In short. In December 2007 a global oilfield services company appointed Reddy Generators to supply the temporary power for a project site: a fleet of diesel generators from 1.5 kVA to 200 kVA, cable junction boxes and distribution boards, and an operating crew of one technician and three operators, with erection, commissioning and transport included. Everything in the order was supplied, and the hire ran for about two and a half years.
| Client | A global oilfield services company (name withheld) |
|---|---|
| Order | December 2007; equipment due on site 18 December 2007 |
| Duration | About two and a half years |
| Scope | Rental supply, erection, commissioning, transport, operation and maintenance |
| Generators | 2 × 200 kVA three-phase, 2 × 75 kVA three-phase, 2 × 15 kVA single-phase, 1 × 1.5 kVA single-phase |
| Distribution | 2 sets of cable junction boxes and distribution boards |
| Crew | 1 technician and 3 operators on site |
The requirement
Oilfield and offshore projects need temporary power long before a permanent supply exists: workshops, offices, lighting, hand tools and equipment testing all have to run from the first week on site. The loads are scattered, they are not all live at the same time, and they grow and shrink as the project moves through its phases. The client wanted a single contractor to deliver, install, run and maintain the supply, so that its own teams could concentrate on the project.
Why a mixed fleet, not one big generator
A single large generator would have run most of the time at light load, burning fuel inefficiently and putting every load on one machine. The order instead matched set sizes to the loads: two 200 kVA sets for the main loads, two 75 kVA sets for secondary areas, 15 kVA single-phase sets for small loads and offices, and a 1.5 kVA set for the smallest point loads. Each engine runs nearer its efficient range, and a fault on one set affects only its own area.
| Equipment | Quantity | Typical role on a project site |
|---|---|---|
| 200 kVA, three-phase | 2 | Main workshop and process loads |
| 75 kVA, three-phase | 2 | Secondary areas and backup capacity |
| 15 kVA, single-phase | 2 | Offices, cabins and small loads |
| 1.5 kVA, single-phase | 1 | Isolated point loads |
Work performed
- Transport of all generators to site
- Erection and commissioning, including cable junction boxes and distribution boards
- On-site operation by one technician and three operators
- Routine servicing and breakdown attendance throughout the hire
Matching each set to its job
A mixed fleet works because each set is sized for the load it serves. Large sets carry the heavy, steady work; medium sets serve areas that run independently; small single-phase units cover isolated loads that would otherwise keep a large engine idling.
| Set size (from this fleet) | Typical role on such a site (illustrative) |
|---|---|
| 200 kVA three-phase | Main workshops, testing bays and large equipment |
| 75 kVA three-phase | Offices, stores and smaller workshops |
| 15 kVA single-phase | Remote cabins, gate houses or lighting groups |
| 1.5 kVA single-phase | Small isolated loads such as instruments or a security point |
Worked example: the cost of one big set at light load (illustrative)
Suppose a site needs 250 kW in the busiest daytime hours but only about 30 kW at night. A single 500 kVA set giving 400 kW would run at under 10% load overnight, where fuel use per kWh is poor and the engine suffers from wet stacking. With a mixed fleet, the night load can run on a 75 kVA set at about half its rating, while the large sets stop. Over months of nights, the fuel saved and the reduced engine wear are substantial.
Distribution with junction boxes and boards
Cable junction boxes and distribution boards let the fleet feed scattered loads safely. Each board is protected, earthed and labelled, with residual current devices on circuits for tools and outdoor sockets. Junction boxes allow cables to be extended or rerouted as the site layout changes without making unsafe joints. Each set has its own earthing, and where sets feed adjacent areas the earthing is bonded so no dangerous voltage appears between equipment fed from different sets.
Roles in an operating crew
| Role | Main duties |
|---|---|
| Technician | Servicing, fault finding, electrical checks and planning maintenance across the fleet |
| Operators | Starting and stopping sets, daily checks, refuelling, logging hours, fuel and readings |
A crew of this kind turns a collection of machines into a managed power system, with one log and one plan for the whole fleet.
Adapting the fleet as the project changes
Over a hire of two and a half years, a site passes through several phases: mobilisation, peak activity and wind-down. Loads grow and shrink, and work areas move. A mixed fleet adapts by moving sets between areas, starting and stopping them with demand, and releasing the ones no longer needed. Reviewing the fleet against the actual loads every few months keeps each set matched to its job.
Service across a fleet
With seven sets of different sizes and running patterns, service is planned set by set from running hours and calendar time: oil and filters at 250 to 500 hours or six months, whichever comes first, and coolant yearly. A fleet log shows which set is due next, so the technician can plan visits around work on site and keep spares for each engine type.
Fuel for a mixed fleet
Several sets of different sizes mean several fuel tanks to keep filled. A daily refuelling round by the operators, recording fuel issued to each set against its hours, keeps every tank above a safe level and makes losses easy to spot. Bulk fuel stored on site is protected, bunded and issued through a single controlled point.
Lessons for project sites with scattered loads
Scattered, changing loads are best served by a fleet matched to them, a proper distribution system, and a crew that runs it as one system. That combination saves fuel, limits the effect of any fault, and lets the project teams concentrate on their own work while the power supply follows the project through every phase.
When single-phase sets make sense
Small single-phase sets are often overlooked, but they solve a real problem. A gate cabin, a remote lighting group or a single instrument would otherwise need a long cable from a large set, or keep that set running at night for a few hundred watts. A dedicated small unit near the load avoids the long cable, saves fuel and keeps the larger sets free to stop when they are not needed.
Clean power for equipment testing
Oilfield services include testing of tools and electronic equipment before they go to the field. Testing needs stable voltage and frequency. Feeding test bays from a set that does not also carry welding or large motor starts, and adding a UPS for sensitive instruments, keeps test results reliable.
Safety on an oilfield services base
Bases handle fuels, chemicals, pressurised equipment and heavy lifts. Generators are placed away from fuel and chemical stores and from any area the site safety team classifies as hazardous, stand on bunded bases, and are kept clear of lifting routes. Earthing is tested after every move, cables are protected at vehicle crossings, and the crew follows the site permit system for hot work and electrical isolation.
Records for the client
A monthly summary for each set, covering hours, fuel, services, faults and any moves, gives the client a clear picture of its temporary power and supports billing. Over a long hire, these records also show how the site load changed through each phase of the project.
Demobilising a fleet
- Release sets in stages as areas close, rather than all at the end.
- Prove any replacement supply before disconnecting each area.
- Record final hours and fuel for every set.
- Recover cables, junction boxes and boards, and leave each area clean.
- Hand over the final records to the client.
Avoiding light-load damage
A diesel engine that runs for long periods at very light load does not burn its fuel completely. Unburnt fuel and soot build up in the exhaust and cylinders, a condition known as wet stacking, which raises smoke, wastes fuel and shortens engine life. Matching set size to load is the main defence, and any set that must run lightly for a while is given a period at higher load, or a load-bank run, to clean it out.
Spares for several engine types
A mixed fleet usually means several engine models, each with its own filters, belts and parts. Holding a small stock for each type on site, labelled by set, lets the technician service on time and fix common faults without waiting. The stock is checked at each service and topped up before it runs out.
Handover between crew members
On a long hire, crew members change shifts and occasionally leave the project. A written handover at each change, covering the state of every set, services due, faults open and fuel levels, keeps the fleet running without gaps in knowledge.
Outcome and limits
The full package was supplied and kept in service for about two and a half years, a long-duration hire in which maintenance, fuel and operator cover mattered as much as the equipment itself. This record is based on the client’s purchase order and our own account of the contract; detailed performance logs are not published.
Questions engineers ask about this project
Why does a mixed generator fleet save fuel?
Because each set runs near a healthy load. In the illustrative case, a single 500 kVA set carrying 30 kW at night would run under 10% load, while a 75 kVA set carries the same night load at about half rating and the large sets stop.
How are scattered site loads distributed from several generators?
Through protected, earthed and labelled distribution boards and cable junction boxes, with residual current devices on tool and outdoor circuits. Junction boxes allow safe extension as the layout changes, and earthing of neighbouring sets is bonded to avoid voltage differences. Each board is inspected regularly.
How is a generator fleet adapted as a project changes?
By moving sets between areas, starting and stopping them with demand and releasing those no longer needed, with the fleet reviewed against actual loads every few months through mobilisation, peak activity and wind-down so each set stays matched to its job. Released sets reduce cost and fuel use.
What is wet stacking and how is it avoided?
Wet stacking is the build-up of unburnt fuel and soot when a diesel runs at very light load for long periods. Matching set size to load prevents it, and any set that must run lightly is given periods at higher load or a load-bank run to clean it out.
What does an operating crew actually do on a long hire?
Daily checks on oil, coolant, fuel and battery condition, logging hours and load, switching sets as the site load changes through the day, refuelling, and first-line fault attendance. On a hire measured in years, that routine is what keeps availability up; the equipment itself is the easier half.
Why use several generator sizes instead of one large set?
Loads differ in size, location and hours. Matching sets from 1.5 kVA to 200 kVA to each load keeps every engine at a healthy loading, saves fuel, and means one breakdown never darkens the whole site. Spare sets cover service downtime, and each set is load-bank tested before dispatch.
What does an operated rental include?
Here it included a technician and three operators on site, so the equipment was started, monitored, refuelled and serviced by people who knew it, rather than by the client’s own staff. Operators keep a daily log of running hours, fuel, readings and alarms, so problems are noticed early and the client sees exactly how each set was used.
Engineering record reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Client name withheld under the confidentiality terms of the order. Source: client purchase order on file. Last reviewed: 20 October 2026.
Related: rental power · rental distribution · oil and gas power · all verified projects