In short. Cold-storage continuity is a race between electrical restoration and the temperature rise the stored product can tolerate. The generator must start the motors in sequence, carry condenser and evaporator fans, and run for the longest credible outage, which in a Telangana monsoon can be many hours. Size on motor starting rather than running load, sequence the restart through the plant controller, link fuel autonomy to product risk, and alarm temperature and generator faults to a person.
Thermal autonomy sets the clock
Every cold store has a thermal autonomy, the time it can hold temperature after refrigeration stops. A full, well-insulated frozen store at minus 18 degrees Celsius rises slowly, often a degree or two over several hours, because the product mass acts as a thermal flywheel. A partly loaded chilled room for fruit, vegetables or seed rises much faster. A blast freezer with product mid-process has almost no autonomy, and pharmaceutical cold chains at 2 to 8 degrees Celsius have excursion limits measured in minutes rather than hours.
The acceptable outage duration therefore depends on the product, the temperature setpoint, the door discipline and the operator’s own quality rules, and it must come from the facility, not from the generator supplier. Once that number is known, everything else follows: how fast the set must start, how fast the motors must be back, and how long the fuel must last.
Motor starting dominates the sizing
Refrigeration load in running terms is modest. The difficulty is restart. Reciprocating-type machines on direct-on-line or star-delta starters draw several times their full-load current for a few seconds; screw-type machines start unloaded but still impose a step; and after a long outage every motor and fan wants to start together while the rooms are warm and suction pressure is high. On a generator that is the event that trips the breaker.
S_start = P_motor × k_start / (η × PF)
In this expression S_start is the starting apparent power in kVA, P_motor is the motor rating in kW, k_start is the starting current multiple for the starter type, η is motor efficiency and PF is the motor’s full-load power factor, since starting kVA scales with the full-load kVA. For a 75 kW reciprocating-type machine started direct-on-line with k_start of 6, η of 0.93 and PF of 0.85, S_start is roughly 570 kVA for the first second or so, which a 300 kVA set cannot hold without a deep voltage dip (illustrative).
The same motor on a soft starter limited to 3.5 times full-load current brings this to roughly 330 kVA; on an inverter drive the step becomes little more than the running load. This is why cold-store generator projects usually include starter upgrades or a strict one-at-a-time restart, and why the method on motor starting on generators matters more here than the kVA = kW / PF arithmetic.
A sizing illustration
A fruit and vegetable cold store near Hyderabad has three 55 kW screw-type machines, 40 kW of condenser fans, 30 kW of evaporator fans and pumps, 25 kW of lighting, office and dock loads, and electric defrost heaters of 30 kW per room that are interlocked so that only one room defrosts at a time (illustrative).
The running load with all three motors loaded is about 260 kW, or 325 kVA at 0.8 PF. If the plant controller starts the motors one at a time, unloaded, with a 30-second interval, a 400 to 450 kVA set carries the restart comfortably; if all three try to start together, the same site needs a set roughly twice that size. The sequencing feature is cheaper than the extra engine.
Sequence, prioritise and protect the right rooms
| Zone or load | Why it matters on backup | Restoration priority |
|---|---|---|
| Plant controller, PLC, temperature monitoring | Nothing restarts safely without it | UPS, no break |
| Frozen and blast rooms | Highest product value per degree of excursion | First motor group |
| Chilled rooms, ripening rooms | Faster temperature rise, quality loss | Second group |
| Condenser fans and pumps | Motors cannot run without heat rejection | With the first motor |
| Evaporator fans | Temperature uniformity inside the room | With each room’s motor |
| Electric defrost heaters | Large resistive steps, deferrable | Blocked until plant is stable |
| Dock doors, lighting, office | Operational convenience | Last |
| Ammonia detection and emergency ventilation | Safety | First, independent of product |
Where the plant uses ammonia, gas detection and emergency ventilation are safety loads and belong on the generator ahead of any product consideration. Prioritising rooms is also a legitimate way to reduce generator size: holding the frozen rooms and accepting a longer excursion in the chilled rooms can halve the motor load the generator must restart. The priority logic is covered on load shedding automation and priority logic.
Fuel autonomy and sustained operation
A cold store’s generator may run for twelve, twenty-four or more hours during a monsoon outage or a feeder fault, and the fuel plan must match the product risk, not the day tank. A set loaded to about 80% consumes in the region of 0.26 to 0.28 litres per kWh, so a 400 kVA set carrying 260 kW uses roughly 68 to 73 litres per hour (illustrative), or well over a thousand litres in a day.
Decide how many hours of fuel are kept on site, how a refill is arranged at night or on a holiday, and who checks the level. The calculation is on fuel consumption and the storage question on fuel tank sizing. Coolant, oil and radiator cleanliness matter as much as fuel in sustained operation at high ambient, and a set that has only ever run a weekly test should be given a load run before the season.
Alarms: temperature, generator and a human
A cold store that loses power at night with nobody on site discovers the failure in the morning. The monitoring system should alarm room temperature, generator fail-to-start, low fuel and loss of mains, and the alarms should reach a named person by SMS or an app, not a hooter in an empty plant room. Remote monitoring of the generator controller is now inexpensive and is described on communications and remote monitoring. The person who receives the alarm must also know who to call for the generator, which is where a service agreement with a defined response earns its cost; see annual maintenance contracts.
Sizing a multi-chamber cold store (illustrative)
A cold store with four chambers runs refrigeration units of different sizes. The generator is sized for the running load of all units plus the start of the largest one last.
| Load | Running | Restart order |
|---|---|---|
| Frozen chamber refrigeration | 45 kW | First, it has the least margin when doors open |
| Chilled chamber 1 refrigeration | 22 kW | Second |
| Chilled chamber 2 refrigeration | 22 kW | Third |
| Ripening chamber | 15 kW | Fourth |
| Evaporator fans, defrost controls, lighting, dock | 20 kW | With the first unit |
| Total running | 124 kW | About 155 kVA at 0.8 power factor |
Because each refrigeration unit starts with several times its running current, and restarting the largest one with the others running is the hardest step, a 250 kVA set gives a comfortable margin for a staged restart in summer.
Thermal autonomy in practice
A well-loaded, well-insulated frozen store holds temperature for hours with doors closed; an empty or frequently opened room warms much faster. During an outage, doors stay closed, dock operations pause, and temperatures are logged. The logs from past outages give each chamber a measured holdover time, which tells the operator how quickly refrigeration must return and whether the generator start and restart sequence are fast enough.
Fuel for long outages
For the example above, about 124 kW at roughly 0.28 litres per kWh uses about 35 litres an hour. A twelve-hour outage needs about 420 litres, so the base tank and a delivery arrangement are planned for the longest outage the store expects. On our standard, oil and filters are changed every 250 to 500 running hours or six months, whichever comes first, and coolant is replaced every year.
Alarms that reach a person
Cold stores often run unattended at night. Generator alarms such as fail to start, low fuel and shutdown, and chamber temperature alarms, are sent to a phone that someone answers. An alarm that sounds only in an empty building protects nothing.
Defrost cycles and the generator
Electric defrost heaters on evaporators draw a large load for a short time. If a defrost cycle begins while refrigeration units are restarting on the generator, the combined step can overload the set. Defrost controls are therefore set to delay any defrost for a period after transfer to generator, and defrost heaters are included in the generator load only with that interlock in place.
Common mistakes
- Sizing the generator on motor running kW. The first simultaneous restart trips the set and the rooms warm while the operator resets breakers.
- Leaving defrost heaters free to switch on during backup. A 30 kW resistive step lands on a set already carrying a motor start.
- Keeping only a day tank of fuel. A long outage ends with the set stopping at 3 am and nobody aware until the morning.
- Omitting condenser fans or pumps from the standby bus. Refrigeration units trip on high discharge pressure within minutes of starting.
- Relying on a weekly no-load test for readiness. The engine has never been asked to pick up a loaded motor until the day it must.
What to send us
Send the refrigeration plant schedule with motor ratings and starter types, condenser and evaporator fan loads, defrost method and interlocks, the room temperatures and the maximum excursion the facility accepts, the plant controller’s ability to sequence restarts, and the longest outage you have experienced. Photographs of the motor nameplates, the main switchboard and any existing generator and AMF panel help. Send your cold-storage requirement.
Questions engineers ask
In what order should cold store refrigeration restart?
The chamber with the least margin first, usually the frozen store, then chilled chambers and ripening rooms, one unit at a time, with evaporator fans and controls returning with the first. Restarting the largest unit last with the others running is the hardest step, and the set is sized for it.
Why should defrost be delayed after transfer to generator?
Electric defrost heaters draw a large load for a short time. If a defrost cycle begins while refrigeration units are restarting on the generator, the combined step can overload the set. Defrost controls are set to delay any defrost for a period after transfer, so the restart completes first.
How do I calculate the generator size for a cold store?
Start from the motor starting kVA for the starter type, decide whether the controller can sequence starts, add the running load of fans, pumps and the rooms already running, and allow for any defrost that cannot be blocked. Sequenced starting typically allows a set around 1.5 times the running kVA; simultaneous starting can demand two to three times (illustrative).
How long can a cold room hold temperature without power?
A full frozen store may hold for several hours with doors closed; a partly loaded chilled room may exceed limits within an hour; a blast freezer or pharmaceutical store may have minutes. The facility’s own records and product rules decide, and the generator start and restart time must be shorter than that.
Should the generator start automatically?
Yes, for almost every cold store. Outages often happen at night when nobody is on site, and the refrigeration must return within the holdover time of the most sensitive chamber. An AMF panel starts the set and transfers the load, and alarms send a message to someone who will respond.
Can a rental generator be used for a cold store in an emergency?
Yes, if it is sized for the running load and the staged restart of the refrigeration units, connected through a proper changeover, and fuelled for the expected outage. Having the connection point and load list ready in advance makes an emergency rental far quicker to arrange.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.