In short. A 1500 kVA generator delivers 2087 A per phase at 415 V, three-phase, at 0.8 power factor — which is 1200 kW and 900 kVAr. At 400 V the same set delivers 2165 A and at 433 V it delivers 2000 A, because current rises as voltage falls for the same kVA. Connected at 11 kV it draws only 78.7 A. The figures below are the starting point for the breaker, the cables and the changeover switch; the page then works through what actually decides a set of this size, which is rarely the current.
Quick answers for a 1500 kVA set
- Full-load current at 415 V: 2087 A per phase
- Real power at 0.8 PF: 1200 kW
- Reactive power at 0.8 PF: 900 kVAr
- Usual breaker frame: 2500 A, set above 2087 A
- At 11 kV: 78.7 A per phase
- Per kVA at 415 V: about 1.39 A, so 1500 × 1.39 ≈ 2087 A
All figures are at the rated power factor of 0.8 and assume a three-phase, four-wire set. Always confirm against the nameplate of the actual machine.
Full-load current at each supply voltage
| Supply voltage | Full-load current (A) | Against 415 V | Where it applies |
|---|---|---|---|
| 380 V 3-phase | 2279 | +9.2% | Older and some imported equipment |
| 400 V 3-phase | 2165 | +3.8% | Nominal European voltage; many nameplates |
| 415 V 3-phase | 2087 | reference | Standard Indian LV supply |
| 433 V 3-phase | 2000 | −4.2% | No-load and lightly loaded alternator setting |
| 11 kV 3-phase | 78.7 | −96.2% | Medium-voltage connection, long runs and campuses |
The pattern is the one every engineer uses as a sanity check: for the same kVA, current and voltage move in opposite directions. Nothing about the machine changes between these rows — only the voltage it is connected at.
How the 2087 A is worked out
For a three-phase set the full-load current is
I = kVA × 1000 ÷ (√3 × V)
With 1500 kVA at 415 V:
- √3 × 415 = 1.732 × 415 = 718.78
- 1500 × 1000 = 1,500,000 VA
- 1,500,000 ÷ 718.78 = 2087 A
The kW and kVAr follow from the power factor rather than from the formula: 1500 × 0.8 = 1200 kW of real power, and 1500 × 0.6 = 900 kVAr of reactive power. Power factor does not appear in the current calculation at all, which is the part that catches people out: a set delivers 2087 A at its rated kVA whatever the power factor of the load, but the kW it can deliver at that current changes completely.
What a 1500 kVA set is used for
A 1500 kVA set is the largest size most buildings and plants in our region ever install as a single machine. Above this, sites usually go to several sets in parallel or to medium voltage. We see them in large process plants, campus central plant rooms, data facilities and projects where a whole substation has to be backed up.
Reading the 2087 A figure properly
2087 A at 415 V is the practical ceiling of low voltage distribution. A 2500 A frame, busbar instead of cable for the last stretch in many designs, and seven or eight paralleled runs per phase if cable is used. The same 1500 kVA at 11 kV draws 78.7 A — which is the whole argument for medium voltage, and the reason this page carries a decision table rather than only a chart.
Standby, prime or continuous: the same set, three different figures
A nameplate reading 1500 kVA does not say how long the set may hold it. The international rating definitions separate three duties, and the same machine carries a different figure in each:
| Duty | What it allows | Typically for this machine | Current at 415 V |
|---|---|---|---|
| Standby | Mains failure only, limited hours a year, no overload | 1500 kVA, 1200 kW | 2087 A |
| Prime | Unlimited hours at a varying load | about 1350 kVA, 1080 kW | about 1878 A |
| Continuous | Unlimited hours at a constant load, base load duty | about 1050 to 1200 kVA | about 1461 to 1669 A |
The percentages differ between manufacturers and between engines, so the figures in the third and fourth columns are the usual pattern rather than a specification: prime is commonly around 90% of the standby rating and continuous around 70 to 80%. What governs is the nameplate of the actual set and the engine maker’s own rating sheet.
This is where two quotations for “a 1500 kVA set” can describe different machines. If one is a standby rating and the other a prime rating, the second is the larger engine and the honest comparison is between the duties, not between the plates. Ask which duty the figure belongs to before comparing anything else.
What the site does to the 2087 A
Published ratings are quoted at reference conditions. Real plant rooms in Telangana and Andhra Pradesh are hotter than the reference, often higher than sea level, and sometimes short of cooling air, and every one of those reduces what the engine will deliver.
- Ambient temperature. The air entering the engine and the radiator is what counts, and in a closed plant room in May it can be well above the outside shade temperature.
- Altitude. Thinner air means less oxygen per stroke. Most of our region is low enough for this to be small, but it is not always zero.
- Air restriction. Undersized louvres, a dirty radiator or a long exhaust run with too many bends all show up as lost output, and they are the commonest cause on sets that used to carry the load and no longer do.
A derate in the region of 5 to 10% is common once a set is installed in regional summer conditions, which would take this machine from 1500 kVA to somewhere between 1350 and 1425 kVA, and the current at 415 V from 2087 A to between 1878 and 1982 A. Those are illustrative figures to show the size of the effect; the engine manufacturer publishes a derating curve for the actual engine, and that curve is what a design should use.
The practical consequence is the margin. A load that comes to 1140 kW against a 1200 kW plate looks like a 5% margin on paper and can be no margin at all on a hot afternoon.
Worked example
The same 1500 kVA, connected two ways.
- At 415 V: 2087 A. Split across eight runs per phase, that is 261 A in each cable — before any grouping or ambient derating, which at eight bunched circuits is severe. So twenty-four power cables plus neutral and earth, a 2500 A breaker, and cleats and supports rated for the fault force.
- At 11 kV: 78.7 A. One modest cable per phase, and switchgear of a size that fits in a cubicle.
- The ratio: 2087 ÷ 78.7 = 26.5 times the current for the same power. Losses go as the square of current, so the same conductor at 415 V dissipates about 700 times what it would at 11 kV.
That is why long runs at this rating go to medium voltage and short runs stay at low voltage. The crossover on most sites is somewhere between 50 and 100 m, and it moves with the cost of the cable route, the switchgear and whether the site already has 11 kV switchgear and the people licensed to work on it.
Low voltage or 11 kV at 1500 kVA? A decision table
| Consideration | Points to 415 V (2087 A) | Points to 11 kV (78.7 A) |
|---|---|---|
| Distance from set to the load centre | Short — inside the plant room or next to it | Long, or across a campus |
| Site already has 11 kV switchgear | No | Yes — the hard part is already there |
| Licensed HV operators on site | No | Yes |
| Will more sets be added in parallel | No | Yes — paralleling at HV is far simpler than a 5000 A LV busbar |
| Cable route space | Generous — two dozen cables need room | Tight |
| The load itself | All low voltage | Partly at 11 kV already, such as HV motors |
Three or more in the right-hand column and the medium voltage option usually wins on the whole installed cost, not just on the cable.
Common mistakes with a 1500 kVA set
- Sizing the LV cable route before asking whether the set should be at low voltage at all. At 2087 A the cable, the supports, the terminations and the labour often cost more than the difference between an LV and an HV machine.
- Assuming 1500 kVA is simply a larger version of 1250 kVA. It is the point where busbar, HV alternatives and paralleling all become live questions. The engineering changes in kind, not just in degree.
- Taking 11 kV as automatically better. It brings a transformer or an HV alternator, HV switchgear, licensed operation, and an earthing and protection design of its own. On a short run to an all-LV load, 415 V is still the right answer.
What to send us
If you are deciding whether a 1500 kVA set is the right size, these five things let us answer properly rather than guess:
- Maximum demand in kW and the power factor it was measured at — both, not one. Against this set the limits are 1200 kW and 1500 kVA, and which one binds depends entirely on the power factor.
- The largest motor, its rating, and how it is started: direct on line, star-delta, soft starter or variable speed drive.
- The supply voltage on the nameplate — 380, 400, 415 or 433 V. It changes the current from 2000 A to 2279 A across that range for the same set.
- The route from the set to the panel: length, whether it is tray, trench, duct or conduit, and the ambient temperature it runs through.
- How the set will be used: standby for a few hours a month, prime power for shifts, or continuous. The same machine carries different ratings for each.
Next step: work your own load through the generator kVA and kW sizing calculator, check the largest motor against the set, then send an enquiry with the five items above and we will confirm the rating in writing.
Questions engineers ask
How many amps is a 1500 kVA generator?
2087 A per phase at 415 V, three phase, at 0.8 power factor, which is 1200 kW. At 400 V it is 2165 A, at 433 V it is 2000 A, and at 11 kV the same set draws only 78.7 A. That difference is why sets of this size are often connected at 11 kV when the loads are spread across a large site.
Should a 1500 kVA generator be connected at 415 V or 11 kV?
Short runs to an all-low-voltage load stay at 415 V. Long runs, campuses, sites with existing 11 kV switchgear, or plans to parallel more sets point to 11 kV, where the same power is 78.7 A instead of 2087 A. The decision table above sets out the six questions.
What breaker does a 1500 kVA generator need?
A 2500 A frame above the 2087 A full load current at 415 V. At 11 kV the same set needs switchgear rated for 78.7 A, which is an entirely different and much smaller piece of equipment, with a neutral earthing arrangement and protection designed for high voltage. The choice of voltage therefore decides the switchgear, the cabling and the skills on site.
Can two 750 kVA sets replace one 1500 kVA set?
In running capacity, yes, and they add redundancy and better part load efficiency. They need a synchronising and load sharing panel and two of everything mechanical, and they hold a direct on line motor start less well than one large machine does. Where one set must carry the essential load alone during servicing, each set is sized for that load.
Full-load current at other ratings
- 5 kVA — 7.0 A at 415 V
- 7.5 kVA — 10.4 A at 415 V
- 10 kVA — 13.9 A at 415 V
- 12.5 kVA — 17.4 A at 415 V
- 15 kVA — 20.9 A at 415 V
- 20 kVA — 27.8 A at 415 V
- 25 kVA — 34.8 A at 415 V
- 30 kVA — 41.7 A at 415 V
- 40 kVA — 55.6 A at 415 V
- 45 kVA — 62.6 A at 415 V
- 50 kVA — 69.6 A at 415 V
- 62.5 kVA — 87.0 A at 415 V
- 75 kVA — 104 A at 415 V
- 82.5 kVA — 115 A at 415 V
- 100 kVA — 139 A at 415 V
- 125 kVA — 174 A at 415 V
- 250 kVA — 348 A at 415 V
- 320 kVA — 445 A at 415 V
- 750 kVA — 1043 A at 415 V
- 1010 kVA — 1405 A at 415 V
- 1250 kVA — 1739 A at 415 V
- Every rating from 7.5 to 3000 kVA — the full chart
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 13 November 2026.