Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

DG Set Foundation and Anti-Vibration Mounting: Sizes, Concrete and Levelling

In short. A generator foundation has three jobs. It carries the set’s weight without settling. It is heavy and stiff enough that the set’s vibration does not travel into the building. It holds the skid level so that the engine and alternator stay aligned. For most canopy sets on firm ground this means a reinforced concrete block of M20 grade or better, weighing 1.5 to 2.5 times the set’s wet weight, extending 150–300 mm beyond the skid on every side, isolated from the surrounding floor and level to within about 1 mm per metre. Pair it with correctly loaded anti-vibration mounts and give the concrete at least seven days to cure before the set goes on.

Who this page is for: civil and electrical contractors, consultants, facility engineers and owners preparing a plinth for a new or relocated set, from a 7.5 kVA canopy set on a terrace to a 2,000 kVA set in a plant room.

Key facts

What the foundation must achieve

Carry the load without settlement

The total load is the set’s wet weight (with oil, coolant and a full base tank) plus the foundation’s own weight. On natural ground this is checked against the soil’s safe bearing capacity. Most firm soils in the Deccan plateau, including the murram and weathered rock common around Hyderabad, carry far more than a generator foundation imposes. Black cotton soil, filled ground and made-up plots need a structural engineer’s advice, because they swell, shrink and settle unevenly.

Resist and absorb vibration

A mass of concrete larger than the set acts as an inertia block. It lowers the amplitude of any vibration that passes through the mounts and stops the slab around it from ringing. A foundation that is too light, or that is cast as part of the building floor, becomes a loudspeaker for the engine.

Hold the set level and true

The engine and alternator are aligned at the factory on a common base frame. A foundation that is out of level, or that twists the frame when bolted down, puts stress on the coupling and alternator bearings. Uneven support also loads some anti-vibration mounts more than others, which spoils their isolation.

Sizing the foundation

Work through four quantities in order: plan size, required mass, depth, and bearing pressure.

  1. Plan size. Take the skid (base frame) length and width from the maker’s general-arrangement drawing and add 150–300 mm on every side. Use the larger margin for bigger sets and where service access is tight.
  2. Required mass. Foundation mass = 1.5 to 2.5 × set wet weight. Use the upper end for sets without integral mounts and for buildings sensitive to vibration. On upper floors the slab’s capacity governs instead; see the terrace section below.
  3. Depth. Depth = required mass ÷ (2,400 kg/m³ × plan area). Round up to a practical figure, usually in 50 mm steps.
  4. Bearing pressure. (Set weight + foundation weight) × 9.81 ÷ plan area, in kN/m². Compare this with the soil’s safe bearing capacity.

Worked example (illustrative): 250 kVA canopy set on natural ground

Data from the maker’s drawing (illustrative): skid 3.6 m × 1.3 m; wet weight with canopy and full base tank 4,000 kg.

  1. Plan size: add 300 mm on each side. Length 3.6 + 0.6 = 4.2 m; width 1.3 + 0.6 = 1.9 m. Area 4.2 × 1.9 = 7.98 m².
  2. Required mass: 2.0 × 4,000 = 8,000 kg.
  3. Volume: 8,000 ÷ 2,400 = 3.33 m³.
  4. Depth: 3.33 ÷ 7.98 = 0.418 m. Round up to 450 mm: 200 mm above finished ground and 250 mm below, on a compacted base with 75 mm lean concrete.
  5. Actual foundation weight: 7.98 × 0.45 × 2,400 = 8,618 kg.
  6. Bearing pressure: (4,000 + 8,618) × 9.81 ÷ 7.98 = 123,783 N ÷ 7.98 ≈ 15.5 kN/m². Firm natural ground typically carries 100–200 kN/m² or more, so this is a large margin.
  7. Reinforcement (typical): 12 mm bars at 200 mm centres both ways, top and bottom, 50 mm cover. Final detailing by the structural engineer.

The same steps for a 62.5 kVA set weighing about 1,400 kg on a 2.2 m × 0.95 m skid give a foundation about 2.8 m × 1.55 m and 250–300 mm deep. Small sets often end up with a practical minimum depth rather than one set by mass.

Typical figures by set size

The table below gives illustrative planning ranges for canopy sets. Weights vary widely between makes and enclosure types, so always take the wet weight and skid dimensions from the general-arrangement drawing of the exact set.

Set rating Typical wet weight with canopy Foundation mass at 2× Typical depth range
15–25 kVA 600–900 kg 1,200–1,800 kg 200–250 mm
62.5 kVA 1,200–1,600 kg 2,400–3,200 kg 250–300 mm
125 kVA 2,000–2,600 kg 4,000–5,200 kg 300–350 mm
250 kVA 3,200–4,200 kg 6,400–8,400 kg 400–500 mm
500 kVA 5,500–7,000 kg 11,000–14,000 kg 400–550 mm
1,000 kVA 12,000–16,000 kg 24,000–32,000 kg 550–750 mm

Concrete, reinforcement and isolation

Anti-vibration mounting

Most canopy sets have anti-vibration mounts between the engine-alternator and the base frame, inside the enclosure. In that case the base frame is bolted directly to the foundation and no further mounts are needed. Adding a second layer of soft mounts under the base frame can make the set rock on starting and stopping, and can strain flexible connections. Open sets, large sets and sets on upper floors may need mounts or spring isolators between the base frame and the foundation; their selection is an engineering decision.

How isolation works

A mount behaves as a spring. Under load it compresses by a static deflection δ, and the set on its mounts then has a natural frequency of about fn ≈ 15.76 ÷ √δ, with fn in Hz and δ in millimetres. Isolation becomes effective once the disturbing frequency is more than √2, about 1.4 times, the natural frequency, and improves as the ratio rises. The transmitted share of vibration for an undamped mount is roughly T = 1 ÷ (r² − 1), where r is the frequency ratio.

Worked example (illustrative): checking mount isolation at 1,500 rpm

  1. Disturbing frequency at 1,500 rpm: 1,500 ÷ 60 = 25 Hz.
  2. Target a mounted natural frequency of 8 Hz. Required static deflection: δ = (15.76 ÷ 8)² = 1.97² ≈ 3.9 mm.
  3. Frequency ratio: r = 25 ÷ 8 = 3.125; r² = 9.77.
  4. Transmissibility: T = 1 ÷ (9.77 − 1) = 1 ÷ 8.77 ≈ 0.114, so about 89% isolation at shaft frequency.
  5. At the 75 Hz firing frequency of a six-cylinder engine, r = 75 ÷ 8 ≈ 9.4 and isolation is better still.
  6. Mount loading: share the set’s weight according to its centre of gravity, not equally. A mount that is overloaded bottoms out; one that is underloaded barely deflects. Either way the isolation in steps 2–4 is lost.

Diagnostic table: foundation and mounting faults

What you see Likely cause Check
Vibration felt in nearby rooms or floors Foundation tied into building slab; foundation too light Isolation joint present and clear; foundation mass
Cracks across the plinth No reinforcement, poor curing, or settlement Crack pattern; levels at the four corners
Set rocks on starting and stopping Double soft mounting; mounts underloaded Mount type under base frame; deflection of each mount
One corner mount flat, others tall Uneven loading or out-of-level foundation Level of plinth; mount positions relative to centre of gravity
Coupling or alternator bearing failures Base frame twisted when bolted down Shim gaps before tightening; frame flatness
Water standing under the base frame Plinth too low; drainage towards set Height above ground; surrounding falls
Loose foundation bolts Grout failure or undersized anchors Torque check; anchor type against drawing

For vibration symptoms that are not caused by the foundation, see generator vibration and abnormal noise.

Terraces, upper floors and plant rooms

On a roof or upper floor, the question changes from soil bearing to structural capacity. The set, its foundation and its fuel add a concentrated load that must be checked by a structural engineer against the slab and beams. A thinner inertia block on spring isolators is usual, with the springs selected for low natural frequency. Flexible connections on exhaust, fuel and cables become essential, and the crane lift itself needs planning. Plant rooms need the same isolation joint discipline and attention to airflow; see generator room ventilation.

Foundation design and handover sheet

Item Value / reference
Set rating and model; drawing reference
Skid length × width (m)
Wet weight with canopy and full tank (kg)
Margin added each side (mm)
Foundation length × width (m) and area (m²)
Mass factor chosen (1.5–2.5) and required mass (kg)
Calculated depth (m) and adopted depth (mm)
Height above finished floor or ground (mm)
Bearing pressure (kN/m²) and soil capacity (kN/m²)
Concrete grade and reinforcement
Isolation joint width and filler
Anchor type, size and positions
Level achieved (mm per metre, four corners)
Casting date; set placed on date
Mount type and measured deflection per mount
Checked by (name, date)

Exceptions and cautions

  • The figures on this page are typical planning values. The maker’s installation manual and a structural engineer’s design take precedence, especially for upper floors, large sets and poor soils.
  • Black cotton soil, filled ground and sites with a high water table need a soil investigation and possibly a raft or piled foundation.
  • Sets in parallel plants, on trailers or in containers have their own mounting requirements.
  • Never weld the base frame to embedded steel unless the maker allows it; it transmits vibration and can distort the frame.

Common mistakes

What to send us

To check a foundation design or a vibration problem, send the set model and rating, the maker’s general-arrangement drawing if you have it, the proposed location (ground, terrace, plant room) and photographs of the existing plinth, mounts and surroundings. Use the service and AMC enquiry, or the generator sales enquiry for a new installation, or WhatsApp 98852 01608.

Questions engineers ask

How big should a generator foundation be?

Typically 150–300 mm larger than the skid on every side, with a mass of 1.5 to 2.5 times the set’s wet weight. Depth follows from that mass divided by the concrete density and plan area.

What grade of concrete is used for a DG set foundation?

M20 as a minimum, with M25 for larger sets and upper floors, reinforced top and bottom and cured for at least seven days.

Does a canopy generator need anti-vibration mounts under it?

Usually not, if it already has mounts between the engine-alternator and the base frame. The base frame is then bolted directly to a level foundation. Open and large sets may need external mounts.

How long should concrete cure before placing a generator?

Keep it wet for at least seven days and place the set after 7–14 days. Full design strength develops over about 28 days.

Why does my generator shake the building?

Most often the foundation is tied into the floor slab, is too light, or the mounts are wrongly loaded. An isolation joint, a heavier inertia block or correctly selected mounts solve most cases.

Can a generator be installed on a terrace?

Yes, if a structural engineer confirms the slab can carry the concentrated load. Use spring isolators, flexible connections and a planned crane lift.

Related pages

Technical content reviewed by D. Srinivas Reddy, Managing Partner and service engineer. Last updated 5 November 2026.

CallWhatsAppEnquire