Engineering Notes

Short generator engineering notes on single calculations such as fuel per kWh, load testing and diagnostics, with inputs, units and limits stated clearly.

In short. An engineering note answers one narrow question, such as how efficiently a generator converts diesel to electricity or what a load test actually proves, with its inputs, units and boundary made visible. Its value is a traceable basis. A correct equation applied to the wrong boundary still gives the wrong answer, so every note states what was measured, what was assumed and which decision the result supports.

What makes a note different from an article

A technical article teaches a whole method. A note isolates one relationship and works it through cleanly. Typical starting points are a motor that will not accelerate on the set, an unexpected voltage dip when a lift starts, current readings that do not agree between the controller and a clamp meter, or uncertainty about how long the fuel will last. The note identifies the condition, the equipment, the operating state and the single calculation or check that moves the investigation forward. It does not claim to settle the final design.

Rate versus performance: litres per hour and litres per kWh

The note we are asked about most concerns fuel. Litres per hour is a consumption rate. It tells you how fast the tank empties, and nothing about efficiency, because it ignores how much electricity was produced. Litres per kWh relates consumption to useful output over the same period and is the figure that allows two generators, or two months, to be compared.

SFC (L/kWh) = fuel used (L) / energy delivered (kWh)

Diesel generator calculator

Fuel use, runtime, tank size and cost

How this is calculated

Real power is kVA × power factor. Fuel use is estimated as L/h ≈ 0.04 × rated kW + 0.22 × load kW, which follows the usual shape of modern diesel gensets: about 0.26 L per kWh near full load, rising towards 0.38 L per kWh at a quarter load because the engine’s fixed losses are spread over less output.

If you enter the full-load figure from your engine datasheet, the curve is scaled to match it. Runtime is usable fuel ÷ L/h. Tank size is L/h × hours, plus the reserve margin, divided by the usable fraction.

These are planning estimates, typically within 10 to 15% of a healthy engine. Actual use depends on the engine model, its condition, altitude, ambient temperature and how the load varies. For a figure you can rely on, use the manufacturer’s fuel curve or a metered test.

Estimates only, worked out in your browser. For a checked selection, send us your load list and site details or call 98852 01608.

Fuel used is the measured diesel consumed in the period, energy delivered is the kWh recorded by the generator’s energy meter or computed as average kW times run hours, and SFC is the specific fuel consumption. Worked example (illustrative): Generator A burns 20 L/h while carrying 80 kW, so it delivers 80 kWh per hour and its SFC is 20 / 80 = 0.25 L/kWh. Generator B burns 15 L/h while carrying 30 kW, so its SFC is 15 / 30 = 0.50 L/kWh.

B looks thriftier by the hour and is twice as costly per unit. At a delivered diesel price of P per litre, A produces electricity at 0.25 × P per kWh and B at 0.50 × P, twice as much for the same unit. The usual cause of a figure like B’s is light loading: diesel engines are most efficient between roughly 60 and 85% of rated load.

Record per periodUnitWhy it is needed
Run hourshConverts average kW to kWh
Average loadkWShows load factor and explains SFC
Energy deliveredkWhDenominator of SFC
Fuel usedLNumerator of SFC, from dip or flow meter
Diesel priceRs/LConverts SFC to cost per kWh

Without useful output the cost per kWh cannot be calculated meaningfully. Use measured litres and measured load where possible, keep estimates labelled, and see fuel consumption for typical curves.

Making a calculation traceable

Record the inputs, units, assumptions and the source of each significant value. Keep measured values separate from estimates. Check whether the method applies to single-phase or three-phase operation, balanced or unbalanced load, and steady or changing conditions. A three-phase power formula applied to one phase reading, or a nameplate power factor assumed when the load is mostly UPS, are the usual sources of a confident wrong answer. Retain the note’s version with any project record that uses it, because a changed input can change the conclusion.

What a load test proves, and what it does not

A generator’s real test happens under load. A loaded test checks load acceptance, voltage and frequency stability, thermal behaviour and fuel consumption, none of which a no-load run reveals. There are two ways to do it.

Load-bank test

A controlled resistive or resistive-reactive bank applies known load in steps, independent of the site. It is the cleaner test for capacity, for burning off wet-stacking in lightly loaded sets and for proving an overhaul. Steady-state and step-load tests may both be needed. It is a defined scope item and is not automatically part of every service visit; see load bank testing.

Site-load test

A test on the actual connected load proves the real interaction with motors, UPS and the changeover panel. It cannot easily reach full rating and its result depends on what was running that day. A narrow boundary means a narrow claim: a site-load test at 40% proves operation at 40%.

Site conditions that masquerade as engine faults

A mechanically healthy generator can overheat because the room or airflow path is wrong: recirculated hot air, a blocked louvre, or a radiator discharge duct that is too small. Diagnosis must therefore include the site, which is covered in generator room ventilation. Air-filter restriction matters in dusty stone, construction and mining sites.

Exhaust back-pressure from long runs or tight bends raises exhaust temperature and smoke; exhaust pipes should be self-supported, isolated from the engine by a flexible connector and discharged outdoors away from openings. Do not treat smoke colour alone as a diagnosis. When load is added, voltage dips briefly and the AVR restores it; a slow or oscillating recovery points to the AVR, the excitation or the governor, not to the engine block.

How fuel use per kWh changes with load

A diesel set uses fuel most efficiently near its rated load. At light load, a larger share of the fuel goes to overcoming friction and keeping the engine turning, so litres per kWh rise. The figures below are typical of modern sets and are illustrative; the engine data sheet gives the real curve.

LoadTypical litres per kWh
25%About 0.33 to 0.37
50%About 0.28 to 0.30
75%About 0.26 to 0.28
100%About 0.25 to 0.27

Worked example: reading a fuel log (illustrative)

A 250 kVA set logs 640 litres of fuel over 10 running hours while the meter records 1800 kWh. That is about 0.36 litres per kWh at an average load of 180 kW, which is 90% of its 200 kW rating. At that load, a healthy set would use nearer 0.26 litres per kWh, or about 470 litres. The gap of about 170 litres points to a fault, a leak, a meter error or fuel loss, and the next step is to check each in turn rather than accept the figure.

Units used in the notes

Correcting for site conditions

Ratings and fuel figures are given at reference conditions. A set in a hot room or at altitude delivers less power, and a test result taken in those conditions is compared with the derated figure, not the catalogue rating. Each note states the conditions behind its numbers so that readers can make the same correction.

How the notes are kept accurate

Each note is reviewed when a referenced standard, rule or common equipment practice changes, and its date is updated. Worked examples are rechecked with the arithmetic shown, so a reader can follow every step and repeat it with their own figures.

Common mistakes

What to send us

For a note-style question about your set, send the nameplate photograph, a few days of run hours, fuel dips or flow-meter readings and kW readings from the controller, the ambient conditions, and a short description of the symptom. Photographs of the room, louvres and exhaust route help with thermal questions. Send your service enquiry, or read the related engine service guidance first.

Questions engineers ask

Why does a generator use more fuel per kWh at light load?

At light load a larger share of the fuel goes to overcoming friction and keeping the engine turning. Typical figures rise from about 0.25 to 0.27 litres per kWh at full load to about 0.33 to 0.37 at quarter load, though the engine data sheet gives the real curve.

How can a fuel log reveal a generator problem?

Divide litres used by kWh generated and compare with the expected figure at that load. In the illustrative case, 640 litres for 1800 kWh is about 0.36 litres per kWh at 90% load, against about 0.26 expected, pointing to a fault, leak, meter error or fuel loss.

What units do the engineering notes use?

kVA for generator ratings with kW at 0.8 power factor unless stated, litres per hour for fuel flow and litres per kWh for efficiency, degrees Celsius and metres for site conditions, and four-digit numbers without a comma, with larger numbers using commas, so figures read the same on every page.

Why do test results need correcting for site conditions?

Ratings and fuel figures are given at reference conditions, and a set in a hot room or at altitude delivers less power. A test result taken in those conditions is compared with the derated figure, not the catalogue rating, so each note states the conditions behind its numbers.

What is a normal litres per kWh for a diesel generator?

A healthy modern set loaded between about 60 and 85% typically falls around 0.26 to 0.30 L/kWh, with small sets at the higher end. At light load the figure rises sharply. Confirm against the manufacturer’s fuel curve for your engine. Track your own figure every month, because a rising trend is often the first sign of injector, filter or loading problems.

How do I measure fuel accurately on site?

A calibrated flow meter on supply and return is best. Failing that, dip the tank at a fixed temperature before and after a run of several hours at steady load and use the tank’s calibration chart. Record the load and the hours from the controller at the same time, so the litres can be divided by the kilowatt-hours delivered.

Why does my lightly loaded generator smoke?

Running for long periods below about 30% load lets unburnt fuel and oil collect in the exhaust, known as wet-stacking. Periodic loaded running or a load-bank session usually clears it, but persistent smoke needs injector and compression checks. Find the cause before the engine glazes or the exhaust leaks.

Is a site-load test enough after major repair?

Usually not, because site load rarely reaches the rating. A stepped load-bank test proves capacity, and a site-load test then proves interaction with the real equipment. Record readings at each step, including temperatures and pressures, so the result can be compared with the commissioning record and with the next test.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.