In short. A 82.5 kVA generator delivers 115 A per phase at 415 V, three-phase, at 0.8 power factor — which is 66 kW and 49.5 kVAr. At 400 V the same set delivers 119 A and at 433 V it delivers 110 A. The figures below are the starting point for the protective device, the cables and the changeover; the page then works through what actually decides a set of this size, using published prime-rated data for CPCB-compliant sets of this rating.
Quick answers for a 82.5 kVA set
- Full-load current at 415 V: 115 A per phase
- Real power at 0.8 PF: 66 kW
- Reactive power at 0.8 PF: 49.5 kVAr
- Usual protective device: 160 A, MCCB, four-pole, set above 115 A
- Diesel at full load: about 18.8 L/h
- Per kVA at 415 V: about 1.39 A, so 82.5 × 1.39 ≈ 115 A
All figures are at the rated power factor of 0.8 on a 50 Hz set. Always confirm against the nameplate of the actual machine.
Full-load current at each supply voltage
| Supply voltage | Full-load current (A) | Against 415 V | Where it applies |
|---|---|---|---|
| 380 V 3-phase | 125 | +9.2% | Older and some imported equipment |
| 400 V 3-phase | 119 | +3.8% | Nominal European voltage; many nameplates |
| 415 V 3-phase | 115 | reference | Standard Indian LV supply |
| 433 V 3-phase | 110 | −4.2% | No-load and lightly loaded alternator setting |
For the same kVA, current and voltage move in opposite directions. Nothing about the machine changes between these rows — only the voltage it is connected at.
How the 115 A is worked out
For a three-phase set the full-load current is
I = kVA × 1000 ÷ (√3 × V)
With 82.5 kVA at 415 V:
- √3 × 415 = 1.732 × 415 = 718.78
- 82.5 × 1000 = 82,500 VA
- 82,500 ÷ 718.78 = 115 A
The kW and kVAr follow from the power factor rather than from the formula: 82.5 × 0.8 = 66 kW of real power, and 82.5 × 0.6 = 49.5 kVAr of reactive power. Power factor does not appear in the current calculation at all: the set delivers 115 A at its rated kVA whatever the power factor of the load, but the kW it can deliver at that current changes completely.
What a 82.5 kVA set is used for
An 82.5 kVA set is a small-factory and commercial-building size: a light-engineering unit with a few machines, a mid-sized office, or an apartment complex with several lifts and a sewage treatment plant. It uses a four-cylinder turbocharged engine and is the first size in this range where the start of a single motor rarely decides the rating on its own.
Reading the 115 A figure properly
At 115 A per phase the current is still within moulded-case breaker territory, and the usual device is a 160 A unit. What decides a set of this size is more often the start of the largest motor, usually a lift or a pump, and the way loads are switched on after the set takes over, than the steady current itself.
The largest motor start
At this size the start of one motor, usually a lift or a pump, often decides the rating before the running load does. A motor started direct on line draws about six to seven times its running current for a second or two, and the set’s voltage dips while the alternator recovers.
| Starting method | Largest motor this set usually starts | What changes |
|---|---|---|
| Direct on line | about 9.3 kW (12.5 HP) | Full starting current, deepest voltage dip |
| Star-delta | about 18.6 kW | Starting current cut to about a third |
| Soft starter | about 23.2 kW | Current held near three times full load |
| Variable speed drive | about 39.6 kW | Starting current close to running current |
Usual pattern for a set of this rating with a voltage dip of about 15 to 20%. The motor and alternator makers’ data decide the actual case.
Lifts are the commonest case. A modern lift on a variable-frequency drive starts gently; an older lift with a direct-on-line or star-delta motor is a much heavier start, and an apartment block with two old lifts can need a larger set than its running load suggests.
Prime or standby: what the 82.5 kVA rating means
Sets of this size in India are normally sold on a prime rating: the set may run for unlimited hours at a varying load, and may carry about 10% more for a short period, typically one hour in twelve. A standby rating, for emergency use of around 200 hours a year, is usually about 10% higher on the same machine. Ask which one a quotation means.
| Duty | What it allows | Rating | Current at 415 V |
|---|---|---|---|
| Prime (normal offer) | Unlimited hours, varying load | 82.5 kVA, 66 kW | 115 A |
| Prime, short overload | About 10% more for a limited time | about 90.8 kVA | about 126 A |
| Standby | Mains failure only, limited hours a year, no overload | about 90.8 kVA | about 126 A |
The percentages are the usual pattern for this size range; the engine maker’s rating sheet for the actual set governs.
The machine behind the figure
Published prime-rated datasheets for CPCB-compliant 82.5 kVA sets give the following. Where two catalogue editions differ, both figures are shown as a range; other makes differ by a few percent.
| Item | Published figure |
|---|---|
| Engine | 4 cylinders, 4.16 litres, turbocharged and aftercooled, 1500 rpm |
| Diesel at 100% load | 18.8 L/h |
| Diesel at 75% load | 13.8 L/h |
| Diesel at 50% load | 10.3 L/h |
| Diesel per kWh at full load | 0.285 L |
| Built-in fuel tank | 150 litres |
| Running time on a full tank at 75% load | about 10 hours |
The diesel-per-kWh line is the one worth reading. At this size the engine is efficient enough that loading matters more than the rating: the same set at half load burns about 55% of its full-load diesel while delivering 50% of the power.
What the site does to the 115 A
Published ratings are quoted at reference conditions. Plant rooms, terraces and side passages in Telangana and Andhra Pradesh are hotter than the reference, and sets of this size are often installed in tight spaces where the radiator draws back its own hot air.
A derate in the region of 5 to 10% is common in regional summer conditions, which takes this set from 82.5 kVA to somewhere between 74.2 and 78.4 kVA, and the usable current at 415 V from 115 A to between 103 and 109 A. These are illustrative figures to show the size of the effect; the engine maker’s derating curve for the actual engine is what a design should use.
The practical consequence is the margin. Keep clear space around the canopy, do not let the hot air from the radiator loop back to the air intake, and keep the radiator fins clean. On a set of this size those three things decide whether it carries its plate in May.
Worked example
A light-engineering unit with lathes, a tool room, lighting and the office measures its first-shift demand. The measured result is 52.4 kW at 0.86 power factor.
- Load in kVA: 52.4 ÷ 0.86 = 60.9 kVA.
- Against the set’s kW limit: the engine is rated 66 kW, so the load uses 79% of rated kW.
- Current drawn: 60.9 × 1000 ÷ (1.732 × 415) = 84.8 A, against the set’s 115 A.
- Largest motor: check it against the table above before signing off.
So a 82.5 kVA set fits, at 79% of its kW rating, which is inside the 80% most owners plan to and leaves room for one more appliance. On a site that is expected to grow, the next rating up is the safer choice.
Does a 82.5 kVA set fit your site? A five-line check
| Check | Figure to use | Pass if |
|---|---|---|
| 1. Running kW | Measured maximum demand in kW | 52.8 kW or less for comfortable loading |
| 2. Running kVA | kW ÷ measured power factor | 66 kVA or less |
| 3. Largest motor started direct on line | Motor kW | About 9.3 kW (12.5 HP) or less, or use a soft starter or drive |
| 4. Protective device | Existing device and setting | 160 A device, set above 115 A |
| 5. Single-phase imbalance | Heaviest phase against lightest | Within about 10% of each other |
Fail line 3 and the set is not too small for the load; it is too small for the start. That is a different fix and usually a cheaper one.
Common mistakes with a 82.5 kVA set
- Reading 82.5 kVA as 82.5 kW. The engine is rated 66 kW. A 72.6 kW load is outside the set even though the kVA figure looks generous.
- Ignoring the lift start. A lift motor started direct on line, or a lift drive without a soft start, can draw several times its running current. Check the largest motor against the set before the load total.
- Setting the generator breaker for the cable rather than the alternator. The breaker protects the alternator first. A setting chosen for the cable can leave the set unprotected against a sustained overload or fault.
What to send us
If you are deciding whether a 82.5 kVA set is the right size, these five things let us answer properly rather than guess:
- Maximum demand in kW and the power factor it was measured at. Against this set the limits are 66 kW and 82.5 kVA, and which one binds depends on the power factor.
- The largest motor — pump, lift or AC unit — its rating, and how it is started.
- Single-phase or three-phase: the building’s electricity connection and how the essential loads are spread across the phases.
- Where the set will stand: terrace, basement, side passage or open yard, and the distance to the changeover.
- How the set will be used: a few hours of power cuts a week, daily shifts, or continuous running. The rating and the service plan follow from it.
Next step: work your own load through the generator kVA and kW sizing calculator, then send an enquiry with the five items above and we will confirm the rating in writing.
Questions engineers ask
How many amps is a 82.5 kVA generator?
115 A per phase at 415 V, three-phase, at 0.8 power factor. At 400 V it is 119 A and at 433 V it is 110 A. The kW rating at the same power factor is 66 kW.
What breaker size suits a 82.5 kVA generator?
A 160 A four-pole MCCB is usual, set above the 115 A full-load current with margin for motor starting. The exact setting belongs to the protection coordination, because it has to protect the alternator and still ride through the largest start.
How many kW is a 82.5 kVA generator?
66 kW at the standard rated power factor of 0.8. The set must stay within both 66 kW and 82.5 kVA; whichever the load reaches first is the limit. For comfortable running, plan the load at about 52.8 kW.
How much diesel does a 82.5 kVA generator use per hour?
Published prime-rated figures are about 18.8 litres per hour at full load, 13.8 at 75% load and 10.3 at 50% load. Actual consumption follows the load, so a set running at half load uses close to the half-load figure.
What is the largest motor a 82.5 kVA set can start?
Direct on line, about 9.3 kW (12.5 HP) with a voltage dip the set recovers from. A larger motor needs star-delta, a soft starter or a drive, or a larger set. The motor and alternator data decide the actual case.
Full-load current at other ratings
- 5 kVA — 7.0 A at 415 V
- 7.5 kVA — 10.4 A at 415 V
- 10 kVA — 13.9 A at 415 V
- 12.5 kVA — 17.4 A at 415 V
- 15 kVA — 20.9 A at 415 V
- 20 kVA — 27.8 A at 415 V
- 25 kVA — 34.8 A at 415 V
- 30 kVA — 41.7 A at 415 V
- 40 kVA — 55.6 A at 415 V
- 45 kVA — 62.6 A at 415 V
- 50 kVA — 69.6 A at 415 V
- 62.5 kVA — 87.0 A at 415 V
- 75 kVA — 104 A at 415 V
- 100 kVA — 139 A at 415 V
- 125 kVA — 174 A at 415 V
- 250 kVA — 348 A at 415 V
- 320 kVA — 445 A at 415 V
- 750 kVA — 1043 A at 415 V
- 1010 kVA — 1405 A at 415 V
- 1250 kVA — 1739 A at 415 V
- 1500 kVA — 2087 A at 415 V
- 2000 kVA — 2782 A at 415 V
- Every rating from 7.5 to 3000 kVA — the full chart
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 23 November 2026.