DG + BESS Hybrid Sizing Calculator

How to screen a diesel generator and battery hybrid: how to split load between engine and battery, expected fuel and runtime effects, sizing logic and the limits of a screening estimate.

In short. A DG and battery hybrid lets the generator run in its efficient band while the battery takes the peaks, the load steps and the light-load hours. Whether it pays depends on the shape of the load, not its size. Large short peaks over a modest base, or long light-load periods, favour a hybrid; a steady load gives it little to do. Screening from a real load profile shows the battery power and energy needed and whether the saving is worth a detailed study.

Who this page is for: For plant owners, consultants and rental users weighing a battery alongside a generator for peaks, fuel, noise or night-time operation.

Key facts

  • BESS power ≈ peak − chosen generator capacity.
  • BESS energy per event ≈ excess power × duration, then divided by usable depth, efficiency and end-of-life capacity.
  • A load profile at 1- to 15-minute resolution is the starting point.
  • Large engines are already efficient at moderate load, so fuel savings from peak shaving alone can be small.
  • The biggest savings come where a set would otherwise run for hours at very light load.
  • For long outages, the generator remains the source; the battery cannot replace it.

Screening steps

  1. Get a load profile at 1- to 15-minute resolution.
  2. Find the peak, the average, the light-load hours and the time above a candidate generator size.
  3. Choose a generator size that runs in a healthy band most of the time.
  4. BESS power covers the excess above that size; energy covers the area above the line.
  5. Allow for losses, reserve and degradation.
  6. Compare fuel, running hours, starts and maintenance with the generator-only case.

Worked example: peaks over a 400 kW base (illustrative)

A site averages 400 kW, with peaks of 900 kW lasting about 10 minutes several times a day.

ItemGenerator onlyHybrid
Generator sizeAbout 900 kW500 kW
Average loadingAbout 44%About 80%
BESS powerNone900 − 500 = 400 kW
Energy per peakNone400 kW × 10 min ≈ 67 kWh
Nameplate for one peakNone67 ÷ (0.9 × 0.94 × 0.8) ≈ 99 kWh; about 250 kWh (1.6C at 400 kW) allows several peaks, reserve and a practical C-rate
Fuel per kWh, from typical curvesAbout 0.28 L/kWhAbout 0.27 L/kWh

The fuel saving here is only a few percent, because a large engine at 44% load is not very inefficient. The hybrid’s case rests elsewhere: a smaller generator, fewer heavy load steps, and the ability to switch the set off when the load is light. If the same site ran 60 kW through the night, the large set would sit near 7% load, burning far more fuel per kWh and building up carbon deposits.

A battery can carry those hours with the set stopped only if it is sized for them: 10 hours at 60 kW needs about 600 kWh usable, roughly 890 kWh nameplate. A smaller battery can still help, with the set running at a healthy load to recharge it and then stopping. See the fuel consumption chart.

Do not justify a hybrid from a generic fuel-saving percentage. Use your own load profile and the engine’s fuel curve; savings range from almost nothing on a steady load to large on a site with long light-load hours.

What to compare

ItemGenerator onlyHybrid
Generator sizeSized for peakSized for base
Light-load runningCommonReduced or avoided
Run hoursMoreFewer
StartsFewerMore, unless controls limit cycling
Noise and emissions at nightSet runsSet can stop
ComplexityLowerControls, battery safety, cooling

See hybrid dispatch control and hybrid modernisation.

Hybrid screening sheet

ItemValue
Average, peak and minimum load (kW) 
Hours per day below 30% of the present set 
Candidate generator size (kW) 
BESS power (kW) and energy (kWh) 
Estimated fuel and run-hour change 

Starting from the load profile

A hybrid of generator and battery is designed around how the load changes through a day, not around its peak alone. An hour-by-hour profile, from a logger or a controller record, shows the base load at night, the daytime level, the peaks and the steps. The battery is given the parts of the profile a generator handles badly: light load, short peaks and sudden steps. The generator is given the long, steady energy it delivers well.

PeriodTypical loadWithout batteryWith battery
Night, 10 pm to 6 am40 kWSet runs at about 13% loadBattery carries the load, set off
Morning start-upSteps to 180 kWLarge steps on the setBattery takes the steps while set starts
Daytime200 to 240 kWSet at a healthy loadSet at a healthy load, recharging battery
Evening peakUp to 290 kW for an hourSet near its limitBattery shaves the peak above 250 kW

For a site whose generator is 375 kVA, or 300 kW at 0.8 power factor, the table shows the familiar pattern: long hours of light load at night, which cause wet stacking and waste fuel, and a short evening peak close to the set limit.

Sizing the battery for those duties

The night duty sets the energy: 40 kW for 8 hours is 320 kWh delivered. With usable depth, end-of-life capacity and conversion losses giving a combined factor of about 0.67, the installed nameplate is about 480 kWh. The step and peak duties set the inverter power: the largest morning step and the 40 kW evening shave, with margin, suggest an inverter of about 150 kW. The generator still recharges the battery during the day, adding up to about 55 to 60 kW over six hours, which fits within the daytime margin of the set.

Estimating the fuel saved

Without the battery, the set runs 8 night hours at 40 kW, where its efficiency is poor. At that load it may burn around 14 litres per hour, about 0.35 litres per kWh, or 112 litres a night. With the battery, the same 320 kWh is generated during the day at a healthy load, at about 0.27 litres per kWh, plus losses through the battery of roughly a third, so about 320 divided by 0.75, or 427 kWh generated, using about 115 litres.

The direct fuel saving is therefore small in this case; the real gains are fewer engine hours, no wet stacking, longer service intervals in calendar time and quieter nights. A simulation on the real profile and the maker fuel curve gives the site figure.

Control rules that make it work

  • Start the generator when the battery reaches its lower state-of-charge limit, or when load exceeds what the battery can carry.
  • Run the generator at a healthy load, charging the battery with any surplus, and stop it when the battery is full and the load is low.
  • Keep a reserve in the battery for outages and for the next morning step.
  • Use minimum run and minimum off times so the set does not cycle on and off.
  • Let the battery inverter form the grid when the set is off, and follow the set when it runs.

Risks to manage

A hybrid adds controls and a battery that must be maintained and protected. The inverter must be grid-forming to run the site with the set off. The battery needs temperature control, fire detection and protection suited to its chemistry. If the controller fails, the site must default safely to generator supply. These risks are manageable, but they are designed for from the start rather than discovered after commissioning.

What to check before committing

  • At least two weeks of logged load, including a weekend, to see the real night and peak loads.
  • The outage history, because long outages still decide the generator rating and fuel store.
  • The generator minimum load and step acceptance from the maker data.
  • Space, ventilation, cooling and fire separation for the battery.
  • Whether the existing generator controller can accept start and stop commands from the hybrid controller.

With these in hand, a simulation over a typical week shows generator hours, fuel, battery cycles and the effect of each control rule before any equipment is ordered.

The simulation result is recorded with its assumptions, so the measured fuel, hours and battery cycles in the first year can be compared with it and the control settings adjusted where the site behaves differently from the plan.

That first-year review is also the point to confirm the battery reserve held for outages is still right for the site.

Common mistakes

  • Using an average instead of a time-resolved profile.
  • Assuming large fuel savings from peak shaving alone.
  • Forgetting battery losses, reserve and degradation.
  • Expecting the battery to replace the generator in long outages.

What to send us

Send a load profile (meter data or logs), the present generator details and what you want to improve: fuel, noise, run hours or resilience. WhatsApp 98852 01608 or use the enquiry form.

Evidence note. Fuel figures are typical values for illustration; engine data and the site profile govern.

Questions engineers ask

How is a battery sized for a generator hybrid?

The night or light-load duty sets the energy and the steps and peaks set the inverter power. A 40 kW night load for 8 hours needs 320 kWh delivered, or about 480 kWh nameplate with typical factors, and the largest morning step and evening shave suggest an inverter of about 150 kW.

Does a generator hybrid always save a lot of fuel?

Not always. Where the battery shifts night energy to daytime generation, the direct saving can be small once battery losses are counted. The larger gains are fewer engine hours, no wet stacking, longer service life in calendar time and quieter nights. A simulation on the real profile gives the site figure.

What control rules does a generator and battery hybrid need?

Start the set at the battery lower limit or when load exceeds the battery capacity, run it at a healthy load while charging, stop it when the battery is full and load is low, hold an outage reserve, and use minimum run and off times so the set does not cycle.

What data do I need before designing a hybrid?

At least two weeks of logged load including a weekend, the outage history, the generator minimum load and step acceptance, space and cooling for the battery, and whether the generator controller accepts external start and stop commands. These let a weekly simulation predict hours, fuel and battery cycles.

When does a hybrid make sense?

When load has large peaks, long light-load periods or frequent steps, and the economics or resilience justify it. Sites such as telecom towers, construction camps and process plants with cycling loads often fit this pattern, while a site with steady load near the generator rating gains little. Logged load data decides.

How much fuel can a hybrid save?

It varies widely with the profile. Estimate from your load data and engine curves, not generic percentages. A simulation hour by hour, using the engine fuel curve and the battery efficiency, shows the generator running hours, fuel and battery cycles for each option, so the saving is based on the site rather than on a brochure figure.

Do I still need a generator?

For long outages, yes. The battery supports but has limited energy. The battery covers short outages, peaks and light-load periods, while the generator supplies energy for as long as the outage lasts and recharges the battery, so the two together give both quick response and long duration.

Does the hybrid need special controls?

Yes, a coordinated controller for dispatch, state of charge and mode transitions. It decides when the generator starts and stops, keeps it at a healthy load, holds the battery within its state of charge limits and manages the change between grid, generator and battery-only operation without disturbing the loads.

Figures are illustrative. A hybrid study is needed before design.