Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Critical Power Solution Architecture Tool

Start from your requirement, outage tolerance, duration, load, site and compliance, and find the complete solution architecture of sources, protection, controls, testing and services.

In short. A complete critical power solution is more than a generator. It brings together sources, power conditioning, distribution, controls, protection, testing and service. Four answers set the outline: the load size, the break the critical load can tolerate, the downtime it can accept, and how often and how long the grid fails. The decision tool above turns those answers into an outline. This page shows how that outline becomes a full scope.

Who this page is for: For owners and consultants turning a critical power requirement into a full scope of work.

Key facts

  • Load size sets the number and rating of sets.
  • Break tolerance decides whether a UPS is needed.
  • Downtime tolerance sets the level of redundancy.
  • Grid outage pattern sets fuel and running-hour planning.
  • Studies, testing and service are part of the solution.
  • Write the scope down before asking for quotations.

Worked example: a pharmaceutical plant, from answers to scope (illustrative)

AnswerScope element
Load 250 to 1000 kVA (about 800 kVA)Three 500 kVA sets in parallel, N+1
Controls tolerate no breakOnline UPS for controls and quality systems
Downtime: minutes a yearLoad shedding, A and B feeds for key loads
Grid outages frequentFuel for long runs; monitoring of hours and fuel
StudiesLoad, short-circuit, coordination, motor starting
TestingFactory, site and integrated mains-failure tests
ServiceMaintenance plan with spare parts

Writing the scope this way means every quotation prices the same thing. See requirement to architecture guide and study selector.

Do not compare quotations that cover different scopes. Fix the scope first, so the cheapest offer is not simply the one that left the most out.

Elements of a complete solution

ElementExamples
SourcesGenerators, UPS, battery storage
DistributionChangeover, boards, A and B paths
ControlsSynchronising, load shedding, monitoring
ProtectionSettings checked on every source
Testing and serviceCommissioning tests, maintenance, spares

See failure testing.

Requirement sheet

QuestionAnswer
Total load 
Break the critical load can take 
Downtime acceptable 
Grid outage pattern 

From a requirement to a working system

Many projects start with a short sentence: we need backup power. A complete solution turns that sentence into a system that is designed, built, tested, operated and maintained as one. The journey has six stages, and skipping any of them is the most common reason a standby system fails on the day it is needed.

StageQuestion answeredOutput
1. RequirementWhat must stay on, for how long, and what break can it accept?Load list with tolerance classes and outage targets
2. ArchitectureWhich sources, at what redundancy, in what arrangement?Single-line diagram and source roles
3. Sizing and studiesWhat ratings, and do protection and voltage work in every state?Ratings, settings schedule, study reports
4. BuildIs it installed as designed and safely?Installation records, approvals
5. CommissioningDoes the whole system respond as intended?Signed test records and baseline readings
6. OperationWill it still work in five years?Maintenance plan, test schedule, records

Tolerance classes in plain terms

Every load fits one of four classes, and the class decides the source that protects it.

  • No break: servers, controls, medical monitoring and instruments that lose data or settings on any interruption. They need a UPS or battery.
  • Short break: lighting, lifts, pumps and many process loads that restart cleanly after a few seconds. The generator and changeover protect them.
  • Long break: loads that can wait hours, such as some air-conditioning or non-essential lighting. They can be shed during an outage.
  • Not protected: loads deliberately left off backup to keep the generator size reasonable.

A load list that places each item in one class, with its kW, power factor and starting method, is the single most useful document in the project.

A requirement worked through (illustrative)

A small hospital wing lists 60 kW of no-break load, 140 kW of short-break load including a 22 kW lift and two 15 kW pumps, and 90 kW of long-break air-conditioning. The outage history shows grid failures of a few minutes several times a week and occasional failures lasting most of a day.

The architecture that follows is a UPS of about 80 kVA for the no-break load with runtime for generator start and transfer, and a generator for the no-break and short-break loads together, 200 kW, with the lift starting while the rest runs. At 0.8 power factor and a sensible margin, a set of about 320 kVA fits, with the air-conditioning shed and restored only when capacity allows. Where the wing cannot accept loss of backup during maintenance, a second set or a prepared rental connection point is added.

Who does what

A complete solution works only when every interface has an owner. The owner sets the requirement and accepts the risk that remains; the designer turns it into an architecture and studies; the suppliers provide equipment that meets the specification; the installer builds it to the drawings; the commissioning team proves the whole system; and the maintenance team keeps it ready. Where one partner coordinates all of these, the scope and the interfaces are still written down, because problems most often appear where one scope ends and another begins.

Keeping the solution working

  • Oil and filters every 250 to 500 running hours or six months, whichever comes first, and coolant every year.
  • Regular test runs on real load, with a load-bank test where the site load is low.
  • A yearly mains failure test of the whole sequence, including the UPS and any battery.
  • Battery health monitoring for the UPS, any BESS and the starting batteries.
  • A yearly review of the load list against the capacity and runtime of each source.

Why complete solutions fail

Failure seenStage where it beganPrevention
Generator too small for a motor startSizingMotor starting check with the running load present
UPS on battery whenever the generator runsStudiesCheck generator frequency and distortion against the UPS input window
Set did not start after a long idle periodOperationBattery monitoring, readiness checks and regular test runs
Changeover worked alone but not in the full sequenceCommissioningIntegrated test of every transition
Critical load added to the wrong boardOperationLoad register reviewed before any change

What to gather before the first meeting

  • A list of the equipment that must run during an outage, with nameplate ratings and photographs.
  • Electricity bills for twelve months, showing maximum demand and its seasonal pattern.
  • The outage history, even if approximate: how often, how long, and at what times.
  • Existing single-line diagrams, panel schedules and any previous studies.
  • Site constraints: space for the set, access for delivery, noise limits and fuel storage options.
  • Any standards, insurer or client requirements the site must meet.

With this information the first meeting can move straight to the requirement and the options, instead of spending its time finding out what the site has.

Scaling the approach to the size of the site

A shop or a small office does not need formal studies; a load list, a sizing check and a correctly installed changeover are enough. A hospital, data room or process plant needs the full six stages with studies and integrated testing. Most sites sit in between, and the approach is scaled to the consequence of a failure: the more it would cost to lose supply, the more of each stage is carried out formally and recorded.

The documents a finished system should hand over

DocumentWhy it matters
Load list with tolerance classesShows what each source protects and why
Single-line diagram as builtBasis for every later change and study
Sequence of operationDescribes every transfer and failure response
Protection settings scheduleLets settings be checked and restored
Commissioning test recordsBaseline for every later test
Maintenance plan and recordsKeeps the system ready over its life

These six documents together let anyone pick up the system years later and understand it without guesswork.

Reviewing the solution every year

Sites change. Loads are added to backed-up boards, critical equipment moves, batteries age and fuel arrangements alter. A yearly review compares the load list with what is actually connected, checks each source against its load with margin, confirms the last integrated test passed, and records any change in the outage pattern. The review takes a few hours and is the cheapest way to keep a complete solution complete, because it finds the drift before an outage does.

The review also confirms that the people who operate the system are trained, that emergency contact numbers are current, and that the written procedures at each panel still match the installed equipment. A short record of the review, signed by the owner, closes the loop each year.

Common mistakes

  • Buying a generator, not a solution.
  • No studies in the scope.
  • Testing left out.
  • Quotations on different scopes.

What to send us

Send your answers to the four questions and your load list. WhatsApp 98852 01608 or use the application engineering enquiry.

Evidence note. The example is illustrative.

Questions engineers ask

What are the six stages of a complete backup solution?

Requirement, architecture, sizing and studies, build, commissioning and operation. Each produces its own output, from a classified load list to signed test records and a maintenance plan. Skipping a stage is the most common reason a standby system fails on the day it is needed.

How are loads grouped when planning backup power?

Into no-break loads that need a UPS or battery, short-break loads that the generator restarts after a few seconds, long-break loads that can be shed during an outage, and loads deliberately left off backup. A load list giving each item its class, kW and starting method guides the whole design.

What documents should I receive when the system is finished?

The classified load list, the as-built single-line diagram, the sequence of operation, the protection settings schedule, the commissioning test records and the maintenance plan with its records. Together they let anyone understand, test, extend and maintain the system years later without guesswork or repeated surveys.

Does a small office need the same process as a hospital?

No. The approach scales with the consequence of losing supply. A small office needs a load list, a sizing check and a correctly installed changeover, while a hospital or process plant needs load studies, protection studies, integrated testing and formal signed records at every one of the six stages.

Where do I start if I only know I need backup?

List what must stay on and for how long. That is the first input to any design. For each load, note whether it can accept a break of a second, a minute or an hour, and how long it must run during an outage, which together decide where UPS, generator capacity and fuel storage are needed.

Do I need studies before buying a generator?

At least a load and sizing review. Larger or more complex sites need studies too. A small office may need only a load list and a sizing check, while a hospital or plant with large motors, drives and several sources needs motor starting, protection and harmonic studies before the generator is chosen.

Can one supplier deliver everything?

Many projects use one lead partner for coordination. Confirm scope and responsibilities. Write down who designs, supplies, installs, tests and maintains each part, and who is responsible for the interfaces between them, because problems most often appear where one contractor scope ends and another begins.

How do I keep the solution working over time?

Maintenance, testing, monitoring and review when loads change. Oil and filters every 250 to 500 running hours or six months, whichever comes first, coolant every year, regular load tests and a yearly review of the load list keep the system healthy and matched to the site.

This guide gives general principles. Solutions are confirmed after a site review.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.

CallWhatsAppEnquire