In short. Runtime equals usable fuel divided by the consumption rate at the load the set will actually carry. Size the tank for the outage you plan to ride through, allow for fuel that cannot be drawn and for a reserve, and plan resupply for anything longer. Check the result at full load as well as typical load, and remember that a tank of old, wet fuel is not the same as a tank of usable fuel.
Who this page is for: For facility managers, consultants and owners deciding tank size, autonomy and refuelling arrangements for standby or prime generators.
Diesel generator calculator
Fuel use, runtime, tank size and cost
How this is calculated
Real power is kVA × power factor. Fuel use is estimated as L/h ≈ 0.04 × rated kW + 0.22 × load kW, which follows the usual shape of modern diesel gensets: about 0.26 L per kWh near full load, rising towards 0.38 L per kWh at a quarter load because the engine’s fixed losses are spread over less output.
If you enter the full-load figure from your engine datasheet, the curve is scaled to match it. Runtime is usable fuel ÷ L/h. Tank size is L/h × hours, plus the reserve margin, divided by the usable fraction.
These are planning estimates, typically within 10 to 15% of a healthy engine. Actual use depends on the engine model, its condition, altitude, ambient temperature and how the load varies. For a figure you can rely on, use the manufacturer’s fuel curve or a metered test.
Estimates only, worked out in your browser. For a checked selection, send us your load list and site details or call 98852 01608.
Key facts
- Runtime (h) = usable fuel (L) ÷ fuel rate (L/h).
- Tank volume (L) = fuel rate × target hours ÷ usable fraction.
- A usable fraction of about 0.8 to 0.9 is common; check the tank’s pickup and design.
- Check runtime at full load, not only at typical load.
- Plan resupply before the tank reaches its reserve, with an agreed delivery arrangement.
- Fuel storage brings safety, spill and approval requirements that must be checked locally.
The calculation
Worked example: 24 hours for a 500 kVA set (illustrative)
A 500 kVA set usually runs at about 75% load, burning about 81 litres per hour; at full load it burns about 104 litres per hour. The site wants 24 hours of autonomy with a usable fraction of 0.85.
| Step | Working | Result |
|---|---|---|
| Tank needed at typical load | 81 × 24 ÷ 0.85 | About 2290 litres |
| Standard tank chosen | Next size up | 2500 litres, about 2125 usable |
| Runtime at 75% load | 2125 ÷ 81 | About 26 hours |
| Runtime at full load | 2125 ÷ 104 | About 20 hours |
| Refill trigger with an 8-hour delivery time and a 4-hour reserve | (8 + 4) × 104 | Order when about 1250 litres usable remain |
The tank meets 24 hours at the usual load but not at full load. If full-load outages of a day are likely, either size up or make the refill arrangement part of the design. See the fuel consumption estimator and the fuel chart.
Do not count the whole tank as runtime. Allow for fuel below the pickup, keep a reserve, check full-load runtime, and agree how fuel will be delivered during a long or regional outage.
Tank arrangements
| Type | Use | Notes |
|---|---|---|
| Base tank | Small to medium sets | Compact; runtime limited by size |
| Day tank | Small tank near the engine, fed from bulk storage | Needs transfer pumps, level control and alarms |
| Bulk tank | Larger storage, above or below ground | Location, bunding and approval rules apply |
Fuel quality
Stored diesel gathers water and can grow microbes at the fuel-water interface. Drain water, sample the fuel, polish it where needed and rotate stock, so the fuel is usable when the outage comes. See fuel cleaning and polishing.
Safety and approvals
Storage above certain quantities needs approvals, bunding, ventilation, fire precautions and spill control under local rules. Check them before choosing tank size and location.
Autonomy worksheet
| Item | Value |
|---|---|
| Fuel rate at typical and full load (L/h) | |
| Target autonomy (h) | |
| Tank size and usable fraction | |
| Runtime at typical and full load (h) | |
| Delivery time and refill trigger level (L) |
Working out autonomy step by step
- Decide the load the set will carry during an outage, in kW, from measurement or the load list, not from the set rating.
- Find the fuel consumption at that load from the maker data, in litres per hour, or estimate it from a litres-per-kWh factor.
- Find the usable fuel: tank capacity minus the unusable heel at the bottom and any space left at the top.
- Divide usable fuel by consumption to get running hours.
- Compare the hours with the longest outage the site must ride through, plus the time to arrange a refill.
A worked autonomy check (illustrative)
A 250 kVA set carries an outage load of 160 kW. At about 0.27 litres per kWh, it uses about 43 litres per hour. Its base tank holds 990 litres, of which about 80%, or 792 litres, is usable once the heel and top space are allowed for. Autonomy is 792 divided by 43, about 18 hours. If the site must ride through a 24-hour outage, it needs about 24 × 43, or 1032 litres usable, so either a larger tank or a guaranteed refill within 18 hours is required.
| Outage load | Litres per hour | Hours on 792 litres usable | Usable litres for 24 hours |
|---|---|---|---|
| 100 kW | about 27 | about 29 | about 648 |
| 160 kW | about 43 | about 18 | about 1032 |
| 200 kW | about 54 | about 15 | about 1296 |
The figures show why autonomy is stated at the real outage load. The same tank gives almost twice the hours at 100 kW as at 200 kW.
Light load changes the factor
Litres per kWh rise at light load, because the engine is less efficient there. At 25% load, a set may use 0.32 to 0.35 litres per kWh instead of about 0.26 to 0.27 near full load. Using the full-load factor for a lightly loaded set overstates autonomy. Where the outage load is light, take the consumption at that load from the maker curve, and confirm it later from the site fuel records.
Planning refills
For long outages, autonomy is a combination of stored fuel and the ability to refill. A written refill plan names the supplier, the delivery route, the time needed from call to delivery, who authorises the order and how the delivery is checked. Storms and floods that cause long outages can also close roads, so critical sites keep enough fuel on site to cover a realistic delay in delivery, not just the normal lead time.
Day tanks and bulk tanks
Larger installations often have a bulk tank feeding a day tank near the engine through a transfer pump. Autonomy then depends on the bulk tank contents, but the engine stops if the day tank runs dry because the transfer pump has failed or lost its supply. The transfer pump is fed from a protected supply, has a level alarm and a high-level cut-off, and is tested with the rest of the system. A day tank of 1000 litres on a set using 230 litres per hour lasts a little over four hours without transfer, which is the time available to correct a pump fault.
Using fuel records to correct the estimate
Once the set has run through a few outages, the fuel register gives the real figure. Litres delivered, tank dips before and after, and running hours over a period give litres per hour at the site load, and dividing by the energy generated gives litres per kWh. If the measured figure differs from the planning factor, the autonomy table is corrected, and a figure that rises over time points to an engine needing attention.
The corrected table is kept at the set with the date it was updated, so operators planning for a long outage use the measured figure rather than the original estimate, and the reserve held on site is adjusted when the outage load or the duty of the set changes.
Common mistakes
- Counting the full tank as usable.
- Checking runtime at typical load only.
- No resupply arrangement.
- Fuel stored for years without testing.
What to send us
Send the generator model, the typical load, the tank size and the autonomy you need. WhatsApp 98852 01608 or use the enquiry form.
Evidence note. Fuel rates are typical values for illustration; the engine maker’s table and local storage rules govern.
Questions engineers ask
How do I calculate generator runtime from my tank?
Find the fuel consumption at the real outage load, work out usable fuel by allowing for the heel and top space, and divide usable fuel by consumption. A 250 kVA set at 160 kW using about 43 litres per hour runs about 18 hours on 792 usable litres.
Why should autonomy be stated at the outage load and not the rating?
Because consumption depends strongly on load. The same 792 usable litres last about 29 hours at 100 kW but only about 15 hours at 200 kW. Using the rating or full-load consumption understates or overstates autonomy, so the real outage load is always used for the calculation.
What should a fuel refill plan include?
The supplier, the delivery route, the time from call to delivery, who authorises the order and how deliveries are checked. Storms that cause long outages can also close roads, so critical sites keep enough fuel to cover a realistic delivery delay, not just the normal lead time.
Why can a set stop with fuel in the bulk tank?
Where a transfer pump feeds a day tank, the engine stops if the day tank runs dry because the pump failed or lost its supply. A 1000-litre day tank at 230 litres per hour lasts a little over four hours, which is the time to correct a pump fault.
How many hours of fuel should I store?
It depends on your outage risk and resupply options. Many critical sites plan for a day or more, with resupply for beyond. Runtime equals usable fuel divided by consumption at the expected load; for example, 800 litres usable at 40 litres per hour gives 20 hours. The resupply contract and route are confirmed before they are needed.
How long can diesel be stored?
It depends on conditions and treatment. Sample and test it regularly, and polish or replace it as needed. Water, heat and air degrade diesel and allow microbial growth, which blocks filters, so tanks are kept full, water is drained from the bottom regularly, and a sample is checked for water and sediment at each service.
Do I need a day tank?
For larger bulk storage, usually yes, to feed the engine safely and consistently. A day tank near the engine gives a steady feed at the right head, limits the fuel inside the plant room, and is refilled automatically from the bulk tank by a transfer pump with level controls, overfill protection and an alarm on failure.
Are there rules for storing fuel?
Yes. Quantities, location, bunding and licensing are regulated locally. Check with the authorities. Larger quantities may need approvals, separation from buildings and boundaries, fire protection and a bund that holds a leak. The rules are confirmed before the tank is ordered, because they affect its size, location and design.
Figures are illustrative. Fuel storage must comply with applicable regulations.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.