UPS Capacity and Load Guide

How to size a UPS: load in kW and kVA, power factor, crest factor, redundancy, growth, efficiency and the generator and battery implications that come with the chosen rating.

In short. A UPS has both a kVA and a kW rating, and the load must fit within both. Add redundancy and growth allowance, then check the battery, input and generator impact of the result. Modern UPS often have a rated power factor of 0.9 to 1.0, so kW is the more useful figure for many loads.

Step 1: Know the load

Step 2: Size the UPS

UPS kVA ≥ Load kVA × (1 + growth) ÷ Target loading
UPS kW ≥ Load kW × (1 + growth) ÷ Target loading

Example (illustrative): load of 96 kW and 100 kVA, 20 per cent growth and target loading of 80 per cent. kVA needed = 100 × 1.2 ÷ 0.8 = 150 kVA. kW needed = 96 × 1.2 ÷ 0.8 = 144 kW. A UPS rated 150 kVA at 0.9 gives 135 kW, so it fails the kW check. A 160 kVA unit at unity power factor (160 kW) passes both. The lesson is to check kW and kVA separately.

Step 3: Redundancy

For N+1 with modules, add a module. For 2N, each system carries the whole load. See modular UPS redundancy.

Step 4: Overload and short-circuit ability

UPS units typically accept short overloads, such as 125 per cent for several minutes or 150 per cent for seconds, but this varies. Check the inverter’s ability to clear downstream faults, since inverters supply limited fault current and may transfer to bypass to clear a fault.

Step 5: Efficiency

Efficiency falls at low load. Redundant or oversized UPS may run at 20 to 40 per cent, where efficiency is lower. Check the efficiency curve at your expected load, and consider eco modes only where the load tolerates them.

Step 6: Upstream impact

Step 7: Battery

Battery size follows the load and the autonomy. See UPS autonomy.

Worked check on the generator (illustrative)

The 160 kVA UPS at 90 per cent load and 95 per cent efficiency draws about 144 ÷ 0.95 ≈ 152 kW, plus battery charging of perhaps 10 kW, so around 162 kW input. With a rectifier power factor of 0.95, that is about 170 kVA of input apparent power, and the generator must be sized for it, plus harmonic effects. The generator rating is therefore greater than the UPS output rating, not equal.

Sizing a UPS

UPS kW rating ≥ load kW × (1 + growth) ÷ loading limit; check kVA with load power factor

Worked example (illustrative)

IT load of 160 kW with 20 percent growth and a target maximum loading of 80 percent: 160 × 1.2 ÷ 0.8 = 240 kW. Choose a 250 kW UPS (or 5 × 50 kW modules for N, with a sixth for N+1). If the UPS is rated 0.9 power factor in kVA, 250 kW corresponds to 278 kVA. Check the manufacturer’s kW rating, since many modern units are rated at unity.

CheckWhy
Load power factorLeading loads reduce capacity on some units
Crest factorPeak current capability for switch-mode supplies
Overload ratingShort-term overload for inrush
Input power factor and THDImpact on generator
Efficiency at expected loadOperating cost
Fault current and bypassProtection of downstream devices

Generator sizing with a UPS

The generator must carry the UPS input power: UPS output ÷ efficiency plus battery recharge power. A 250 kW UPS at 95 percent efficiency draws 263 kW plus recharge, perhaps 20 percent more. For a six-pulse rectifier, add alternator margin for harmonics. See UPS and nonlinear loads.

See battery autonomy guide.

Common mistakes

What to send us

Send the load list, redundancy target and autonomy. Send your application details. See also UPS architecture.

Questions engineers ask

Is a UPS rated in kVA or kW?

Both. Check each, since the kW rating depends on the output power factor.

How much spare capacity should I leave?

Commonly 20 to 30 per cent for growth and tolerance, depending on policy and redundancy.

Why must the generator be bigger than the UPS?

Because of UPS losses, battery charging and input power factor and harmonics.

Can a UPS clear faults downstream?

Inverters supply limited current, so protection may rely on bypass or fast-acting devices.

Figures are illustrative. Use manufacturer ratings for design.