Diesel + Gas Dual-Fuel Engineering

The engineering of dual-fuel operation: pilot ignition, gas admission, air-fuel control, knock and misfire limits, controller strategy, sensors, gas quality and effects on the alternator.

In short. Dual-fuel engineering is about keeping combustion stable at every load. Too much gas at light load causes misfire. Too much at high load causes knock. The controller sets a safe gas share for each load, using signals for gas pressure, exhaust temperature, knock and load, and returns smoothly to diesel when limits are reached. Load-step response and governor settings must be rechecked after conversion.

Who this page is for: For engineers specifying, commissioning or troubleshooting dual-fuel conversions.

Key facts

  • The gas share is mapped against load, not fixed.
  • Light load: low gas share to avoid misfire.
  • High load: gas share limited to keep knock margin.
  • Exhaust temperature per cylinder shows combustion balance.
  • Gas quality changes, especially in biogas, need conditioning or lower shares.
  • Recheck load steps, governor and voltage control after conversion.

Worked example: a gas-share map and load test (illustrative)

LoadGas share of energyReason
Below 30%0–20%Misfire risk
50%about 40%Stable combustion
75%about 60%Best range
Above 90%about 50%Knock margin
Gas pressure low0%Smooth return to diesel

In this illustrative scenario, a load-step test on diesel and then on dual fuel shows a slightly deeper frequency dip on dual fuel, so the controller is set to cut the gas share briefly during large steps. See generator load steps and performance and substitution.

Do not run a converted set without knock and exhaust temperature monitoring on the gas side. Knock can damage pistons and rings before the operator notices any other symptom.

System parts

PartRole
Gas trainIsolation, filtering, pressure regulation and safety shut-off
Mixer or port injectionAdmits gas with intake air
Dual-fuel controllerSets gas share and manages fallback
SensorsGas pressure, exhaust temperature, knock, speed, load

See dual-fuel overview and compatibility.

Commissioning record

LoadGas shareExhaust temperature spreadKnock events
25%   
50%   
75%   
100%   

Reading the gas-share map

The map in the worked example is the core of a dual-fuel controller. It holds, for each load band, the share of the engine energy that may come from gas. The share is low at light load because the gas and air mixture is too lean for the small diesel pilot to ignite reliably, so some of the gas passes through unburnt.

It rises through the middle of the range, where combustion is stable and the cylinders are hot. It is trimmed back near full load, because a richer gas mixture in a hot cylinder approaches knock, where part of the charge ignites ahead of the flame front and hammers the piston crown and rings.

The map is not copied from a brochure. It is built on the actual engine during commissioning, band by band, with the limits set by the exhaust temperatures, the knock signal and the stability of speed and voltage, and then written down as the settings record for that set.

Signals the controller uses

SignalWhat it showsTypical action
Engine loadWhich band of the map appliesSets the allowed gas share
Gas pressure at the train outletWhether the supply can deliver the flowReduces gas, or returns to diesel below a set pressure
Exhaust temperature per cylinderCombustion balance between cylindersReduces gas if one cylinder runs hot or the spread grows
Knock sensorsAbnormal combustionCuts gas share at once and logs the event
Speed and frequencyResponse to load changesCuts gas briefly during large load steps
Intake air temperatureKnock margin on hot daysLowers the high-load gas share

Exhaust temperature as the health check

On a diesel engine the exhaust temperatures of the cylinders usually sit close together at a given load. Gas admitted through a single mixer does not always reach every cylinder equally, so on dual fuel the spread between the hottest and coolest cylinder is the most useful single indicator of how well the conversion is working.

A spread that grows over months points to an injector, a valve or a mixer problem, and a single cylinder running hot is a warning of knock or overload on that cylinder. Per-cylinder thermocouples are therefore part of the conversion, not an option, and their readings are logged at each load band during commissioning to set the baseline.

Load steps and the governor

When a large load arrives, the governor calls for more fuel. On diesel only, the injection pump responds within a fraction of a cycle. With gas in the intake, the gas already in the manifold and the time the gas train takes to respond slow the engine down. The controller therefore cuts the gas share briefly during large steps and restores it once speed recovers.

The governor gains set for diesel-only operation may also need retuning, because the engine behaves differently with gas. After any change, the largest expected load step is repeated in both modes and the frequency dip and recovery time are recorded against what the loads can tolerate.

Designing the gas train

  • A manual isolating valve outside the generator room or enclosure, accessible in an emergency.
  • A filter to keep dust and scale out of the regulator and mixer.
  • A pressure regulator sized for the highest gas flow at full load, with the outlet pressure held within the mixer range during load steps.
  • Two automatic shut-off valves in series, closing on any trip, loss of the controller or emergency stop.
  • Low and high pressure switches that reduce gas or return the set to diesel.
  • Gas detection in the enclosure or room, placed for the gas in use, linked to the shut-off valves.

The train is pressure tested after installation and after any modification, and the test is recorded with the commissioning results.

Biogas and variable gas quality

Natural gas from a pipeline has a fairly steady composition. Biogas does not: its methane content can swing with the digester, and it carries moisture and hydrogen sulphide. Moisture condenses in the train and mixer, and hydrogen sulphide forms acids that corrode the engine and degrade the oil. Biogas is therefore dried and cleaned before it reaches the engine, its methane content is monitored, and the gas-share map is set for the leanest gas the site expects, not the best. Oil analysis at shorter intervals shows whether the cleaning is working.

Fallback to diesel

Fallback is the most important function of the conversion, because it is what keeps the load supplied when the gas supply fails or a limit is reached. The controller closes the gas valves and the governor restores full diesel fuelling. The change is designed to be quick, but it is never assumed: it is tested at the highest load band by closing the gas supply, with frequency, voltage and the time to stable diesel operation recorded, and the test is repeated each year.

What changes in maintenance

  • Gas train components, pressure switches and shut-off valves are tested at the intervals their makers state.
  • Knock sensors and per-cylinder thermocouples are checked against a reference at each service.
  • Oil condition is watched closely, especially on biogas.
  • Injectors are kept in good condition, because a poor pilot spray reduces the gas the engine can burn cleanly.
  • The gas-share map and the settings record are reviewed after any engine work.

Commissioning sequence

  1. Run the set on diesel only through each load band and record exhaust temperatures, speed stability and the largest load step as the baseline.
  2. Pressure test the gas train and prove every shut-off and pressure switch.
  3. Introduce gas at a low share in the middle band and raise it in small increments, watching the exhaust spread and the knock signal.
  4. Repeat for each band, stopping each increase at the first sign of a limit and setting the map below it with a margin.
  5. Repeat the largest load step in dual-fuel mode and set the gas cut-back during steps.
  6. Close the gas supply at the highest band to prove fallback.
  7. Measure emissions in each band by the applicable method and record the final settings.

Common faults after conversion and their signs

SignLikely causeFirst check
Frequent returns to diesel at high loadGas pressure falls during peaksPressure at the train outlet during a load step
Knock events on hot afternoonsHigh intake temperature reduces the knock marginCharge cooling and the high-load gas share
One cylinder running hotUneven gas distribution or a poor injectorInjector test and mixer condition
Rising unburnt methane at light loadGas share too high in the light bandLight-band settings in the map
Deeper frequency dips than at commissioningGas cut-back during steps disabled or slowedController settings against the record
Falling substitution over monthsGas quality change, worn injectors or a drifting sensorGas analysis, injectors and sensor calibration

Records that keep the conversion healthy

A converted set needs a short monthly record alongside its normal log: running hours on dual fuel and on diesel only, the number of returns to diesel and their causes, knock events, the exhaust temperature spread at a typical load, and the diesel and gas used. Read together, these show whether the conversion is still delivering what it did at commissioning, and they point to the cause when it is not. A set whose returns to diesel or knock events start to climb is checked before the next service, not after a failure.

Safety interlocks to prove

Before the set runs on gas unattended, each safety function is proved by operating it, not by inspection: gas detection in the room closes both shut-off valves and returns the set to diesel or stops it as designed; loss of room ventilation does the same; the emergency stop removes gas as well as diesel; and a controller fault or loss of its power supply leaves the gas valves closed. Each result is written on the commissioning record with the date and the name of the person who witnessed it.

The same checks are repeated at every annual service, because a safety function that worked at commissioning can be defeated later by a bypassed relay, a failed detector or a changed setting.

Common mistakes

  • Fixed gas share at all loads.
  • No knock sensing.
  • Load steps not retested.
  • Biogas used without cleaning.

What to send us

Send engine data, gas details and load profile. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative.

Questions engineers ask

Why are per-cylinder exhaust temperatures needed on a dual-fuel set?

Because gas admitted through a single mixer does not always reach every cylinder equally. The spread between the hottest and coolest cylinder shows how evenly the engine is burning, a growing spread points to an injector, valve or mixer fault, and one cylinder running hot warns of knock or overload on that cylinder.

How is the gas-share map set during commissioning?

Band by band on the actual engine. Gas is introduced at a low share and raised in small steps while the exhaust spread, knock signal and speed stability are watched, and each increase stops at the first sign of a limit. The map is then set below that point with a margin and recorded.

Why does low load limit gas?

At light load the gas and air mixture is lean and the cylinders are cool, so the small diesel pilot cannot ignite it reliably. Part of the gas passes through unburnt, which wastes fuel and raises methane and carbon monoxide in the exhaust. The controller therefore holds the gas share low or runs on diesel only in the light band.

Does gas quality matter?

Yes. Composition changes the heating value and the knock resistance of the mixture. Biogas varies with the digester and carries moisture and hydrogen sulphide, which must be removed before the engine. The gas-share map is set for the leanest gas the site expects, and methane content and oil condition are monitored.

Is fallback instant?

It is designed to be quick: the gas valves close and the governor restores full diesel fuelling. It is never assumed, though. Test it at the highest load band by closing the gas supply, record frequency, voltage and the time to stable diesel running, and repeat the test every year.

Does the alternator change?

No, the alternator is not modified. What can change is the dynamic response of the set, because the engine responds differently to load steps with gas in the intake. Retest the largest load step, retune the governor if needed, and check that voltage recovery still suits the connected loads.

General guidance only. Follow conversion maker procedures.