RECD Operation, Monitoring & Maintenance Engineering

How to run and maintain a RECD: back-pressure trends, regeneration, ash cleaning, sensor checks, reagent quality, alarms, records and the warning signs that a filter or catalyst is failing.

In short. An emission control device protects the air only while it works. Log the pressure across the filter and the exhaust temperature at a fixed reference load, watch the trend, and give lightly used sets regular runs on load so the filter can clean itself. Clean out ash on schedule, check sensors and any urea supply, and keep records that show the device is performing.

Who this page is for: For facility managers and maintenance staff responsible for generators fitted with emission control devices.

Key facts

  • Read filter pressure at the same load each time so readings compare.
  • A steady rise means soot or ash loading.
  • A sudden fall can mean a cracked filter or a leak.
  • Lightly used sets need planned runs on load to burn off soot.
  • Ash must be removed by cleaning; it does not burn off.
  • Engine health, especially oil consumption, sets device life.

Worked example: monthly filter readings at 75% load (illustrative)

MonthPressure across filterAction
12.0 kPaBaseline
22.4 kPaNone
32.9 kPaWatch
43.5 kPa, alarm set at 4.0 kPaTwo-hour run on load bank
After the run2.2 kPaSoot cleared

Without the trend, the filter would have blocked during an outage. If the reading after each run keeps creeping up, it is ash, and the filter needs cleaning. See how the device works and emissions records.

Do not ignore visible smoke from a set fitted with a filter. It usually means a damaged filter or a bypass, and needs urgent inspection.

TrendMeaningResponse
Pressure climbs steadilySoot or ashRun on load; clean if it persists
Pressure falls suddenlyCrack or leakInspect
Temperature change at the same loadHigher: air restriction, turbocharger or injection fault; lower: sensor fault or exhaust leak upstreamCheck engine and sensor
Ammonia smell (urea systems)Over-dosing or catalyst faultCheck dosing

Monthly log

Twelve months of readings from the device fitted to Set A, the 500 kVA set that runs 2600 hours a year at Unit 1 of a pharmaceutical contract manufacturer. The example above shows five months of filter pressure and the load-bank run that cleared it; this log runs a full year and records the exhaust temperature alongside, which is what turns two of the entries below into findings the pressure column alone could not produce. Every reading is taken at the same 75% reference load.

DateLoadFilter pressureExhaust temperatureAction
Month 175%2.1 kPa412 °CBaseline, set at device commissioning. Alarm set at 4.0 kPa
Month 275%2.4 kPa410 °CNone
Month 375%2.8 kPa414 °CNone
Month 475%3.3 kPa411 °CWatch. Trend is steady, not sudden, so soot or ash rather than damage
Month 575%3.8 kPa413 °CTwo-hour run on load bank. Pressure after the run: 2.3 kPa
Month 675%2.6 kPa412 °CNone. Note the post-run baseline is 2.3, not the original 2.1
Month 775%3.0 kPa409 °CNone
Month 875%3.6 kPa411 °CTwo-hour run on load bank. Pressure after the run: 2.6 kPa
Month 975%2.9 kPa410 °CPost-run baseline now 2.6 against 2.1 at commissioning. That rise is ash, which does not burn off. Cleaning booked
Month 1075%3.4 kPa385 °CTemperature 26 °C below the year’s running figure at the same load. Not an engine fault: an exhaust leak was found at the sensor flange upstream. Gasket replaced
Month 1175%3.9 kPa411 °CAsh cleaning carried out by the maker’s method. Pressure after cleaning: 2.1 kPa
Month 1275%2.3 kPa412 °CBaseline restored to 2.1 after cleaning. Twelve-month trend restarted from here
     
     

The in-service pressure column tells a reassuring story twice over: it rises, a run on load clears it, and it rises again. Read on its own it would have produced two load-bank runs a year and no further thought. The finding is in a number that is not a column at all — the reading taken immediately after each run.

Those three readings are 2.3, 2.6 and, after cleaning, 2.1, against 2.1 at commissioning. Soot burns off and returns the device to its baseline; ash does not, and it is the creep in that baseline, 0.2 kPa and then a further 0.3, that says cleaning is due rather than another run. A log that records only the monthly reading can never separate the two, because both look like a rising pressure.

Month 10 is the other finding, and it belongs to the temperature column. A 26 °C fall at the same load is not something an engine does quietly: the plausible engine causes raise exhaust temperature rather than lowering it, and a genuine drop points at either a sensor that has gone wrong or gas that is escaping before it reaches the sensor.

Here it was the second, at the flange upstream — which also means the device had been receiving less of the exhaust than it should have, so a month’s emission performance was compromised without the pressure reading moving at all. The reading that found it cost nothing beyond writing a second figure in a second column.

None of the above works without the first column being disciplined. Every one of these twelve readings was taken at 75% load, which is why a 26 °C difference means something and why a 0.2 kPa baseline creep is worth acting on. Readings taken at whatever load the plant happened to be carrying would scatter by far more than either signal, and the trend that found both faults would simply not exist.

For a set like A, at 2600 hours a year, the reference load reading is easy to arrange. For a standby set it has to be a planned run on load, which is the same discipline and more trouble — and on a lightly used set it is also the only thing that stops the filter loading up quietly until the outage it was bought for.

Reading the pressure trend: four shapes, and what each one means

A retrofitted emission control device reports its own condition through one number, the differential pressure across it, and almost everything a site needs to know is in the shape of that number over time rather than in its value on any one day. Four shapes cover nearly every case, and three of them are acted on differently.

Shape of the trendWhat it meansWhat to doHow quickly
Rises steadily, drops back to the baseline after cleaning, repeatsNormal. The device is loading with ash and cleaning is restoring itNothing. Record the cleaning interval it settles at — that is the real one for this setRoutine
Rises steadily but each cleaning returns it to a higher baseline than beforeSomething is accumulating that cleaning does not remove. Usually oil, sometimes a damaged substrateCheck oil consumption on the engine. A rising floor is an engine symptom reported by the deviceWithin weeks. The device will reach its limit and stop being cleanable
Rises far faster than the duty suggestsThe set is running lighter or colder than assumed, so unburnt fuel rather than ash is filling the deviceCheck the duty with fuel divided by hours. The fix is the load, not the deviceWithin weeks, before the deposit sets
Flat, unchanging, month after monthAlmost always a sensor nobody is reading, not a device that is not loadingVerify the instrument against a separate gauge at full load. A flat trace is the commonest fault on this pageImmediately. A flat trace means the alarm is unproven too

The fourth row is the one to check first on any installation inherited rather than commissioned. A flat differential trace is read as good news and it is nearly always a dead reading — a blocked tapping, a sensor out of range, or a gauge that was never piped up. It matters more than it looks: on an installation whose back-pressure margin at the cleaning threshold is only a couple of millibars, the pressure switch is the only thing standing between the device and an engine running over its exhaust limit, and a dead sensor disables it silently.

Ash and soot are not the same problem

Two different things fill a device and they behave in opposite ways, which is why one cleaning regime does not cover both.

Soot is carbon, and it burns off. It accumulates when the exhaust is cooler than the device needs and it is removed by running hot enough for long enough, either in normal duty or in a deliberate regeneration. A device filling with soot is reporting a duty problem, and the cure is load and running time rather than a service visit.

Ash is incombustible, and it does not. It comes mostly from the additive package in the lubricating oil, it accumulates slowly and permanently, and it is removed only by physically cleaning the element. Ash is what sets the real cleaning interval, and because its source is oil consumption, an engine using more oil fills its device faster in a way no change of duty will fix.

The practical consequence is in the diagnosis. A device whose differential rises and comes back down with a hot run was holding soot. One whose differential comes down only after a physical clean was holding ash. And one that comes down after a clean but not all the way — the second row of the table above — is holding oil residue, which is neither, and which is the signal to look at the engine rather than the device.

One exception is worth stating because it reverses the usual advice. On a standby set that runs a few hours a year, neither ash nor soot accumulates meaningfully, and the device’s maintenance is governed by time and by the condition of its reagent if it has one, not by its pressure trend. For that set the task is a dated replacement and an annual proving of the instrument, and reading the trend monthly tells nobody anything.

What to log, how often, and the one entry that makes the rest useful

A device’s record is three numbers and a date, and the discipline is in taking them together rather than in taking them often.

EntryHow oftenWhy it is in the same row as the others
Differential pressure across the deviceMonthly, and after every cleanThe number the whole regime turns on
Load the reading was taken atEvery reading, without exceptionDifferential rises with the square of flow, so a reading without a load is not comparable with any other reading
Running hours at the timeEvery readingTurns a sequence of readings into a loading rate, which is what sets the cleaning interval
Cleaning or replacement, with what was foundEach timeDistinguishes ash from soot from oil residue after the fact

The second row is the entry that makes the other three worth having, and it is the one most often left blank. Because differential pressure follows the square of exhaust flow, a reading at half load and a reading at full load on the same healthy device can differ by a factor of four — so a column of pressures with no loads beside them is a column of unrelated numbers, and a trend drawn through it will show rises and falls that are nothing but the load on the day. Sites that log the load alongside can draw a real trend from quarterly readings; sites that do not cannot draw one from weekly readings.

Common mistakes

  • Readings at random loads.
  • No runs on load for standby sets.
  • Improvised filter cleaning that cracks it.
  • Device left out of the maintenance plan.

What to send us

Send your device logs and the generator’s running pattern. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative.

Questions engineers ask

What does a flat differential pressure reading on an emission control device mean?

Almost always a sensor nobody is reading, not a device that is not loading. A blocked tapping, a sensor out of range or a gauge never piped up all produce a flat trace, and it gets read as good news. It matters because on an installation with only a couple of millibars of margin at the cleaning threshold, the pressure switch is the only protection the engine has, and a dead sensor disables it silently.

What is the difference between ash and soot in a filter?

Soot is carbon and it burns off, so a device filling with soot is reporting a duty problem that load and running time cure. Ash is incombustible, comes mostly from the oil additive package, accumulates permanently and is removed only by physically cleaning the element. Ash sets the real cleaning interval, and an engine using more oil fills its device faster in a way no change of duty will fix.

Why must the load be recorded with every pressure reading?

Because differential pressure rises with the square of exhaust flow, so readings at half and full load on the same healthy device can differ by a factor of four. A column of pressures with no loads beside them is a column of unrelated numbers. Sites that log the load can draw a real trend from quarterly readings; sites that do not cannot draw one from weekly readings.

How often to clean ash?

At the interval the device maker states, adjusted by the trend in back-pressure. Ash from burnt oil builds up slowly and cannot be burnt off, so a steady rise in back-pressure at the same load shows when cleaning is due. Each cleaning is recorded with the readings before and after.

Can I bypass during an outage?

Only if the design includes an approved bypass and the applicable rules allow its use; never assume it. Where a bypass exists, its use is logged with the date, time, duration and reason, because operating without the device may affect compliance and must be explainable at inspection.

What if the sensor fails?

Treat it as a fault and repair it promptly. Without the sensor, rising back-pressure or a failed regeneration can go unnoticed until the engine is affected or the device is damaged. The fault, the repair and the date are recorded, and the readings are checked again after the repair.

Does fuel matter?

Yes. Fuel with high sulphur or contamination degrades catalysts and adds to the ash and soot the device must handle. Use fuel of the specified quality, keep the tank clean and free of water, and record deliveries, so a change in device behaviour can be traced to a fuel cause if needed.

General guidance only. Follow maker schedules.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.