In short. Critical power systems have several sources: transformer, generator, UPS and sometimes battery storage. Each needs a correct neutral-to-earth connection for every switching state. The neutral must be earthed at the right point, and only at that point, for whichever source is supplying the load. Changeover switching, three-pole or four-pole, decides whether that is possible. A wrong arrangement causes nuisance earth-fault trips or, worse, a floating neutral.
Who this page is for: For consultants, electrical engineers and facility managers with generators, UPS or several sources on one site.
Key facts
- Each supply arrangement needs one neutral-to-earth connection.
- Earthing the neutral at both transformer and generator with a three-pole changeover creates a parallel path.
- That parallel path makes earth-fault relays see normal neutral current.
- A four-pole changeover lets each source have its own neutral earth.
- A UPS with an isolating transformer needs its own neutral earth.
- Check earthing in every source and switching state.
Worked example: nuisance earth-fault trips (illustrative)
| Finding | Effect | Fix |
|---|---|---|
| Neutral earthed at both transformer and generator | Normal neutral current split through the earth path | Changeover replaced with four-pole switching |
| Three-pole changeover | Generator neutral permanently joined to the mains neutral, so the two earth links were in parallel | Only the connected source’s earthed neutral now serves the load |
| Earth-fault relay on the incomer saw about 30 A of normal neutral current | Trips whenever single-phase load was unbalanced | Trips stopped after the change |
See earthing studies and transfer coordination.
Do not remove a neutral-to-earth link to stop nuisance trips without checking every source. A source with no neutral earth can leave the neutral floating, so earth faults may not trip and exposed metalwork can become live.
Arrangements compared
| Arrangement | Neutral earth point | Notes |
|---|---|---|
| Three-pole changeover, one earth point at main board | Common point | Simple; generator must not have its own link |
| Four-pole changeover, each source earthed | At each source | Earth-fault protection works on each source |
| UPS with isolating transformer | At UPS output | Treated as a new source |
In an island, the neutral must stay earthed through the source running at the time, or through the common earth point where that is the design. See islanded operation.
Neutral earthing sheet
| Source | Neutral earthed where? | Changeover poles | Earth-fault protection works? |
|---|---|---|---|
| Transformer | |||
| Generator | |||
| UPS output |
What actually makes an earth fault safe
In a system where the neutral is earthed at the source, a fault from a phase conductor to a metal enclosure drives current back to the source through the protective conductors, and that current trips the breaker. What makes the fault safe is that loop: a protective conductor of low enough impedance, continuous from the enclosure back to the source’s neutral-earth bond, so that the fault current is large enough to trip the protection quickly, and every exposed metal part bonded together so that people cannot touch two parts at very different voltages while it does.
The earth electrode, the rod or mat in the ground, plays little part in clearing such a fault; the current does not flow through the soil. Its jobs are different: it ties the installation to the general mass of earth, so that the system does not float at an unknown voltage; it gives lightning and surge currents a path; and in a TT system, where the installation’s earth is independent of the supply, it is the return path, which is why TT systems need residual-current devices.
A low electrode resistance is valuable, but on a TN system it is not what protects people from an indirect contact, and chasing a lower figure while the protective conductors are undersized or discontinuous misses the point.
The separate “clean earth” that is not safe
A persistent request on sites with sensitive electronics is for a separate, “clean” earth electrode for the computer or instrument equipment, unconnected to the main electrical earth, in the hope of keeping electrical noise out of it. It does the opposite of what is intended and creates a hazard. During a fault or a lightning surge, the main earth and the isolated electrode can rise to very different voltages, and any equipment connected to both — through its power supply on one and its data cable or chassis on the other — sits across that difference, which can destroy the equipment and endanger anyone touching it.
The correct arrangement is a single earthing system with every electrode and every earth bar bonded together, and noise managed by other means: a dedicated, well-routed protective conductor to sensitive equipment, an isolation transformer with an earthed screen creating a new neutral-earth bond close to the load, and good cable segregation. If a separate electrode already exists, it should be bonded to the main earthing terminal, not removed, and the reason recorded so that it is not disconnected again.
Will the protection still disconnect on generator?
Every final circuit must disconnect within a set time when a fault occurs between a phase and an exposed metal part, typically 0.4 seconds for final circuits feeding socket outlets and portable equipment and 5 seconds for distribution circuits. On the mains, with plenty of fault current, a miniature circuit breaker trips on its magnetic element well within that time. On a generator the fault current is much smaller, and the check has to be repeated.
A 32 A type C breaker needs up to 10 times its rating, 320 A, to trip on its magnetic element; at 230 V that requires a total fault loop impedance no higher than about 0.72 Ω, including the source.
A 100 kVA generator with a rated current of about 139 A that can sustain around three times rated current in a fault delivers about 417 A at its terminals, less at the end of a long final circuit — enough for the 32 A breaker if the cable is short, not enough for a 63 A one, which needs 630 A. Where the magnetic element will not operate on generator, the protection relies on the breaker’s thermal element, which may take far longer than 0.4 seconds. The common remedy on final circuits is residual-current protection, which trips on a small earth leakage current regardless of the source’s fault capacity, and which many installations need anyway for additional protection.
Earthing a hired or portable generator
A hired generator connected to an installation brings its own earthing question. Many portable and hire sets are supplied with their neutral bonded to their frame inside the set, so that they are safe when used alone. When such a set is connected to an installation that already has its own neutral-earth bond at the main board, the result is two bonds and a parallel path for neutral current through the earth conductors, with the same nuisance trips and safety doubts as any other double bond.
The connection procedure must therefore settle the earthing each time: whether the set’s internal link is to be removed and the installation’s bond used, or the installation’s changeover switches the neutral so that the set’s own bond applies while it is connected. The set’s frame must be bonded to the installation’s main earthing terminal in either case. A connection point designed for hired sets, with the earthing arrangement fixed and labelled, removes the decision from the day of the outage, when it is most likely to be made in a hurry.
Measurements that prove the earthing in every state
The earthing of a multi-source installation changes with the switching state, and the only way to know it is right in each is to measure it in each. A short set of readings, taken on mains, on generator and in any other state the changeover allows, shows whether there is one bond or several and whether the protective conductors are sound.
| Measurement | Where | What a good result looks like |
|---|---|---|
| Current in the main earthing conductor, with a clamp meter | Between the neutral-earth bond and the main earth bar | Near zero with no fault; a steady current means neutral current is returning through earth |
| Neutral-to-earth voltage | At the critical distribution boards, under load | A few volts, steady, similar in each source state |
| Earth fault loop impedance | At the farthest outlet of each critical final circuit | Within the limit for the breaker, on the source with the lowest fault capacity |
| Continuity of protective conductors | From each critical board back to the main earthing terminal | Low and consistent with the conductor size and length |
Record the readings for each state on the neutral earthing sheet, and repeat them after any change to the changeover, the generator connection or the main switchboard. A steady current in the earthing conductor on generator that is absent on mains, or the reverse, is the single most useful sign that the bonding arrangement is not what the drawings say.
An earthing drawing, separate from the single-line diagram
Most single-line diagrams show phases and breakers clearly and the neutral and earth hardly at all, which is why so many earthing problems survive design review. A separate earthing schematic, one page, removes that blind spot. It shows every source with its neutral-earth bond and where that bond physically is; the number of poles on every changeover, transfer switch and tie; every earth electrode and how it is bonded to the main earthing terminal; the protective conductors to each critical board; and every UPS, isolation transformer or other device that creates a new neutral.
Two labels on site complete it. At every neutral-earth link, a durable label states what the link is and that it must not be removed without reference to the drawing. At every changeover, a label states whether it switches the neutral. With the drawing in the switchroom and the labels in place, the person who later connects a hired set, replaces a changeover or adds a UPS can see at once how the earthing works, and does not have to discover it by tripping something.
Common mistakes
- Neutral earthed at two points with a three-pole changeover.
- Links removed to stop trips.
- UPS output neutral not earthed.
- Earthing checked on mains only.
What to send us
Send the single-line diagram with neutral and earthing details. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. The example is illustrative.
Questions engineers ask
Is a separate clean earth for computer equipment a good idea?
No. An earth electrode not bonded to the main earthing system can rise to a very different voltage from it during a fault or a lightning surge, and equipment connected to both through its power supply and its data cables sits across that difference, which can destroy it and endanger people. Use one bonded earthing system, and manage noise with dedicated protective conductors, isolation transformers with earthed screens and good cable segregation.
How should a hired generator be earthed when connected to a site?
With exactly one neutral-to-earth bond for the system that is running. Many hire sets have their neutral bonded to the frame inside, so connecting one to an installation that already has its own bond creates a double bond and neutral current in the earth conductors. Either remove the set link and use the installation bond, or switch the neutral at the changeover so the set bond applies. Bond the set frame to the main earthing terminal in either case.
Should the generator neutral be earthed?
It depends on the system. With a switched neutral, each source is earthed in turn. With a solid neutral, earth at one point. Follow the design and applicable standards. The arrangement decides whether the changeover is three-pole or four-pole and where earth fault protection measures current, so it is fixed in the design and checked on site before energising.
Why do I need a four-pole ATS?
To switch the neutral with the phases so each source keeps its own earth reference without creating parallel neutral paths. Parallel neutral paths split the neutral current between the earth and neutral conductors, which can cause earth fault relays to trip falsely and leave current on earth conductors, so a four-pole changeover is used wherever each source has its own neutral earth bond.
Why do ground-fault relays trip falsely on generator?
A second neutral-earth bond or unbalanced neutral current can create a residual that mimics a fault. A test with the generator on load, while measuring current in the earth and neutral conductors, shows whether neutral current is returning on the earth path. Removing the extra bond, or changing to a four-pole changeover, usually cures the false trips.
Does a UPS change the earthing?
It can, especially with an isolation transformer. Define it at each stage. An isolation transformer creates a separately derived system that needs its own neutral earth bond, while a UPS without one passes the upstream earthing through. The single-line diagram shows the earthing at each stage, and earth fault protection is set to match.
Earthing must comply with applicable electrical codes. Confirm with a qualified engineer.