Power Quality Problem Finder

Match a power-quality symptom, such as sags, flicker, harmonics, unbalance or transients, to the measurement or engineering study that finds the cause and the likely solutions.

In short. Power-quality problems look alike on the surface: equipment trips, lights flicker, cables run hot. Each has its own causes and needs its own measurement or study. Match the symptom, and whether it happens on mains, on the generator or on both, to the right study before buying a stabiliser, filter or UPS. That way the fix suits the actual cause.

Who this page is for: For facility managers and plant engineers facing trips, dips, overheating or failures and wanting to know what to investigate.

Key facts

  • Start with the symptom and when it happens.
  • Problems only on generator often point to the set itself, or to how the loads interact with it.
  • Problems on both supplies usually point to the site’s own loads; problems only on mains point to the incoming supply.
  • Measure before buying equipment.
  • Record events with time stamps to link cause and effect.
  • One problem may need two studies.

Symptom to study

SymptomLikely causeStudy or measurement
Breakers or drives tripSettings, dips, earth faultsProtection coordination and event recording
Lights dip when motors startStarting currentMotor-starting study
Hot neutrals, cables or transformersHarmonics or overloadHarmonic measurement and load study
Flicker on generatorGovernor, voltage regulator or load swingsGenerator test and transient check
Low power factor chargesReactive loadPower factor study
Electronics or capacitors fail earlyHarmonics, resonance or surgesHarmonic and surge study

Worked example: three complaints traced (illustrative)

ComplaintWhenFindingFix
Office lights flickerGenerator onlyVoltage regulator hunting with a large UPS loadRegulator retuned; alternator checked for harmonic load
Drives trip in the plantBoth suppliesDeep dips when a 75 kW compressor startsSoft starter on the compressor
Capacitor bank failingBoth suppliesResonance with drive harmonicsDetuned bank

A stabiliser bought for the office flicker would not have fixed a regulator problem on the generator. See harmonic screening and motor starting.

Do not buy correction equipment before measuring. The wrong device can hide the symptom for a while, or make the real cause worse.

Symptom record

SymptomDate and timeMains or generatorLoads running
    
    
    

Common mistakes

  • Buying a fix before measuring.
  • Not noting whether it happens on generator.
  • No time stamps on events.
  • Treating several symptoms as one.

What to send us

Send a description of the symptom, when it happens and any readings. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. The examples are illustrative.

Questions engineers ask

How long should I record power quality?

At least a week to capture normal cycles and events; longer for intermittent problems.

Is a stabiliser the answer to voltage problems?

For slow voltage variation, yes. It does not fix interruptions or harmonics.

What if the problem only occurs on the generator?

Check generator regulation, harmonics from non-linear loads and step loading.

Do I need a standard to compare against?

Yes, for example EN 50160 for supply voltage characteristics and IEEE 519 for harmonics.

This guide gives general principles. Diagnosis needs measurements at your site.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.