100 kVA Generator Full-Load Current

In short. A 100 kVA generator delivers 139 A per phase at 415 V, three-phase, at 0.8 power factor — which is 80 kW and 60 kVAr. At 400 V the same set delivers 144 A and at 433 V it delivers 133 A. The figures below are the starting point for the protective device, the cables and the changeover; the page then works through what actually decides a set of this size, using published prime-rated data for CPCB-compliant sets of this rating.

Quick answers for a 100 kVA set

  • Full-load current at 415 V: 139 A per phase
  • Real power at 0.8 PF: 80 kW
  • Reactive power at 0.8 PF: 60 kVAr
  • Usual protective device: 200 A, MCCB, four-pole, set above 139 A
  • Diesel at full load: about 21.9 L/h
  • Per kVA at 415 V: about 1.39 A, so 100 × 1.39 ≈ 139 A

All figures are at the rated power factor of 0.8 on a 50 Hz set. Always confirm against the nameplate of the actual machine.

Full-load current at each supply voltage

Supply voltage Full-load current (A) Against 415 V Where it applies
380 V 3-phase 152 +9.2% Older and some imported equipment
400 V 3-phase 144 +3.8% Nominal European voltage; many nameplates
415 V 3-phase 139 reference Standard Indian LV supply
433 V 3-phase 133 −4.2% No-load and lightly loaded alternator setting

For the same kVA, current and voltage move in opposite directions. Nothing about the machine changes between these rows — only the voltage it is connected at.

How the 139 A is worked out

For a three-phase set the full-load current is

I = kVA × 1000 ÷ (√3 × V)

With 100 kVA at 415 V:

  1. √3 × 415 = 1.732 × 415 = 718.78
  2. 100 × 1000 = 100,000 VA
  3. 100,000 ÷ 718.78 = 139 A

The kW and kVAr follow from the power factor rather than from the formula: 100 × 0.8 = 80 kW of real power, and 100 × 0.6 = 60 kVAr of reactive power. Power factor does not appear in the current calculation at all: the set delivers 139 A at its rated kVA whatever the power factor of the load, but the kW it can deliver at that current changes completely.

What a 100 kVA set is used for

A 100 kVA set carries a supermarket, a mid-sized hospital block, a factory office with its canteen, or a large apartment complex. It is the largest rating below 125 kVA and the size at which owners most often ask whether one set or two smaller sets is the better arrangement.

Reading the 139 A figure properly

At 139 A per phase the current is still within moulded-case breaker territory, and the usual device is a 200 A unit. What decides a set of this size is more often the start of the largest motor, usually a lift or a pump, and the way loads are switched on after the set takes over, than the steady current itself.

The largest motor start

At this size the start of one motor, usually a lift or a pump, often decides the rating before the running load does. A motor started direct on line draws about six to seven times its running current for a second or two, and the set’s voltage dips while the alternator recovers.

Starting method Largest motor this set usually starts What changes
Direct on line about 11 kW (15 HP) Full starting current, deepest voltage dip
Star-delta about 22 kW Starting current cut to about a third
Soft starter about 27.5 kW Current held near three times full load
Variable speed drive about 48 kW Starting current close to running current

Usual pattern for a set of this rating with a voltage dip of about 15 to 20%. The motor and alternator makers’ data decide the actual case.

Lifts are the commonest case. A modern lift on a variable-frequency drive starts gently; an older lift with a direct-on-line or star-delta motor is a much heavier start, and an apartment block with two old lifts can need a larger set than its running load suggests.

Prime or standby: what the 100 kVA rating means

Sets of this size in India are normally sold on a prime rating: the set may run for unlimited hours at a varying load, and may carry about 10% more for a short period, typically one hour in twelve. A standby rating, for emergency use of around 200 hours a year, is usually about 10% higher on the same machine. Ask which one a quotation means.

Duty What it allows Rating Current at 415 V
Prime (normal offer) Unlimited hours, varying load 100 kVA, 80 kW 139 A
Prime, short overload About 10% more for a limited time about 110 kVA about 153 A
Standby Mains failure only, limited hours a year, no overload about 110 kVA about 153 A

The percentages are the usual pattern for this size range; the engine maker’s rating sheet for the actual set governs.

The machine behind the figure

Published prime-rated datasheets for CPCB-compliant 100 kVA sets give the following. Where two catalogue editions differ, both figures are shown as a range; other makes differ by a few percent.

Item Published figure
Engine 4 cylinders, 4.32 litres, turbocharged and aftercooled, 1500 rpm
Diesel at 100% load 21.9 L/h
Diesel at 75% load 16.9 L/h
Diesel at 50% load 12.2 L/h
Diesel per kWh at full load 0.274 L
Built-in fuel tank 230 litres
Running time on a full tank at 75% load about 13 hours

The diesel-per-kWh line is the one worth reading. At this size the engine is efficient enough that loading matters more than the rating: the same set at half load burns about 56% of its full-load diesel while delivering 50% of the power.

What the site does to the 139 A

Published ratings are quoted at reference conditions. Plant rooms, terraces and side passages in Telangana and Andhra Pradesh are hotter than the reference, and sets of this size are often installed in tight spaces where the radiator draws back its own hot air.

A derate in the region of 5 to 10% is common in regional summer conditions, which takes this set from 100 kVA to somewhere between 90 and 95 kVA, and the usable current at 415 V from 139 A to between 125 and 132 A. These are illustrative figures to show the size of the effect; the engine maker’s derating curve for the actual engine is what a design should use.

The practical consequence is the margin. Keep clear space around the canopy, do not let the hot air from the radiator loop back to the air intake, and keep the radiator fins clean. On a set of this size those three things decide whether it carries its plate in May.

Worked example

A supermarket with lighting, refrigerated display cases, billing, and air conditioning measures its peak evening demand. The measured result is 63.6 kW at 0.88 power factor.

  1. Load in kVA: 63.6 ÷ 0.88 = 72.3 kVA.
  2. Against the set’s kW limit: the engine is rated 80 kW, so the load uses 80% of rated kW.
  3. Current drawn: 72.3 × 1000 ÷ (1.732 × 415) = 101 A, against the set’s 139 A.
  4. Largest motor: check it against the table above before signing off.

So a 100 kVA set fits, at 80% of its kW rating, which is inside the 80% most owners plan to and leaves room for one more appliance. On a site that is expected to grow, the next rating up is the safer choice.

Does a 100 kVA set fit your site? A five-line check

Check Figure to use Pass if
1. Running kW Measured maximum demand in kW 64 kW or less for comfortable loading
2. Running kVA kW ÷ measured power factor 80 kVA or less
3. Largest motor started direct on line Motor kW About 11 kW (15 HP) or less, or use a soft starter or drive
4. Protective device Existing device and setting 200 A device, set above 139 A
5. Single-phase imbalance Heaviest phase against lightest Within about 10% of each other

Fail line 3 and the set is not too small for the load; it is too small for the start. That is a different fix and usually a cheaper one.

Common mistakes with a 100 kVA set

What to send us

If you are deciding whether a 100 kVA set is the right size, these five things let us answer properly rather than guess:

  1. Maximum demand in kW and the power factor it was measured at. Against this set the limits are 80 kW and 100 kVA, and which one binds depends on the power factor.
  2. The largest motor — pump, lift or AC unit — its rating, and how it is started.
  3. Single-phase or three-phase: the building’s electricity connection and how the essential loads are spread across the phases.
  4. Where the set will stand: terrace, basement, side passage or open yard, and the distance to the changeover.
  5. How the set will be used: a few hours of power cuts a week, daily shifts, or continuous running. The rating and the service plan follow from it.

Questions engineers ask

How many amps is a 100 kVA generator?

139 A per phase at 415 V, three-phase, at 0.8 power factor. At 400 V it is 144 A and at 433 V it is 133 A. The kW rating at the same power factor is 80 kW.

What breaker size suits a 100 kVA generator?

A 200 A four-pole MCCB is usual, set above the 139 A full-load current with margin for motor starting. The exact setting belongs to the protection coordination, because it has to protect the alternator and still ride through the largest start.

How many kW is a 100 kVA generator?

80 kW at the standard rated power factor of 0.8. The set must stay within both 80 kW and 100 kVA; whichever the load reaches first is the limit. For comfortable running, plan the load at about 64 kW.

How much diesel does a 100 kVA generator use per hour?

Published prime-rated figures are about 21.9 litres per hour at full load, 16.9 at 75% load and 12.2 at 50% load. Actual consumption follows the load, so a set running at half load uses close to the half-load figure.

What is the largest motor a 100 kVA set can start?

Direct on line, about 11 kW (15 HP) with a voltage dip the set recovers from. A larger motor needs star-delta, a soft starter or a drive, or a larger set. The motor and alternator data decide the actual case.

Full-load current at other ratings

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 23 November 2026.