Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Textile Industry Power

How to plan standby and prime diesel generator power for spinning, weaving, dyeing and finishing units, including humidification, drives and restart sequencing.

In short. A textile mill is a drive-dense, humidity-dependent, continuous process, so its generator must be sized on the restart sequence and the humidification plant, not on the connected load. Spinning and weaving tolerate a short break if machines restart in a controlled order; dyeing and finishing often cannot. Classify departments by consequence, size for the largest motor start on top of the running load, and allow for harmonic current from inverter drives.

Why a textile load is different from a factory load

A spinning mill in Telangana or Andhra Pradesh runs around the clock, and electricity is usually its second largest cost after fibre. The load is made up of hundreds of small and medium motors on blow room, cards, draw frames, speed frames, ring frames, autoconers and looms, plus a humidification plant that can be a fifth of the whole demand. Very little of it is resistive, much of it is on variable-frequency drives, and almost none of it can simply be switched back on together after an outage.

The consequence of an interruption is also unusual. On a ring frame an outage breaks ends across the whole machine, and the piecing work that follows costs more production than the outage itself. In a dye house a stopped jet or soft-flow machine mid-cycle can mean shade variation and a re-dye. On a stenter, a stop with fabric in the chamber can scorch the cloth. These are process losses, not just lost minutes, and they decide what the generator must protect.

Classify departments by consequence, not by kW

The useful first step is a department-by-department table that records what happens one second, one minute and one hour after supply is lost, and what must be running before that department can restart. The pattern below is typical of composite mills, although the numbers belong to each site.

DepartmentConsequence of a short outageMust be live before restartUsual backup class
Blow room and cardsLap and sliver breaks, cleaning timeFiltration and waste suctionShort break, staged restart
Ring frames and autoconersEnd breaks across the frame, piecing labourHumidification, compressed airShort break, one frame at a time
Looms (air-jet, rapier)Stop marks, weft breaksCompressed air at pressureShort break, motor first
Dyeing and finishingShade variation, scorching, re-processingThermic fluid or boiler auxiliariesEssential, short break
Humidification plantRH drift, yarn breakage rises within minutesNone, it is the enablerEssential, first on the bus
Offices, lighting, canteenInconvenienceNoneShed or restore last

Two points usually surprise mill owners. The humidification plant and the compressed-air plant are production enablers and belong at the top of the restoration list. And the processes that look least electrical, such as dyeing, often have the least tolerance for a break. A structured approach is described in critical-load classification and prioritisation.

Sizing: running load, starting steps and harmonics

Three things set the generator rating in a textile mill. The first is the running load of the departments to be backed up, measured rather than taken from nameplates, because textile motors run well below rated output most of the time. The second is the largest load step that will be applied during restart, which is normally a humidification fan bank, a chiller or a compressed-air plant started direct-on-line. The third is the harmonic current drawn by inverter drives, which heats the alternator and distorts voltage for every other machine on the bus.

S = P / PF

Here S is apparent power in kVA, P is the real running load in kW and PF is the power factor at the generator terminals, typically 0.8 for sizing. For a spinning unit with a measured running load of 900 kW on the protected departments, S is 1125 kVA at 0.8 PF (illustrative).

If the largest single start is a 110 kW humidification fan on a star-delta starter, the step is manageable on a set of that size, but if a 160 kW screw-type machine must start direct-on-line, the transient dip should be checked using the method on motor starting on generators. Where more than a third of the load is on variable-frequency drives, many engineers specify the alternator one frame size larger or request the manufacturer’s nonlinear load rating; see harmonics and THD.

One large set or several smaller sets

Mills that need the whole process on backup often do better with two or three sets in parallel than with one large unit. Partial load is then carried by fewer engines at better efficiency, one set can be serviced without losing backup, and the controller can add sets as departments restart. The trade-offs are covered under generator paralleling.

Restart sequencing is where the plan succeeds or fails

A generator that is correctly sized can still trip on restart if the operators or the AMF panel reconnect everything at once. A workable sequence for a spinning unit looks like this.

Where the mill has a load management system, these priorities should be programmed as timed steps; where restart is manual, they should be printed and posted at the PCC. Either way the sequence has to be rehearsed on a planned test, not discovered during a monsoon outage. Guidance is on restart sequencing.

Keeping the plan aligned with the mill

Textile demand changes with count, blend and machine replacement. A move to compact spinning, the addition of autoconers, or a new humidification plant can shift the running load by a quarter without anyone updating the generator file. Record the assumptions used when the set was sized, including which departments were included and the measured load that day, and review them whenever machinery changes. Note planned expansions so that generator room space, cable routes and fuel storage are not boxed in. The general method for this is set out on generator sizing, and the wider industrial context on industry power solutions.

Classifying a spinning mill by consequence (illustrative)

A spinning mill’s departments differ in what an outage costs. Classifying them by consequence rather than by kW decides what the generator carries.

DepartmentConsequence of an outageGenerator treatment
Humidification plantHumidity falls, yarn breaks rise when production resumesProtected, restarted early
Ring framesEnds down, waste and restart labourProtected in groups where the set allows
Autoconer and windingPackage quality and restart effortProtected, restarted after ring frames
Blow room and cardingMaterial chokes and restart effortRestarted in sequence
Compressed-air plantPneumatic controls and cleaning stopProtected
Offices and non-production areasInconvenienceShed

A restart sequence that works

  1. Controls and drive electronics hold on UPS or ride through the transfer.
  2. Humidification plant and the compressed-air plant restart first.
  3. Ring frames restart in groups, with time between groups for the set to recover.
  4. Autoconers and winding follow.
  5. Blow room and carding restart last, under supervision, so material flow resumes cleanly.

Restarting everything at once is the commonest reason a mill generator trips; staggering the groups lets a correctly sized set carry the mill.

Drives and harmonics in textile mills

Modern ring frames, looms and fans run on inverter drives, which draw distorted current. When a large share of the generator load is drive load, the alternator is selected with margin for it, and voltage distortion is measured on generator supply during commissioning. On our standard, oil and filters are changed every 250 to 500 running hours or six months, whichever comes first, coolant is replaced every year, and air filters are cleaned often in fibre-laden air.

Fibre and the generator room

Cotton fibre in the air settles on radiators and air filters and blocks them within days. The set is placed where it draws clean air, with its intake away from the production halls, and the radiator is cleaned from the fan side outwards at every check.

Sizing for the restart, not the total

A mill with 900 kW of connected load may protect around 450 kW of humidification, ring frames, winding and the compressed-air plant. At 0.8 power factor that is about 560 kVA of running load, and the restart groups decide the margin. A 750 kVA set carries it at about 75% with groups restarted in order; trying to restart the whole protected load at once would need a far larger set and still risk a trip.

Common mistakes

What to send us

Send a department-wise load list with measured running kW where you have it, the single-line diagram of the mill, the rating and starter type of the humidification fans, motors and chillers, and a note on which departments must stay in production on backup. Photographs of the existing generator nameplate and the AMF or PCC panel help if a replacement or an addition is being considered. Send your textile power requirement.

Questions engineers ask

In what order should a spinning mill restart on generator power?

Controls hold on UPS or ride through, the humidification plant and compressed-air plant restart first, ring frames follow in groups with time for the set to recover, then autoconers and winding, and finally blow room and carding under supervision. Restarting everything at once is the commonest reason a mill generator trips.

How large a generator does a spinning mill need for its protected load?

For about 450 kW of protected humidification, ring frames, winding and compressed air, the running load is about 560 kVA. Restarting in groups, a 750 kVA set carries it at about 75%; restarting everything at once would need a far larger set and still risk tripping.

What size generator does a spinning mill need?

There is no rule of thumb per spindle that survives contact with a real mill. Measure the running load of the departments you intend to back up, add the largest motor start, and allow for the nonlinear load from drives. A unit with 900 kW measured running load typically lands in the 1000 to 1250 kVA range (illustrative), but the sequencing plan matters as much as the rating.

Should the humidification plant be on the generator?

Usually yes. When humidity falls, yarn breaks rise sharply as production resumes, so the humidification plant is restarted early in the sequence. Its large fans and pumps are restarted in steps, and their drive load is allowed for in the alternator selection so voltage stays clean for the ring frames that follow.

Do inverter drives on ring frames and looms affect generator selection?

Yes. Drives draw distorted current, and when they form a large share of the load the alternator is selected with margin for it and the voltage regulator chosen to suit. Voltage distortion is measured on generator supply during commissioning, at the real mill load, to confirm the choice.

Is it better to back up the whole mill or only critical departments?

That depends on how long outages last and what a stopped department costs. Many mills protect humidification, compressed air, dyeing and a subset of spinning or weaving, and shed the rest. The decision should be written down with the reasons, so it can be revisited.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.