In short. An automatic synchroniser brings an incoming generator into step with the bus by matching its voltage, frequency and phase angle. It then issues the close command early enough to allow for the breaker’s closing time. An independent check-synchronising relay confirms the window, so a single synchroniser fault cannot close the breaker out of phase. Phase sequence must be proven before the first close.
Who this page is for: For control and commissioning engineers setting up paralleled generators or generator-to-grid synchronising.
Key facts
- Match frequency (slip), voltage and phase angle before closing.
- Slow, positive slip lets the incoming set take a little load at once instead of motoring.
- Advance angle = slip frequency × 360° × breaker closing time.
- An independent check-sync relay must also permit the close.
- Wrong phase sequence at the first close is a short circuit; prove it first.
- Typical windows: voltage within a few percent, slip a fraction of a hertz, angle within about 10 degrees.
The sequence
Incoming set running, permissives satisfied, speed and voltage matched, slip and angle inside the window, close command issued ahead of zero, breaker closes, feedback confirmed, set takes load.
Matching variables
| Variable | Adjusted by | Why |
|---|---|---|
| Frequency (slip) | Speed raise and lower, or analogue bias | Slow slip gives time to close near zero angle |
| Voltage | AVR raise and lower, or analogue bias | Limits reactive current at closing |
| Phase angle | Close command leads by the closing time | Contacts meet near zero angle |
| Phase sequence | Checked before first operation | Wrong sequence is a short circuit |
Worked example: setting the advance angle (illustrative)
| Item | Working | Result |
|---|---|---|
| Breaker closing time (measured) | 80 ms | |
| Target slip | Incoming set slightly fast | +0.1 Hz |
| Angle travelled during closing | 0.1 × 360 × 0.08 | about 2.9 degrees |
| Close command issued | About 3 degrees before zero | |
| If slip were 0.3 Hz | 0.3 × 360 × 0.08 | about 8.6 degrees: close to the edge of a 10 degree window |
The site set the slip window to 0.05 to 0.2 Hz, so the advance stays small and the contacts meet within a couple of degrees of zero. At commissioning, the first closes were made with the breaker in test position and a recorder on both voltages and the breaker auxiliary contact to confirm the angle at closing.
Never make the first close on a new or rewired generator without proving phase sequence and phase identity with instruments. A wrong connection closed in “sync” is a three-phase short circuit.
Two layers of protection
- The automatic synchroniser decides when to close.
- An independent check-sync relay permits the close only inside its window.
See dead-bus, live-bus and sync-check logic, synchronisation and paralleling studies.
Synchroniser settings record
| Setting | Synchroniser | Check-sync relay |
|---|---|---|
| Voltage difference | ||
| Slip window | ||
| Angle window | ||
| Breaker closing time and advance |
Worked example: how long synchronising takes (illustrative)
Once speed and voltage are matched, the synchroniser waits for the phase angle to come round to the closing point. At a slip of S hertz, the angle completes one full turn every 1 ÷ S seconds, so in the worst case the wait is one full slip cycle.
| Slip | One slip cycle | Worst-case wait for the angle | Advance with an 80 ms breaker |
|---|---|---|---|
| 0.05 Hz | 1 ÷ 0.05 = 20 s | up to 20 s | 0.05 × 360 × 0.08 ≈ 1.4 degrees |
| 0.1 Hz | 10 s | up to 10 s | about 2.9 degrees |
| 0.2 Hz | 5 s | up to 5 s | about 5.8 degrees |
Very low slip gives a precise close but can make the set wait up to 20 seconds, which matters when a mains failure has left load waiting. Higher slip is quicker but needs a larger, more critical advance. A slip window of about 0.05 to 0.2 Hz, as in the example above, balances the two; where the plant must parallel fast, aim near the upper end and make sure the breaker closing time entered is the measured one.
Worked example: what a voltage difference costs at closing (illustrative)
A voltage difference between the incoming set and the bus drives a reactive current at the instant of closing, limited by the reactance of both sides. For an incoming set closing onto a bus held by an identical running set, each with a subtransient reactance of about 0.12 per unit, the total is about 0.24 per unit.
| Voltage difference | Reactive current at closing |
|---|---|
| 2% | 0.02 ÷ 0.24 ≈ 0.08 times rated |
| 5% | 0.05 ÷ 0.24 ≈ 0.21 times rated |
| 10% | 0.10 ÷ 0.24 ≈ 0.42 times rated |
Voltage difference is far less damaging than phase angle error, which is why voltage windows of a few percent are acceptable. Matching voltage also matters for what happens next: a set closing with high voltage immediately exports reactive power into the others and has to be pulled back by the reactive sharing control, which can look like a sharing fault in the first seconds after every close.
How the synchroniser moves speed and voltage
| Method | How it works | Tuning point |
|---|---|---|
| Raise and lower pulses | Relay contacts pulse the governor or regulator set point | Pulse length and interval: too long overshoots and hunts, too short is slow |
| Analogue bias | A voltage or current signal shifts the set point continuously | Gain and polarity; a reversed polarity drives the set away from synchronism |
| Digital communication | The synchroniser writes set points to the controller over a network | Update rate and behaviour if the link is lost mid-synchronisation |
Whichever method is used, check the direction first: command raise speed and confirm the frequency rises. A reversed bias is a common commissioning fault, and it shows as a set that drifts steadily away from the bus however long the synchroniser runs.
Setting the check-synchronising relay
The check relay must be independent of the synchroniser: its own voltage inputs, its own settings and its own contact in series with the close circuit. Its window is usually set equal to or slightly wider than the synchroniser’s, so it never blocks a good close but always blocks a bad one; a check window narrower than the synchroniser’s causes closes to be refused at random. The relay also needs a deliberate rule for dead-bus closing, when one side has no voltage to compare, normally permitted only when the dead-bus logic confirms the bus is truly dead and no other breaker is closing.
Proving phase sequence and phase identity
- Check phase rotation on both sides of the breaker with a rotation meter or the controller display.
- With the breaker racked to its test position and both sides live, measure voltage across each open pole with the synchroscope showing zero angle: each should read near zero; a reading near line voltage means a phase is crossed.
- Confirm the synchroniser and check relay VTs are connected to the same phases on both sides.
- Repeat after any rewiring, alternator replacement or cable work, not only at first commissioning.
Synchronising across a transformer
Where the incoming set connects through a step-up transformer and the breaker being closed is on the other side, the transformer’s vector group shifts the phase. A Dyn11 transformer, for example, shifts its secondary 30 degrees from its primary. If the synchroniser compares a voltage taken on one side with a voltage on the other, it must compensate for that 30 degrees, either by a matching VT connection or by a setting in the device. Get it wrong and the synchroniser closes the breaker exactly 30 degrees out of phase every time, a severe close it believes to be perfect.
Commissioning the synchroniser
Make the first closes with the breaker in its test position, recording both voltages and the breaker auxiliary contact, so the actual angle at the moment of contact can be read from the record. Adjust the closing time entered until the recorded close angle sits within a couple of degrees of zero, then make live closes under the same recording. Keep the records: a close angle that drifts upwards over the following years points to a breaker that is slowing down.
Synchronising to the grid compared with synchronising to a set
Onto a bus held by other generators, both sides move: the running sets’ frequency wanders slightly with load, and the synchroniser chases a moving target. Onto the grid, the reference is rock steady and all the adjustment is on the incoming set. Two differences follow. Grid synchronising usually needs the utility’s permission and an interface protection scheme, and the window is often tighter. And once closed, the set is locked to the grid, so its governor and regulator must change mode at once to control kW and power factor rather than frequency and voltage. See utility and DG transfer control.
Keep a record of every close
Most modern synchronisers and controllers can log the slip, voltage difference and angle at the close command, and the time to synchronise. Download those logs at each service visit and compare them over time. A rising time to synchronise suggests a governor or bias problem; a rising close angle suggests the breaker is slowing; a sudden change after a service suggests a setting was altered. Each is cheap to catch from the records and expensive to discover from a damaged coupling.
Set an alarm on the time to synchronise as well, for example if a set has not closed within 60 seconds of being ready. A set that cannot synchronise is unavailable in practice, and the plant should call the next set rather than wait.
Common mistakes
- Breaker closing time not entered.
- No independent check-sync relay.
- Negative slip, so the set motors at closing and can trip on reverse power.
- First close made without proving sequence.
What to send us
Send the generator and breaker data, the controller settings and any close records. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Times and windows are illustrative; makers’ data and studies govern.
Questions engineers ask
How long does automatic synchronising take?
Once speed and voltage match, up to one full slip cycle while the angle comes round: up to 20 s at 0.05 Hz slip, 10 s at 0.1 Hz and 5 s at 0.2 Hz. Very low slip gives a precise close but a long wait; higher slip is quicker but needs a larger breaker-time advance, about 5.8 degrees at 0.2 Hz with an 80 ms breaker.
How is a generator synchronised across a transformer?
The synchroniser must allow for the transformer phase shift. A Dyn11 transformer shifts its secondary 30 degrees from its primary, so if the voltages compared are taken on opposite sides, the VT connections or a device setting must compensate the 30 degrees. Otherwise the synchroniser closes exactly 30 degrees out of phase every time while reporting a perfect close.
Why compensate for breaker time?
Because the breaker contacts meet some tens of milliseconds after the close command, and the phase angle keeps moving at the slip frequency meanwhile. The advance is slip times 360 times the closing time: about 2.9 degrees at 0.1 Hz with an 80 ms breaker. Without it, a close commanded at zero lands several degrees late, and more as slip rises.
Is manual synchronising still used?
Sometimes, as a backup when the automatic synchroniser is out of service, using a synchroscope, voltage and frequency indication on both sides and an operator close switch. The independent check-sync relay must still be in the close circuit, so a mistimed manual close is blocked. Operators need training and practice, because manual synchronising is rarely done.
What if slip is too fast?
The synchroniser trims the incoming set speed to bring the slip into its window, or waits. Closing at high slip needs a large advance and leaves the set with a large power swing after the close. If the slip will not settle, the governor is usually hunting or the speed bias is too aggressive, and needs tuning rather than a wider window.
Do I need check-sync with an auto synchroniser?
Yes. The check-sync relay is independent protection against the synchroniser failing: it has its own voltage inputs and settings, and its contact is in series with the close circuit, so a faulty synchroniser cannot close outside the window. Set it equal to or slightly wider than the synchroniser window, never narrower.
Values are illustrative. Follow manufacturer settings.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.