a battery that removes light-load running. The comparison of these routes is set out on the page on other routes linked above.

The assessment step by step

  1. List every set with rating, engine model, age, running hours, typical load and location.
  2. Screen out standby sets with low hours and sets without a gas supply.
  3. Check engine condition on the remaining sets: compression, oil consumption, injectors and exhaust balance.
  4. Confirm that an approved conversion kit exists for each engine model.
  5. Obtain gas supply data: pressure, flow, quality and reliability.
  6. Estimate the diesel saving from measured fuel use and a realistic substitution for the load profile.
  7. Review site safety and the approvals needed.
  8. Settle warranty, insurance and service arrangements.
  9. Run a trial on the best candidate and measure the result.
  10. Decide set by set, record the assumptions and plan a review after a year.

Measuring fuel before the decision

The diesel figure in the screening is the one most often guessed. A better figure comes from fuel records: deliveries into the tank, tank dips at the start and end of each period, and the hour meter over the same period. Divided by the energy generated, read from the controller or an energy meter, it gives litres per kilowatt-hour at the real load, which can differ noticeably from the typical 0.27 used for illustration. An engine that uses well above its maker figure has a fault to fix whether or not it is converted, and fixing it may save more than the conversion would.

How much gas the set will draw

The gas train and supply are sized from the gas the engine draws at its highest gas share. For set A at 60% load, the engine delivers about 240 kW; at a fuel efficiency of about 35% it takes in roughly 690 kW of fuel energy, and at a 60% gas share in that band about 410 kW of it comes from gas.

Natural gas carries roughly 10 kWh per standard cubic metre, so the engine draws about 41 standard cubic metres an hour at that point, and more at higher loads. These figures are illustrative; the kit maker states the flow for the engine, and the supply is confirmed against it with a margin for load steps.

Emissions after conversion

Dual fuel usually reduces particulate emissions because less diesel is burnt, but carbon monoxide and unburnt methane can rise, especially at light load. The assessment therefore includes a measurement in each load band after conversion, by the method that applies to the set, and a comparison with the limits that apply to it. A conversion is not assumed to improve compliance until the measurements show it.

Reviewing the decision after a year

A year after conversion the decision record is reopened. The diesel actually bought, the gas consumed and the hours in each load band are compared with the assumptions, together with the returns to diesel, knock events and maintenance work on the gas side. Where the saving matches the trial, the conversion of the next set on the ranking can proceed with confidence. Where it falls short, the cause is usually more light-load running than expected, lower gas pressure at high load or a controller that cuts gas more often than it should, and each of these can be corrected before more sets are converted.

The review is also the moment to recheck the approvals, the insurance terms and the gas contract, since any of them may have changed during the year, and to update the fleet ranking with the measured result rather than the original estimate.

Common mistakes

  • Converting standby sets.
  • No trial.
  • Warranty and insurance not checked.
  • Assumptions not written down.

What to send us

Send each set’s hours, load and engine details. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative.

Questions engineers ask

How do I estimate the diesel a set will save on dual fuel?

Multiply the diesel used in a year by the realistic weighted substitution. For a 500 kVA set at 60% load for 3000 hours, about 194,000 litres a year at 35% substitution saves about 68,000 litres. Use measured fuel records where possible, and check light-load hours first.

What should a dual-fuel trial record?

Diesel use in each load band before and during the trial, gas use corrected to standard conditions, exhaust temperature spread, knock events, returns to diesel, the frequency dip for the largest load step in both modes, and emissions in each band. The trial result, not the brochure figure, decides the fleet.

What is the main risk?

Assuming a higher substitution rate than the site delivers. Brochure figures usually apply near full load in good conditions, while real sets spend hours at light load and see frequent load steps. A trial on one set with measured diesel and gas use in each load band replaces that assumption with data.

Does engine age matter?

Yes, through condition and support for the kit. A worn engine with low compression, high oil consumption or poor injectors misfires and knocks more readily on gas, and older models may have no approved conversion kit. Check condition first and overhaul or choose another route where needed.

Can I keep diesel backup?

Yes. A dual-fuel engine always burns some diesel as the pilot and can run on diesel alone, so the set returns to diesel automatically when gas fails or a limit is reached. Keep the diesel store and its fuel quality managed as for any standby set, and test the fallback on load every year.

Who approves?

Check with the local authorities that cover gas installations, emissions and electrical safety for the site, and with the engine maker or kit supplier for the conversion itself. The approvals required depend on the gas source, the quantity stored and the location, so they are confirmed before the work is ordered.

General guidance only. Values illustrative.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.