In short. The alternator is the electrical machine on the end of the engine that turns shaft power into 415 V, 50 Hz output. Its stator, rotor, exciter, rotating rectifier, AVR and optional permanent magnet generator decide voltage regulation, how deep the voltage dips when a motor starts, how well it tolerates UPS and drive loads, and how hot it runs. Two sets with the same engine and kVA can perform quite differently because their alternators differ.
How a brushless alternator works
Almost every generator set sold in India above a few kVA uses a brushless synchronous alternator. The main rotor carries a DC field winding and turns inside the main stator, whose three windings produce the output. Field current comes not from brushes but from a small exciter on the same shaft: its stationary field is fed by the AVR, its rotating armature produces AC, and diodes on the shaft rectify that AC into the DC the main rotor needs.
The AVR senses output voltage and adjusts the exciter field to hold the set point. On larger machines a permanent magnet generator on the shaft end feeds the AVR, so excitation does not depend on output voltage and the machine can sustain short-circuit current and recover from a deep dip. With no wearing contacts beyond the bearings, alternators routinely run for decades between rewinds.
| Component | Function | Typical failure and symptom |
|---|---|---|
| Main stator | Three output windings, star connected, neutral brought out | Insulation breakdown after moisture or overheating; earth fault or one phase low |
| Main rotor | DC field winding producing the rotating flux | Winding failure; low voltage that the AVR cannot correct |
| Exciter | Supplies field power without brushes | Field open circuit; no voltage build-up |
| Rotating rectifier | Diodes converting exciter AC to rotor DC | Shorted or open diode; unstable or low voltage, overheated exciter |
| AVR | Controls exciter field to regulate output voltage | Component failure or wrong setting; voltage hunting, over or under voltage |
| PMG | Independent power source for the AVR | Magnet or winding damage; loss of voltage under fault or heavy load |
| Bearings | Support the rotor; single bearing on most sets with flexible disc coupling to the engine | Grease failure or misalignment; vibration, noise, eventual seizure |
The AVR and PMG excitation pages explain the control loop in more depth.
Reactances: the figure behind every voltage dip
When a motor starts or a transformer is energised, the alternator sees a sudden demand for reactive current and its terminal voltage falls before the AVR can respond. How far it falls in the first cycles is set by the sub-transient reactance, X″d, expressed as a percentage on the machine’s own rating.
Voltage dip (approximate, percent) ≈ (Starting kVA × X″d) ÷ (Starting kVA × X″d + Alternator kVA) × 100
Here starting kVA is the motor’s locked-rotor demand, X″d is the sub-transient reactance as a per-unit value and alternator kVA is the machine’s rating. As an illustrative example, a 45 kW motor on direct-on-line start demanding about 330 kVA, fed by a 500 kVA alternator with X″d of 0.12 per unit, produces an initial dip of roughly 330 × 0.12 ÷ (330 × 0.12 + 500), which is about 7%; the same motor on a 250 kVA alternator with X″d of 0.16 dips about 17% (illustrative).
Most contactors drop out somewhere below 70 to 80% voltage, so the second case is marginal if anything else is running. Lower-reactance alternators cost more because they contain more copper and iron, but specifying one is often cheaper than stepping the whole set up to the next engine size. The reactance and short-circuit page and the voltage dip page cover the calculation and the recovery that follows.
Nonlinear loads and temperature rise
UPS rectifiers, variable-frequency drives, LED drivers and switched-mode power supplies draw current in pulses rather than a sine wave. Those harmonic currents flow through the alternator’s reactance and distort the terminal voltage, which can confuse the AVR, heat the rotor through induced currents and overheat the stator beyond what the RMS current suggests.
The usual safeguards are a 2/3 pitch stator winding that suppresses the third harmonic, a larger alternator frame than the kW alone would call for, and an AVR that senses true RMS or average on all three phases rather than the peak of one. Where more than about a quarter of the load is rectifier-fed, the alternator should be selected with its harmonic capability stated in writing; the nonlinear loads page sets out the derating approach.
Temperature rise is the other limit. Alternators are built with Class H insulation but normally rated for a Class F rise of 105 K above a 40 °C ambient, with the margin to Class H held as a reserve. Running at 45 °C ambient, with harmonic heating, or with a blocked air inlet erodes that reserve and halves insulation life for every 10 K of sustained overheating. Standby-rated alternators use more of the thermal margin than prime-rated ones, which is part of why the same frame carries a different kVA at each rating class.
Diagnosing a voltage problem
A set with no voltage, low voltage or unstable voltage does not automatically need a new AVR, although that is the part most often changed first. The measured approach starts at the output terminals under known load, checks residual voltage with the AVR disconnected to prove the main machine, measures the exciter field and the rotating diodes, confirms the sensing wires reach the AVR with the right voltage, and checks engine speed, because a governor fault that drops speed a few percent looks exactly like a weak alternator. Only when the chain is proven is the AVR condemned. The alternator service page describes the tests, and the alternator parts page the diodes, AVRs and bearings most often replaced.
Related photographs and videos
Insulation class, temperature and life
Alternator windings are insulated to a temperature class, commonly class H for the materials, with the temperature rise held to the lower class F limits so the windings run cooler than their materials allow. Heat ages insulation: as a rough rule, every 10 °C of extra winding temperature can halve its life. Overload, harmonic currents from UPS and drives, unbalance, blocked cooling air and high ambient all add temperature, which is why an alternator that is loaded within its rating but runs hot still loses life.
Insulation resistance tests
| Test | What it shows | What to do with a poor result |
|---|---|---|
| Insulation resistance at a suitable test voltage | Moisture, dirt or damaged insulation | Dry the windings, clean, retest before running |
| Polarisation index, ten-minute over one-minute reading | Overall condition of the insulation | A low index suggests contamination or ageing |
| Trend over years | Gradual deterioration | Plan cleaning, varnishing or rewinding before failure |
A set that has stood for months in the monsoon is tested before it is run on load, because damp windings can fail when voltage is applied. The alternator maker’s minimum values govern the decision.
Excitation types compared
| Type | Behaviour on a heavy load step or fault | Suits |
|---|---|---|
| Self-excited, from the main output | Excitation weakens as the output voltage dips | General loads, modest motor starts |
| Auxiliary winding | Extra excitation power available during dips | Motor starting, better fault current support |
| Permanent magnet generator | Excitation independent of output voltage | Large motor starts, UPS and drives, fault current support for protection |
See generator short-circuit contribution.
Rewind, repair or replace
A failed alternator is not always a lost one. Bearings, the rotating diode assembly, the regulator and the exciter are replaceable parts, and many faults that stop the output are found there. Where the main windings have failed, rewinding with modern insulation restores the machine if the frame, shaft and rotor are sound and the work is done to the original winding data; replacement suits machines whose frame is damaged, whose spares are unobtainable, or where a larger frame is wanted for better motor starting. The decision follows the inspection and test results, not the age alone.
Bearings and alignment
Most single-bearing alternators rely on one rear bearing, with the engine flywheel carrying the front. Greasing intervals, where the bearing is regreasable, and replacement intervals are given by the maker in running hours or years. Noise, vibration and rising temperature at the bearing are early signs, and misalignment after a set is moved shortens bearing life quickly, so alignment is checked whenever the engine and alternator are separated.
Common mistakes
- Replacing the AVR for every voltage complaint; a shorted rotating diode or a loose sensing wire is the real cause and the new AVR fails the same way.
- Selecting the alternator on kVA alone for a plant with large direct-on-line motors; the voltage dip at starting drops contactors across the plant.
- Feeding a UPS of more than a quarter of the set rating without checking harmonic capability; the alternator overheats and the AVR hunts.
- Starting a set after the monsoon without an insulation resistance test; damp windings fail on the first load.
- Loading one phase heavily with single-phase circuits; the rotor overheats although total load is modest.
What to send us
Send a photograph of the alternator nameplate showing make, model, frame, kVA, voltage, connection and insulation class, and of the AVR with its type number, together with the symptom in your own words, the voltage readings on all three phases under load and at no load if you have them, and the engine speed or frequency at the time. For a new set, send the largest motor rating and starting method and the UPS or drive kVA. Use the generator sales enquiry for a new machine or the spare parts enquiry for AVRs, diodes and bearings, and we will respond with a diagnosis path or a selection.
Questions engineers ask
How much does winding temperature affect alternator life?
A great deal. As a rough rule, every 10 degrees of extra winding temperature can halve insulation life. Overload, harmonic current from UPS and drives, unbalance, blocked cooling air and high ambient all add temperature, so an alternator that is within its kVA rating but runs hot still loses life.
Should a failed alternator be rewound or replaced?
Bearings, diodes, the regulator and the exciter are replaceable parts and cause many faults. Where the main windings have failed, rewinding to the original data restores a machine with a sound frame, shaft and rotor; replacement suits a damaged frame, unobtainable spares, or a wish for a larger frame for better motor starting.
What is the difference between a brushless alternator and one with slip rings?
A brushless machine feeds its rotor field through a shaft-mounted exciter and rotating diodes, so there are no brushes to wear or spark. Slip-ring machines, now rare in gensets, pass field current through carbon brushes that need regular inspection and replacement. Virtually all industrial generator alternators today are brushless.
Why does a PMG matter on a generator?
A permanent magnet generator gives the AVR a power source that does not collapse when the output voltage collapses, so the alternator can deliver about three times rated current into a short circuit for several seconds to trip breakers, and can recover from the deep dip of a large motor start. Self-excited machines without a PMG lose excitation under those conditions.
What voltage regulation should a generator alternator hold?
A modern AVR holds steady-state voltage within about ±1% from no load to full load at constant speed and power factor. Transient dips during load changes are a separate matter governed by the alternator reactances and the excitation system, not by the AVR’s steady-state accuracy.
Can an alternator be rewound, and is it worthwhile?
Yes, stator and rotor rewinding is routine for machines above about 100 kVA, and it is usually economic where the frame, shaft and bearings are sound. For small alternators a replacement is often cheaper than a rewind. The rewound machine should be tested for insulation resistance, winding resistance balance and voltage build-up before it goes back into service.
How often should alternator bearings be greased or replaced?
At the intervals the alternator maker gives in running hours or years. Many smaller machines have sealed bearings that are replaced rather than greased; regreasable bearings get a measured amount of the specified grease. Noise, vibration or rising bearing temperature call for inspection before the interval is reached.
Generators by rating
- Under 15 kVA generators
- 15–50 kVA generators
- 50–125 kVA generators
- 125–250 kVA generators
- 250–500 kVA generators
- 500–1000 kVA generators
- 1000–2000 kVA generators
- 2000 kVA and above generators
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.

