Retrofitted Emission Control Devices (RECD) for Diesel Generator Sets

What RECD is, how retrofit emission control on existing diesel generators works (oxidation catalyst, DPF, SCR), what it can and cannot achieve, and the checks before fitting one.

In short. A retrofitted emission control device (RECD) is aftertreatment added to the exhaust of an existing diesel generator. It usually has an oxidation catalyst and a particulate filter, and sometimes a NOx reduction stage using urea. It works only if the engine is sound, the exhaust gets hot enough for the filter to clean itself (or active cleaning is provided), and the added back-pressure stays within the engine maker’s limit. Approval requirements should be confirmed for the site.

Who this page is for: For owners and facility managers considering an emission control device for an existing generator.

Key facts

  • The oxidation catalyst cuts carbon monoxide and hydrocarbons.
  • The particulate filter traps soot and must be cleaned by heat or service.
  • Ash from lubricating oil does not burn off; filters need periodic cleaning.
  • Back-pressure rises as the filter loads; it must stay below the engine limit.
  • Low-load standby duty often keeps the exhaust too cool for self-cleaning.
  • Fuel and oil quality affect device life.

Stages and their jobs

StageJob
Oxidation catalystConverts carbon monoxide and hydrocarbons; helps the filter burn soot
Particulate filterTraps soot in porous walls
NOx reduction with urea (optional)Reduces NOx to nitrogen and water
Sensors and controllerTemperature, back-pressure and alarms

Worked example: back-pressure budget (illustrative)

ItemClean filterLoaded filter
Silencer3.0 kPa3.0 kPa
Piping and bends2.0 kPa2.0 kPa
Catalyst and filter2.0 kPa5.0 kPa
Total against a 10 kPa engine limit7.0 kPa (70%)10.0 kPa (100%)

The design was acceptable only with an alarm at about 8.5 kPa, so the filter is cleaned before it reaches the limit. A shorter exhaust run would have given more margin. See selection and compatibility and installation.

Do not design for a clean filter only. Check back-pressure with the filter loaded, and set an alarm before the engine limit.

Duty and self-cleaning

DutyExhaust temperatureApproach
Steady prime duty at good loadUsually high enoughPassive cleaning
Standby with short runsOften too lowActive cleaning or periodic load-bank runs
Very light loadLowReconsider device or duty

See operation and maintenance.

First check sheet

ItemValue Example: the 500 kVA standby set on this page (illustrative)
Engine make, model, year  Use the nameplate and engine plate of the actual set
Hours per year and typical load  About 120 hours a year; tests at light load, outages at 35 to 45%
Engine back-pressure limit  10 kPa, from the engine maker’s datasheet
Oil consumption  Recorded against fuel at each service; a rising trend is repaired first

How each stage works, and what it needs

StageWhat happens insideWhat it needs from the engine
Diesel oxidation catalystCarbon monoxide and unburnt hydrocarbons are oxidised on a precious-metal coating; some nitric oxide becomes nitrogen dioxide, which later helps burn sootExhaust above its light-off temperature, typically around 200 to 250 °C, and low-sulphur fuel
Diesel particulate filterExhaust passes through porous ceramic walls that trap soot; soot is burnt off by heat (regeneration), while ash stays behindEnough time at high exhaust temperature for passive regeneration, or an active system that adds heat
NOx reduction with ureaUrea solution injected into the exhaust forms ammonia, which reduces nitrogen oxides on a catalyst; a small slip catalyst removes excess ammoniaExhaust within the catalyst’s working window, correct urea quality and a dosing system that is kept filled
Sensors and controllerInlet and outlet temperatures, differential pressure across the filter, alarms and a running logA display and alarm path that someone actually reads

The common thread is temperature. Every stage works best when the engine is properly loaded, which is why the duty of the set matters more than the brochure of the device.

Worked example: will a standby set clean itself? (illustrative)

A 500 kVA standby set runs about 120 hours a year: a 30-minute test each month at light load, and outages of one to three hours at 35 to 45% load. A temperature logger at the device inlet for a quarter of a year shows how its running hours divide:

Operating conditionShare of running hoursFilter behaviour
Monthly test at light loadabout 5%Soot collects; no regeneration
Outages at 35 to 45% loadabout 70%Exhaust below the passive regeneration range most of the time
Outages with heavy afternoon loadabout 25%Some passive regeneration

With three-quarters of its hours too cool, this set will load its filter faster than it cleans it. The choices are an active system that adds heat, a monthly test moved onto a load bank at a substantial share of rating so the filter regenerates on schedule, or a different device or duty. Logging first, before buying, is what turns this from a guess into a decision.

Reading the back-pressure trend

The back-pressure budget on this page shows 7.0 kPa with a clean filter against a 10 kPa engine limit, with an alarm at about 8.5 kPa. The 1.5 kPa between clean and alarm is the filter’s working range. If the differential pressure across the filter rises by about 0.05 kPa for every running hour on this duty, the alarm is reached in about 30 running hours, a few outages, so the cleaning plan is set by the trend, not by the calendar. A trend that rises faster after a service points to an engine fault rather than to the filter.

Ash, oil and the engine behind the device

Soot burns; ash does not. Ash comes mainly from lubricating oil burnt in the cylinders, so an engine that burns more oil fills its filter with ash faster. An engine using 0.1 litres of oil an hour with oil of about 1% ash leaves roughly 0.9 grams of ash an hour, about 440 grams over 500 hours; double the oil consumption and the ash doubles too. The filter is removed and cleaned of ash on the maker’s schedule, and the oil consumption is recorded at every service so that a rising trend is caught early.

Before a device is fitted, the engine itself is checked:

  • Oil consumption against fuel used, recorded over several services.
  • Crankcase blow-by and breather condition.
  • Injector condition and visible smoke on load.
  • Exhaust leaks upstream of the device, which upset its sensors.
  • The engine maker’s back-pressure limit, from the datasheet rather than an assumption.

A tired engine fouls a new device within months. Repairing the engine first, or choosing a replacement set, is often the better use of the budget.

Commissioning and records

At commissioning the set is run on a load bank across its load range while inlet and outlet temperatures, differential pressure and smoke are recorded, and the alarm setpoints are proved. Those readings become the baseline. Every later service records the same figures, the oil consumption and any cleaning, so that the owner can show the device is working and the next engineer can see at a glance whether anything has changed.

Passive or active regeneration

ApproachHow soot is removedSuitsCost of ownership
PassiveBurnt off continuously by exhaust heat, helped by nitrogen dioxide from the catalystPrime and continuous duty at good loadLowest, if the duty really is hot enough
Active, fuel dosing or burnerExtra heat added when back-pressure risesMixed duty with some light-load runningFuel for each regeneration and a more complex controller
Active, electric heaterFilter heated electrically, often off-line or during a scheduled runStandby sets with short, light runsElectrical supply and scheduling discipline
Off-line cleaningFilter removed and cleaned in a furnace or by a service providerVery low running hoursDowntime and a spare filter, or planned windows

The choice follows the temperature log, not the price list. A passive device on a cool standby set is the most common and most expensive mistake in this field, because it works on paper and blocks in practice.

Living with a urea stage

Where a NOx reduction stage is fitted, the urea solution becomes another consumable to manage. It is bought to the specified quality, stored sealed, out of direct sun and away from heat, because it degrades faster in hot storage, and used within its shelf life. The dosing tank is kept filled and its level recorded with fuel and oil, and the dosing lines and nozzle are inspected at each service. A system run without urea, or with poor-quality solution, stops reducing NOx and can damage its catalyst.

What to record at every run

  • Running hours and load, from the controller.
  • Device inlet and outlet temperatures, and the differential pressure across the filter.
  • Any alarms and any regeneration events.
  • Urea level and quantity added, where fitted.
  • Oil added since the last record.

Five lines in a log book, kept from the first day, are what let the owner show that the device is doing its job and let the engineer see a problem forming weeks before it becomes a blocked filter. For the wider decision between fitting a device and replacing or converting the set, see the RECD, dual-fuel or replacement decision tool.

Space, weight and the exhaust run

A device is heavier and longer than the silencer it often sits beside, and it needs access for sensor replacement and filter removal. On a canopy set the device may sit on the roof of the canopy or on a separate frame; in a plant room it sits in the exhaust run, where its weight must be carried by supports, not by the engine’s exhaust outlet or flexible bellows.

Insulating the pipe between the engine and the device keeps the exhaust hotter at the filter, which helps regeneration, and keeps the room cooler. The added length and bends count in the back-pressure budget, so the route is drawn and checked before the device is ordered.

Where the set stands outdoors in a canopy, the device and its sensors are also protected from rain entering the outlet, with a rain cap or a downward-turned outlet, because water in a hot filter or a wet sensor connector is a common cause of false alarms after the first monsoon.

Common mistakes

  • Design for a clean filter only.
  • Standby sets that never get hot.
  • Worn engines fouling the device.
  • No back-pressure alarm.

What to send us

Send the engine details, hours and load profile. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Values are illustrative; use the engine maker’s back-pressure limit.

Questions engineers ask

Why does a standby generator struggle with a particulate filter?

Because short runs at light load keep the exhaust too cool for the filter to burn off its soot. In the example on this page three quarters of the running hours are too cool, so the set needs an active system that adds heat, scheduled load-bank runs or a different device or duty.

Why does oil consumption matter for an emission control device?

Ash in the filter comes mainly from lubricating oil burnt in the engine, and ash does not burn off. An engine using 0.1 litres of oil an hour leaves roughly 440 grams of ash in 500 hours; double the oil use and the ash doubles, so cleaning is needed sooner.

Does RECD make an old set equal to a new one?

Not necessarily. The result depends on the engine condition, the device and the duty, and it has to be verified by measurement after fitting. A worn engine with high oil consumption fouls a new device quickly, so repairing or replacing the engine can be the better use of the budget.

Does it affect engine performance?

It can. The device adds back-pressure, which must stay below the engine maker limit with the filter loaded, not only when clean. The example on this page uses 7 kPa of a 10 kPa limit when clean, with an alarm at about 8.5 kPa so the filter is cleaned in time.

Is approval needed?

Approval and testing requirements depend on the location, the set and the applicable rules, so confirm them with the relevant authority and the device supplier before purchase. Keep the test reports and commissioning records, because they are what an inspection or an audit will ask to see first.

Is maintenance heavy?

Filters and sensors need regular attention. Back-pressure and temperatures are read at every run, ash is cleaned out of the filter on the maker schedule, urea quality is checked where a NOx stage is fitted, and oil consumption is recorded at each service to catch engine problems early.

General guidance only. Confirm approvals and test data.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.