In short. An irrigation generator should be sized from the water requirement, not from pump horsepower or borewell depth. Flow and total head define the hydraulic power, pump and motor efficiencies convert it to electrical demand, and the motor starting method usually decides the generator kVA. Cable length to a submersible pump and high summer temperatures in Telangana then refine the choice. Getting the starting calculation right avoids the most common failure, a set that runs the pump but cannot start it.
Water first, then kVA
The farm needs water, the pump needs torque, the motor needs voltage and the generator must deliver all three at the right moment. That gives a clear engineering chain: water requirement, flow and head, pump, motor, starting method, cable, generator and finally the energy source, whether diesel, solar, battery or grid.
A common request is to match a borewell depth to a generator size. Bore depth alone does not establish generator size, because the pump’s duty depends on the dynamic water level, the delivery height and pipe friction, not the drilled depth.
Agricultural applications are not all the same
- Submersible borewell pumps, very common across Telangana, where long drop cables add voltage drop.
- Surface centrifugal pumps lifting from canals, tanks or open wells.
- Drip and sprinkler systems, which need steady pressure and often run filtration and fertigation equipment.
- Farm processing loads such as dryers, small mills, cold rooms and dairy chillers.
- Poultry and livestock sheds, where ventilation and lighting loss affects animal welfare within hours.
Each has a different load shape, and none should receive a generic HP-to-kVA recommendation.
From flow and head to electrical demand
Total head is the sum of the static lift from pumping water level to delivery point, plus friction losses in pipes and fittings, plus any pressure needed at the outlet. It is usually different from bore depth.
Pe = (ρ × g × Q × H) / (1000 × ηp × ηm)
Here Pe is the electrical input in kW, ρ is water density (about 1000 kg/m³), g is 9.81 m/s², Q is flow in m³/s, H is total head in metres, and ηp and ηm are the pump and motor efficiencies from the pump curve and motor data.
Example (illustrative): a borewell pump delivers 10 litres per second (0.010 m³/s) against a total head of 60 m. Hydraulic power is 1000 × 9.81 × 0.010 × 60 / 1000, or about 5.9 kW. With a pump efficiency of 0.60 and motor efficiency of 0.85, electrical input is about 11.5 kW. At a running power factor of 0.8 that is roughly 14.4 kVA. The starting demand, discussed below, will be several times larger.
Pump horsepower is an input, not the answer
When a customer says they have a 10 HP pump, that tells us the motor’s nominal output. We still need the voltage, whether the motor is single-phase or three-phase, full-load current, power factor, starting method, cable length and whether other loads run at the same time. A rule of thumb that multiplies HP by a fixed number ignores the factor that matters most, which is starting.
Motor starting usually governs
A pump motor draws far more current while accelerating than when running. Running kW is not starting kVA.
| Starting method | Typical starting current | Effect on generator size | Where it fits |
|---|---|---|---|
| Direct-on-line | About 6 to 8 times full-load current | Largest; often two to three times the running kVA requirement or more | Small motors, simple installations |
| Star-delta | About one third of DOL current | Reduced, but a transition surge occurs | Surface pumps that can start lightly loaded |
| Soft starter | Adjustable, commonly 2.5 to 4 times | Moderate | Larger pumps where a smaller set is wanted |
| Variable-speed drive | Close to full-load current | Smallest starting margin, but harmonics need review | Pressure-controlled drip and sprinkler systems |
Figures are typical ranges; the motor and starter data for the actual equipment govern. Starting current also depends on pump torque, acceleration time and the voltage dip the motor can tolerate. No universal multiplier should be applied without checking these.
Cable, voltage and site conditions
A submersible motor may sit 100 metres or more below the surface, and the drop cable plus the run from the generator adds resistance. Voltage drop during starting can be large enough that the motor fails to accelerate even when the generator is adequately sized. Our generator cable sizing page explains the calculation. Summer ambient temperatures in Telangana regularly exceed 40 °C, so generator output and cooling should be checked against derating data, and enclosures should be placed in shade with free airflow.
Choosing the energy source
Diesel generators suit intermittent irrigation, emergency backup when grid supply to agricultural feeders is restricted, and remote fields. Solar pumping suits daytime irrigation with low running cost, and a small generator can back it up during cloudy monsoon spells. Battery storage helps with sensitive loads such as dairy chillers and poultry ventilation. Where several pumps share a set, sequence their starts so only one motor accelerates at a time. Compare with water and wastewater power for larger pumping schemes, and see rental power for seasonal or short-term needs.
From water need to generator size (illustrative)
A farmer needs 30 cubic metres an hour from a borewell where the pumping water level is 60 metres below ground, delivered to a tank 10 metres high through a pipe with about 10 metres of friction loss. The working below shows how the generator follows from the water.
| Step | Working | Result |
|---|---|---|
| Total head | 60 + 10 + 10 metres | 80 metres |
| Hydraulic power | Flow 30 m³/h × head 80 m ÷ 367 | About 6.5 kW |
| Pump and motor efficiency | Combined about 55% for a submersible set | About 11.9 kW electrical input |
| Motor chosen | Nearest standard submersible rating | 15 HP, 11 kW, running near full load |
| Starting | Direct on line, several times running current | Start decides the set size |
| Generator | Running about 15 kVA, start allowed for | About 30 to 40 kVA, less with a soft starter |
The pump curve for the actual pump confirms the duty point; the table shows why the borewell depth alone does not decide the motor, and why the motor start, not its running load, usually decides the generator.
The long cable down the borewell
Submersible pumps sit deep, and their cable can be well over a hundred metres from the starter. The voltage drop in that cable adds to the dip from the generator during starting. If the motor terminal voltage falls too far, the pump struggles to start or trips on overload. The cable is sized for the running current and length, and the starting voltage at the motor is checked rather than assumed from the generator terminals.
Seasonal care for farm generators
- Before the season: change oil and filters, test the battery, check belts and hoses and clean the radiator.
- During harvest: clean air filters and radiator fins often, because chaff and dust block them quickly.
- Fuel: keep it in clean, closed containers, drain water from the tank, and avoid fuel left standing for months.
- Off-season: run the set on load regularly rather than leaving it idle, or store it properly with fresh fuel and a charged battery.
On our standard, oil and filters are changed every 250 to 500 running hours or six months, whichever comes first, and coolant is replaced every year. A set irrigating ten hours a day reaches 250 hours in under a month of peak season.
One generator for several pumps
Farms with more than one pump often try to run them all from one set. That works when the pumps are started one at a time, the largest first, and the set is sized for the running load of all pumps plus the start of the last one. Starting two pumps together on a set sized for one start is the commonest reason a farm generator trips.
Generators alongside solar pumps
Solar pumps cut fuel use dramatically in sunny months, but cloudy days, early mornings and evening irrigation still need power. A generator that backs up a solar pump is connected through the pump controller’s AC input where it has one, or through a changeover that keeps the two sources apart. The set is sized for the controller and motor starting, and run on load when it is used, rather than idling for hours as a just-in-case source.
Keeping a simple log of litres used and hours run each week also shows when a pump is working harder than before, which often points to a falling water level or a worn pump before it fails.
Common mistakes
- Sizing from borewell depth. The pump duty is set by water level and head, so the set may be badly undersized or oversized.
- Multiplying pump HP by a fixed factor. The starting method and cable are ignored, and the set stalls when the motor starts.
- Ignoring voltage drop in long drop cables. The motor overheats or fails to start, and windings burn out.
- Starting several pumps together. The combined inrush trips the generator.
- Running a single-phase pump from one phase of a lightly loaded three-phase set without checking imbalance. The set runs with unbalanced voltage that damages other loads.
What to send us
Send the pump nameplate photo, motor rating and voltage, starting method, flow required, pumping water level and delivery height, cable length and size, and any other loads that run at the same time. Site photos showing where the generator will stand help with cooling and access. Use the generator sales enquiry and we will check the starting case before recommending a size.
Questions engineers ask
How is a borewell pump motor sized from water need?
Add the pumping water level, the delivery height and friction losses for total head, then hydraulic power is flow in cubic metres per hour times head in metres divided by 367. Divide by the combined pump and motor efficiency for electrical input. For 30 cubic metres an hour at 80 metres that is about 12 kW, so a 15 HP motor.
Can one generator run several farm pumps?
Yes, if the pumps are started one at a time, largest first, and the set is sized for the running load of all pumps plus the start of the last one. Starting two pumps together on a set sized for a single start is the commonest reason a farm generator trips.
What size generator do I need for a 10 HP borewell pump?
It depends mainly on the starting method and cable length. A 10 HP motor on direct-on-line starting usually needs a generator well above its running requirement, while a soft starter or drive reduces that. Send the motor data and we will calculate it rather than guess.
Why does my generator run the pump but fail to start it?
Starting current is several times running current, and the voltage dip during starting may stall the motor. Long cables down the borewell and undersized sets make it worse. A larger set, a reduced-voltage starter or a heavier cable usually solves it, after checking the starting voltage at the motor itself.
Is borewell depth the same as pump head?
No. Head is measured from the pumping water level to the delivery point plus friction losses, and the water level is often far above the bottom of the bore. Use the pump curve and the actual water level for sizing, because using bore depth leads to an oversized motor and a larger set than needed.
Can a generator back up a solar pump?
Yes, if the solar pump controller accepts an AC input or a changeover arrangement keeps the two sources apart. Size the generator for the pump motor and controller starting characteristics, check the guidance of the controller maker first, and run the set on load when used rather than leaving it idling.
How does summer heat affect an irrigation generator?
High ambient temperature reduces available output and stresses the cooling system. Check the derating data for the set, keep it shaded and well ventilated, keep the radiator and air filter clean during dusty harvest periods, and service on time, because peak season brings the most running hours.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.