Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Generator kVAr and Power-Factor Sharing Control

How parallel generators share reactive power: voltage droop, cross-current compensation, power-factor control with the utility, circulating current causes and how to test and tune AVRs.

In short. Reactive power (kVAr) is shared between paralleled generators through their AVRs, not their engines. If the voltage settings differ slightly, one set pushes reactive current into another, which shows up as circulating current, unequal amps and heating at the same kW. Voltage droop or cross-current compensation makes sets share kVAr in proportion to their rating. In parallel with the grid, sets control power factor or kVAr instead of voltage.

Who this page is for: For commissioning engineers and technicians setting up or troubleshooting paralleled generator sets.

Key facts

  • Real power follows the engine; reactive power follows the excitation.
  • Small voltage set-point differences cause large kVAr flows, because the sets are tied together with almost no impedance between them and each AVR tries to hold its own set point.
  • Voltage droop lowers voltage slightly as reactive load rises, so sets share.
  • Cross-current compensation links the sets’ CTs so they share without voltage droop.
  • Equal kW but unequal current means reactive power is not shared.
  • In parallel with the grid, control power factor or kVAr, not voltage.

Sharing methods

MethodHow it worksPoints
Voltage droopVoltage falls a few percent from no reactive load to fullSimple; bus voltage varies with reactive load
Cross-current compensationCT signals interconnected between AVRsHolds voltage; wiring must be correct on every set
Power factor or kVAr controlUsed in parallel with the gridGrid holds voltage; set holds its power factor

Worked example: unequal currents at equal kW (illustrative)

Two 500 kVA sets in parallel each carry 300 kW, but the meters read 520 A on set 1 and 440 A on set 2 at 415 V.

ItemSet 1Set 2
kVA = 1.732 × 415 × Aabout 374 kVAabout 316 kVA
kVAr = √(kVA² − kW²)about 223 kVArabout 100 kVAr
Power factor = kW ÷ kVA0.800.95

Total reactive load was about 323 kVAr, but set 1 carried about 69% of it. Its voltage set point was about 1% higher. After matching set points and checking droop, both sets read about 475 A and about 160 kVAr each. See kW and kVAr sharing.

Do not ignore unequal currents between sets carrying equal kW. The set carrying extra kVAr runs hotter in its windings and can trip on overcurrent, while the other set, if pushed towards a leading power factor, can trip on loss of excitation.

Commissioning checks

  1. Match voltage set points with the sets off-load.
  2. Set equal droop on all sets.
  3. Check cross-current CT polarity and wiring, if used.
  4. Load the bus with reactive load and compare amps and kVAr per set.
  5. Check loss-of-excitation and reverse reactive protection. See generator protection.

For grid-parallel operation, see interconnection studies; for real power, see kW sharing.

Sharing check sheet

SetkWAmpskVArPower factor
1    
2    
3    

Why a 1% setting error moves so much reactive power

Paralleled alternators are joined by a few metres of busbar with almost no impedance between them. Each voltage regulator tries to hold its own set point, and the only thing that decides how reactive power divides is the droop: how far each regulator lets its voltage fall as its reactive output rises. With reactive droop expressed as the voltage fall at rated kVA of reactive output, two sets of rating S share as follows when their set points differ by ΔV:

Difference in reactive output ≈ (ΔV ÷ droop) × S

Reactive droop, two 500 kVA sets (illustrative)Set point error 0.5%Set point error 1%Bus voltage fall at 0.6 per unit kVAr
2%0.005 ÷ 0.02 × 500 = 125 kVAr250 kVAr1.2%
4%62.5 kVAr0.01 ÷ 0.04 × 500 = 125 kVAr2.4%
6%about 42 kVArabout 83 kVAr3.6%

The 4% row matches the worked example above: a 1% set point error left set 1 carrying about 223 kVAr and set 2 about 100 kVAr, a difference of about 123 kVAr. More droop makes sharing less sensitive to calibration but lets the bus voltage wander further with reactive load; 3 to 5% is the usual compromise. With no droop and no cross-current link at all, nothing limits the circulating current except the regulators’ own limits, and one set can end up over-excited while the other is driven towards loss of excitation.

Cross-current compensation: the wiring that makes or breaks it

  • One CT per set, on the same phase: each regulator takes a current signal, usually from phase B, through a burden resistor, and the CT secondaries of all sets are connected in a series loop.
  • Polarity: one reversed CT turns sharing into run-away; the set that should shed kVAr takes more. Check by loading each set alone with reactive load and watching the voltage fall slightly, never rise.
  • Sets out of service: a breaker auxiliary contact must short the CT of a set that is off the bus, or the loop is broken and every other set loses compensation.
  • Grid parallel: the loop must be switched to droop or opened when the plant parallels with the grid, because the grid does not take part in the loop and would otherwise see the plant drift in voltage.
  • Different ratings: choose CT ratios in proportion to set ratings so each regulator sees the same signal at the same per-unit loading.

Worked example: power factor control in parallel with the grid (illustrative)

Connected to the grid, a set cannot change the voltage, so a regulator left in voltage control fights the whole network: if the grid voltage rises 2%, the regulator lowers excitation to pull it back, and the set swings towards a leading power factor. The regulator therefore switches to power factor or kVAr control when the breaker closes. A 500 kVA set exporting 400 kW at 0.95 power factor lagging supplies 400 × tan(cos−1 0.95) ≈ 400 × 0.329 ≈ 131 kVAr, and holds that ratio as its kW changes.

Limit to respectWhy it matters
Rated kVAAt 400 kW the set has up to 300 kVAr available within 500 kVA; asking for more overloads the stator
Field current limitHigh lagging kVAr at low voltage overheats the rotor
Under-excitation limitLeading operation weakens the magnetic coupling and approaches loss of synchronism; the maker’s capability chart sets the limit
Site and utility agreementThe power factor at the point of connection may be fixed by the utility

Reading the instruments

What the instruments showLikely causeWhere to adjust
Equal kW, unequal amps, power factors moving apartVoltage set points or droop not matchedVoltage regulator
Unequal kW, equal power factorSpeed droop or load-share signalGovernor or load-share controller
Amps that do not fall when load is removedCirculating kVAr between setsVoltage regulator, cross-current loop
Kilovars swinging after a load stepRegulator gains too high or sets with very different responsesRegulator tuning
Neutral current with balanced loadThird-harmonic current circulating between alternators of different winding pitchNeutral arrangement or matched alternators

Mixing alternators of different winding pitch

Alternators wound with different coil pitches generate different third-harmonic voltages. When their neutrals are connected together, that difference drives a third-harmonic current round the neutrals even with no load, heating windings and confusing earth-fault protection. Two-thirds pitch windings produce very little third harmonic, which is why they are preferred for parallel duty. Where pitches differ, keep only one neutral connected to the bus or add a neutral reactor, as the earthing design allows.

Worked example: sharing between sets of different ratings (illustrative)

A 1000 kVA set and a 500 kVA set carry a combined reactive load of 600 kVAr. Correct sharing is by rating, not equal kilovars: each set carries the same per-unit reactive output.

SetShare of ratingkVArPer unit of its rating
1000 kVA1000 ÷ 1500 = two thirds400 kVAr0.4
500 kVA500 ÷ 1500 = one third200 kVAr0.4

If both regulators are set to the same droop percentage of their own rating and the same no-load voltage, this division happens on its own. If the smaller set is given a droop referred to the larger set’s rating, it takes twice its share of every change in reactive load.

Commissioning sharing with a reactive load

StepCheckPass when
1. Each set alone, no loadVoltage set points matched with one calibrated instrumentWithin about 0.2% of each other
2. Each set alone, reactive loadVoltage falls by the set droopFall matches the setting; never a rise
3. Sets in parallel, no loadCurrentsClose to zero on every set
4. Parallel, rising reactive loadkVAr per set at 25, 50 and 75%Each set within about 10% of its per-unit share
5. Load stepsSwings in kVAr after a stepSettle within a few seconds without hunting

A load bank with a reactive section is what makes steps 2 and 4 possible; a resistive bank alone tests kW sharing and hides kVAr problems until the first motor-heavy load arrives.

Protection that watches reactive sharing

Sharing errors that controls do not correct must be caught by protection before they damage a machine. Three functions do the work on paralleled sets:

  • Loss of excitation: trips a set whose field has failed or whose regulator has driven it far into leading operation, where it draws reactive power from the others and can lose synchronism.
  • Reverse reactive power: a simpler element on smaller sets that alarms or trips when a set absorbs more than a set amount of kVAr, catching a regulator failing low.
  • Overcurrent and over-excitation limits: protect the set that has taken too much lagging kVAr, which shows as stator current above rating at moderate kW, and as high field current.

Set them from the alternator capability chart, test them by injection, and record every operation, because a trip on any of them usually points to a sharing or regulator problem that will recur until it is found and corrected.

Common mistakes

  • Checking kW sharing only.
  • Different droop settings on different sets.
  • Cross-current CTs wired with wrong polarity.
  • Voltage control left on in grid parallel.

What to send us

Send readings of kW, amps and power factor per set and the AVR settings. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. Readings are illustrative.

Questions engineers ask

How much kVAr flows for a 1% voltage setting difference?

Roughly the setting difference divided by the reactive droop, times the set rating. For two 500 kVA sets with 4% droop, 0.01 divided by 0.04 times 500 gives about 125 kVAr difference between them, so one carries about 62 kVAr more than its share and the other about 62 kVAr less. With 2% droop the same error doubles the difference.

What reactive droop should paralleled generators use?

Usually 3 to 5% at rated kVA of reactive output, the same on every set. Less droop holds bus voltage tighter but makes sharing very sensitive to small set point errors; more droop shares more robustly but lets the bus voltage fall further with reactive load, about 2.4% at 0.6 per unit kVAr with 4% droop.

What does circulating current look like?

Sets that share kW equally but show different currents and power factors, one lagging more and the other moving towards unity or leading, and currents that stay high when load is removed. The excess current is reactive, flowing from the set with the higher voltage setting into the other. Alternators can run warm even at light load.

Do I need droop on every set?

Yes, unless every set is in a cross-current compensation loop. Reactive droop is what makes regulators share, so a single set without it tries to hold voltage alone and takes or rejects reactive power until it hits a limit. Use the same droop percentage on all sets, on a per-unit basis, so sets of different ratings share in proportion.

Why is power-factor control used on the grid?

Because the grid fixes the voltage, a generator regulator cannot change it, and in voltage control it would fight every small grid voltage change by swinging its reactive output. In power factor or kVAr control the set holds its own reactive output steady, for example 0.95 lagging, within its capability chart and the utility agreement.

What if an AVR fails?

A regulator failing high drives the set to maximum excitation and large lagging kVAr; failing low drives it towards loss of excitation, drawing reactive power from the other sets. Over-excitation, loss-of-excitation and reverse reactive protection trip the faulty set, and the remaining sets must be able to carry the load, so plan reserve and shedding for it.

Values are illustrative. Follow manufacturer guidance.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.

CallWhatsAppEnquire