In short. Two mains feeders improve availability only if they are genuinely independent. If both come from the same substation or the same transformer, or share a cable route, one event can take out both. A dual-utility scheme needs a known upstream topology, an automatic changeover or main-tie-main arrangement, and usually a generator as well, because some outages hit both feeders.
Who this page is for: For owners and consultants of large sites deciding whether a second utility feeder is worth it and how to connect it.
Key facts
- Find out where each feeder comes from: substation, transformer and route.
- Feeders from one substation share its outages.
- Automatic changeover between feeders needs interlocks and timing.
- Paralleling the two feeders needs the utility’s permission and higher fault ratings.
- A second feeder reduces generator running hours but rarely replaces it.
- Track outages by cause to judge the real benefit.
Worked example: one year of outages (illustrative)
| Outage cause | Events | Covered by second feeder from same substation? | Covered by feeder from another substation? |
|---|---|---|---|
| Feeder fault or maintenance | 14 | Yes | Yes |
| Substation outage | 2 | No | Yes |
| Wide grid disturbance | 1 | No | Possibly not |
A second feeder from the same substation would cover 14 of 17 events. One from another substation would cover 16. The generator stays for the rest, but it now runs far less. See main-tie-main distribution.
Do not treat two incoming cables as two independent supplies until the utility confirms where each comes from. Shared substations, transformers and routes are common.
Connection schemes
| Scheme | Behaviour |
|---|---|
| Manual changeover | Break while someone switches |
| Automatic changeover | Break of seconds; interlocked |
| Main-tie-main, tie normally open | Each feeder supplies half; tie closes if one fails, so each feeder and transformer must carry the whole load, or some loads must be shed |
| Feeders in parallel | No break, but utility approval and higher fault level |
See source hierarchy and short-circuit studies.
Feeder independence sheet
| Item | Feeder A | Feeder B | Shared? |
|---|---|---|---|
| Substation | |||
| Transformer | |||
| Cable route | |||
| Outages last year |
What a second feeder is worth, in hours
The benefit of a second utility feeder depends almost entirely on how many of its outages it shares with the first. Take two feeders, each interrupted 12 times a year for an average of 45 minutes. Each is unavailable for about 9 hours a year. If their outages were completely independent, both would be off together for only about 33 seconds a year on average, and a second feeder would look like a near-perfect remedy.
Real feeders are rarely independent. Outages on the upstream grid, at the shared substation or on the transmission system that feeds it, take out both together. If 3 of each feeder’s 12 annual outages come from such shared causes, at the same 45 minutes each, the site loses both feeders together for about 2.25 hours a year — hundreds of times the independent figure, and the shared events are the only ones that matter. The second feeder still removes most outages, which is valuable, but it does not remove the ones that come from upstream, and those are often the longest.
| Shared outages a year, 45 minutes each | Time both feeders are off together | What it means for the generator |
|---|---|---|
| None, fully independent | About 33 seconds | Rarely needed except for long events |
| 1 | About 45 minutes | Needed for each upstream event |
| 3 | About 2.25 hours | Needed several times a year, as it would be with one feeder for long events |
The utility’s outage records for each feeder, with their causes, are the information that decides this, and they are worth asking for before the second connection is designed. A second feeder from a different substation, fed from a different transmission point, shares far fewer outages than one from the same substation’s other bus, and the difference in benefit is usually larger than the difference in connection effort.
The shared events also tend to be the long ones. A local fault on one feeder is usually found and repaired within an hour or two; a failure at a grid substation, a transmission tripping or a planned shutdown of an upstream line can last much longer, and it removes both feeders together.
That is why a second feeder reduces how often a site’s generator runs much more than it reduces how long the generator must be able to run when it does. The generator, its fuel stock and its refuelling plan should still be sized for the longest outage the site expects, not for the shortened list of events that remain once the second feeder is connected.
Utility auto-reclose and the site’s transfer delay
Many overhead distribution feeders are protected with auto-reclosing breakers: after a fault, the breaker opens and then recloses automatically after a short dead time, because most overhead faults — a branch touching a line, a bird, a lightning flash — clear themselves. A single reclose after a fraction of a second to a few seconds is common, sometimes followed by further attempts with longer dead times before the breaker locks out.
The site’s automatic changeover between feeders has to be set with that behaviour in mind. If the transfer delay is shorter than the first dead time, the site transfers to the second feeder on every reclosing event, then transfers back when the first feeder is proven healthy, adding two transfers for an interruption the feeder would have cleared by itself.
If the delay is longer than the first dead time but shorter than the full reclose sequence, the site rides out most transient faults and still transfers promptly for a permanent one. Ask the utility for the reclose settings on each feeder, and set the transfer delay against them rather than at a default. Loads that cannot tolerate the dead time belong on a UPS whatever the transfer setting.
Three ways to move between feeders
The transfer between two utility feeders can be made in three ways, and they differ in the break the load sees, in what they ask of the switchgear and in what the utility must agree to.
| Transfer | Break seen by the load | Requirements |
|---|---|---|
| Open transition, with delays | The confirmation delay plus switching time, typically a few seconds | Interlocks; delays set against the utility’s reclose times |
| Fast open transition | A fraction of a second, with a check on the residual voltage of running motors | Fast-acting breakers and a transfer relay; motor loads considered |
| Closed transition | None; the feeders are paralleled for a moment | Utility agreement, switchgear rated for the combined fault level, synchronising check, strict time limit |
For most sites the first is the right choice, with a UPS covering the loads that cannot accept its break. The fast transfer suits large motor loads that would otherwise stop and need restarting, provided the residual-voltage check is in place to prevent damaging out-of-phase reclosing. The closed transition is reserved for planned transfers, such as returning to the preferred feeder after it has been restored, and only where the utility permits it.
Protection between two utility incomers
With two incoming feeders, a site creates a possible path from one feeder to the other through its own switchboard. If the interlocks fail, or a transfer scheme parallels the feeders without the utility’s agreement, current can flow from one utility feeder into the other through the site, feeding a fault on the other feeder or energising a line the utility believes is dead. The protection at the site incomers must therefore include more than overcurrent.
Typical additions are a directional overcurrent or reverse-power function on each incomer, which trips if power flows out of the site towards a feeder; mechanical and electrical interlocks that prevent both incomers being closed with the tie closed; and, where any closed-transition transfer is permitted, a strict time limit on paralleling with a backup trip. The utility usually specifies what it requires at its connection points, and its requirements override the site’s preferences. A test of each of these functions at commissioning, witnessed where the utility asks for it, completes the arrangement.
How the second feeder is brought into the site
At medium-voltage sites, the two feeders usually arrive at a ring main unit or a small switchboard ahead of the site transformers. Two arrangements are common. In the first, each feeder supplies its own transformer, and the two transformers feed the two halves of a double-ended low-voltage board; the transfer happens on the low-voltage side, as described on the main-tie-main page. In the second, both feeders arrive at one medium-voltage board with an automatic transfer between them, and a single transformer or pair of transformers is fed from whichever feeder is live.
The first arrangement also covers the failure of a transformer, because each half has its own; the second covers feeder outages but leaves the transformer as a single item unless it too is duplicated. The medium-voltage transfer in the second arrangement also requires switchgear and protection suited to that voltage, and its operation must follow the utility’s rules for its network. For most critical sites, the first arrangement gives more resilience for the same number of feeders.
Keeping an outage log that answers the question
Whether a second feeder was worth its connection is answered only by records. A simple log of every supply event at the site, kept from the day the second feeder is connected, makes it possible: the date and time, which feeder or feeders were affected, how long each event lasted, whether the transfer operated and how long it took, and the cause where the utility reports it.
After a year, the log shows how many events each feeder had, how many were shared, how many the transfer covered and how often the generator was still needed. That is the evidence for or against further investment, and the information the utility needs when the site asks for better service.
Common mistakes
- Assuming independence.
- No interlock between feeders.
- Removing the generator after adding a feeder.
- Fault ratings not checked for paralleled feeders.
What to send us
Send your supply details and outage records. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. The example is illustrative.
Questions engineers ask
How much does a second utility feeder reduce outages?
It depends on how many outages the two feeders share. Two feeders each off 12 times a year for 45 minutes would, if fully independent, both be off together for only about 33 seconds a year. If 3 of those outages come from shared upstream causes, the site loses both for about 2.25 hours a year. The second feeder removes most short local outages but not the upstream ones, which are often the longest, so the generator is still needed.
Why does the site change over to the second feeder and then straight back?
Usually because the transfer delay is shorter than the utility auto-reclose dead time. The feeder breaker opens on a transient fault and recloses automatically within a fraction of a second to a few seconds, but the site has already transferred and then transfers back once the first feeder is proven healthy. Ask the utility for the reclose settings and set the transfer delay to ride through the first reclose, with a UPS covering loads that cannot tolerate the dead time.
Is a dual utility supply enough without a generator?
Usually not for critical sites. Dual feeds protect against some local faults but not against grid-wide events or shared failures. A generator covers those cases. The second feed reduces how often the site depends on the generator, while the generator remains the source that does not rely on the grid at all.
What does main-tie-main mean?
Two incoming supplies, each with a main breaker, joined by a tie breaker between two bus sections. The tie is normally open and closes when one source fails. Each bus section then carries its own loads, and interlocks stop the tie from closing while both mains are closed, unless the utility permits that and protection is designed for it.
How can I check whether two feeders are independent?
Ask the utility for the single-line diagram and route details showing where the feeders come from, share substations or cross. Check that the customer-side switchgear and controls are also separate. Two feeders from one substation share its failures, and two cables in one trench share a single excavation fault.
When is closed-transition transfer between utility feeds allowed?
Only with the distribution utility’s permission and with synchronism checks and protection in place, because it briefly parallels two feeders. The parallel period is kept very short, the fault level during it is checked against the switchgear rating, and the permission and settings are recorded with the commissioning results.
This guide gives general principles. Utility arrangements and permissions vary by location and supplier.