In short. In a main-tie-main board, two transformers each feed half the board through their own incomer, and a tie breaker between the halves stays open. If one supply fails, its incomer opens and the tie closes, so the other transformer carries both halves. This works only if that transformer can carry the whole load. Interlocks must also stop all three breakers closing together, unless the fault level allows it.
Who this page is for: For consultants, plant engineers and facility managers with double-ended boards or planning one.
Key facts
- Normal: both incomers closed, tie open.
- One supply lost: its incomer opens, tie closes.
- Each transformer must carry the whole load, or loads must be shed.
- Paralleling both transformers roughly doubles the fault level.
- Interlocks normally allow only two of the three breakers closed.
- Generators can connect to each half or to the tie section.
Worked example: two 1000 kVA transformers at 415 V (illustrative)
| Check | Working | Result |
|---|---|---|
| Load | Side A 650 kVA, side B 550 kVA | 1200 kVA total |
| Loss of transformer A | 1200 kVA on one 1000 kVA transformer | 120%: overload |
| Fix | Shed at least 200 kVA of non-essential load automatically when the tie closes | about 1000 kVA or less: acceptable |
| Fault level, one transformer at 6% impedance | about 1391 A ÷ 0.06 | about 23 kA |
| Both transformers in parallel | Roughly double | about 46 kA: above a 36 kA board rating |
The interlock was therefore set to allow only two of the three breakers closed at once. See short-circuit studies and dual utility supply.
Do not close the tie with both incomers closed unless the board and every breaker are rated for the combined fault level. Rely on interlocks, not on procedures alone.
Operating states
| State | Incomer A | Tie | Incomer B |
|---|---|---|---|
| Normal | Closed | Open | Closed |
| Loss of A | Open | Closed | Closed |
| Loss of B | Closed | Closed | Open |
Automatic transfer should be blocked if the incomer opened on a fault in its own half, so the tie does not close onto the fault. See bus arrangements.
Main-tie-main check sheet
| Item | Value or status |
|---|---|
| Total load vs one transformer | |
| Load shedding when tie closes | |
| Fault level, one and two transformers | |
| Interlock type | |
| Transfer blocked on bus fault? |
What closing the tie does to the fault level
In normal running, with the tie open, each half of a double-ended board is fed by one transformer and sees that transformer’s fault level. Two 1000 kVA transformers of 5% impedance each deliver about 27.8 kA at 415 V, so each half sees about 27.8 kA. Close the tie with both incomers still closed and the two transformers feed any fault in parallel: about 55.6 kA, double the figure, before any contribution from motors is added.
Running motors add their own contribution in the first cycles of a fault, roughly four times their full-load current. A board with 300 kW of motors running at a power factor of about 0.9 and an efficiency of about 0.93, about 499 A of running current, adds about 2 kA. The switchgear on a double-ended board must therefore either be rated for the paralleled fault level, about 58 kA in this example, or the interlocks must make it impossible for both incomers and the tie to be closed at once, even briefly.
The interlock that allows only two of the three breakers to be closed is what lets each half be built for 27.8 kA plus motors; remove it, or allow a closed-transition transfer, and the switchgear must be rated for the higher figure.
Closed transition and the circulating current
Some schemes return from the tie to normal running by closed transition: the incoming breaker of the restored transformer closes while the tie is still closed, the two transformers run in parallel for a moment, and then the tie opens. The load sees no break. During that moment, the switchgear sees the paralleled fault level described above, and any difference between the two transformers’ open-circuit voltages drives a current round the loop between them.
| Tap difference between the two transformers | Circulating current, two 1000 kVA transformers at 5% | As a share of each transformer’s rated current |
|---|---|---|
| None | None | 0% |
| 2.5% | about 348 A | 25% |
| 5% | about 696 A | 50% |
The working is the voltage difference divided by the sum of the two impedances: 2.5% divided by 10% is a quarter of rated current, about 348 A on a 1391 A transformer. For a moment of paralleling that is harmless, but it adds to the load current and can trip sensitive protection; if the paralleling is held for longer, through a failed tie trip, it heats both transformers for no useful purpose.
Closed-transition schemes should therefore check that both transformers are on the same tap before allowing the transfer, limit the paralleling time to a fraction of a second, and trip the tie by a backup route if it has not opened in that time.
The conditions the automatic transfer must check
An automatic double-ended scheme closes the tie only when a short list of conditions is all true, and each condition exists to stop the scheme making things worse.
| Condition before closing the tie | Why |
|---|---|
| Loss of voltage on one side confirmed for a set delay | Rides through dips that would clear by themselves |
| The incomer on that side is open | Prevents paralleling a healthy transformer onto a dead or recovering one |
| The incomer did not open on a protection trip | A trip means a fault on that half of the board; closing the tie would feed the fault from the healthy side |
| The other side is healthy, in voltage and phase sequence | There is no point transferring to a supply that is also failing |
| Residual voltage on the dead side has decayed | Avoids reclosing onto running motors out of phase |
The third condition is the one most often missing from simple schemes, and its absence turns a busbar fault on one half into a fault on both. The incomer’s protection trip must block the automatic tie closing until someone has inspected the faulted half and reset the block by hand.
Loading each transformer for the tie-closed state
A double-ended board protects the load against the loss of one transformer only if the other can carry everything. Two 1000 kVA transformers sharing a load of 1300 kVA run at 65% each in normal running, which looks comfortable, but after one is lost the other must carry 1300 kVA, 130% of its rating. A transformer can carry a short overload, depending on its design, its cooling and its loading before the event, but not 130% indefinitely.
The design must state what happens in that state: either the total load is held within one transformer’s rating, so that the tie-closed state is sustainable, or a defined block of load is shed automatically when the tie closes, so that the remaining load fits. In the example, shedding 300 kVA brings the surviving transformer to its rating. The shed block should be chosen from the load classes — comfort cooling, non-essential process — and wired so that the shedding happens before or at the moment the tie closes, not after the transformer has been overloaded for some minutes.
Protection settings that work in every state
The settings of the incomer protection are usually chosen for normal running, when each incomer carries half the load. With the tie closed, one incomer carries everything, and its long-time setting must allow that without tripping, or the scheme that was meant to keep the supply on will open the only remaining incomer. At the same time, the tie breaker sits between the incomer and the outgoing feeders of the other half, so it needs its own settings that discriminate with both: it should trip before the incomer for a fault on the far half, and after the outgoing feeders for a fault on any of them.
The coordination study for a double-ended board therefore has to be drawn for each state: both incomers closed with the tie open, each incomer alone with the tie closed, and any generator connection. A study drawn for the normal state only will look correct and fail on the day it matters.
Neutral and earth on a double-ended board
Each transformer’s star point is bonded to earth, and on a double-ended board those two bonds, joined through the neutral bar when the tie closes, create more than one path for neutral current. If the neutral is not switched with the phases, neutral current from one half can return to the other transformer through the earth conductors, and earth-fault protection that measures residual current on each incomer then sees currents that are not faults. The result is nuisance tripping in normal running, or worse, a real earth fault that the protection does not see correctly.
The common solutions are four-pole incomers and tie that switch the neutral with the phases, so that each half has one source and one bond at any time, or a single-point earthing arrangement with earth-fault protection designed for the multiple-source case, which sums the currents at the incomers and the tie. Either works if it is designed deliberately; mixing three-pole and four-pole breakers without a plan does not. The earth-fault protection should be tested by injection in each operating state, not only in normal running.
Testing every state, not just the normal one
A double-ended scheme spends almost all its life in normal running, and the states that matter are visited only during failures and maintenance. Each should be tested at commissioning and at least every few years after: loss of each transformer in turn, with the tie closing automatically and the shed block dropping; return to normal from each, by open or closed transition as designed; a simulated protection trip on each incomer, confirming that the tie does not close; and manual operation of every interlock, confirming that three breakers cannot be closed at once. Record the timings and the load on each transformer in each state. A scheme that has only ever been seen in normal running is still a design, not a proven arrangement.
Common mistakes
- Transformers sized for half the load.
- No automatic load shedding.
- Tie closing onto a bus fault.
- Interlocks bypassed.
What to send us
Send the board layout, transformer data and loads. WhatsApp 98852 01608 or use the application engineering enquiry.
Evidence note. Values are illustrative.
Questions engineers ask
How much does closing the tie raise the fault level?
It roughly doubles it when both incomers stay closed. Two 1000 kVA transformers at 5% impedance each give about 27.8 kA at 415 volts; in parallel they give about 55.6 kA, and running motors add more, about 2 kA for 300 kW of motors. Either the switchgear is rated for the paralleled level or the interlocks prevent all three breakers being closed at once, including during any closed-transition transfer.
Why does earth-fault protection trip on a double-ended board?
Usually because the two transformer neutrals are both bonded to earth and the neutral is not switched with the phases. Neutral current from one half can then return to the other transformer through the earth conductors, and residual-current earth-fault protection on the incomers sees it as a fault. Four-pole incomers and tie, or a single-point earthing scheme with protection that sums currents at the incomers and tie, solve it. Test the protection in every operating state.
Why must the tie be interlocked?
To prevent paralleling two sources unintentionally, which can cause fault levels above ratings and circulating currents. Mechanical or electrical interlocks, often key-based, allow only two of the three breakers to be closed at once, and the interlock logic is proved at commissioning and after any panel modification.
Can the tie be closed in normal operation?
It can, but fault level rises and protection becomes more complex. Many sites keep it open. Closing the tie parallels the two transformers, so the fault study, the switchgear rating and the protection grading must all cover that state. Running open keeps each half independent and the protection simpler.
How much overload can a transformer take?
It depends on the design, cooling and ambient temperature, and the duration. Confirm with the manufacturer’s loading guide. In a double-ended scheme each transformer must carry the whole critical load when the other is out, so its rating, or its short-term overload capacity with the expected cooling, is checked against the full load.
What happens if the tie closes onto a fault?
The fault transfers to the other source and may take it down too. That is why the lockout after a protection trip matters. A main breaker that trips on a fault, rather than on loss of supply, blocks the automatic tie closure until the fault has been found and cleared, so a single fault does not take down both halves of the board.
This guide gives general principles. Ratings, settings and interlocks require engineering design and testing.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.