Time Synchronisation and Electrical Event Correlation

How to synchronise clocks across relays, controllers and SCADA: GPS, NTP, PTP, IRIG-B, accuracy needs, time-quality flags, failures and using synced data to correlate events.

In short. To work out what happened in a trip, the records from every relay, generator controller and SCADA system have to share one clock. If they disagree by even tens of milliseconds, the order of events can appear reversed and the wrong device gets blamed. Choose a time source and distribution method that match the accuracy you need, monitor every device’s offset, flag time quality on the records, and use UTC inside the systems.

Who this page is for: For protection, control and SCADA engineers setting up or troubleshooting event recording across generator plants and switchboards.

Key facts

  • Operator logs need about one-second accuracy; relay sequence-of-events needs about one millisecond.
  • A satellite-referenced master clock with holdover is the usual time source.
  • Distribute time by a method matched to the accuracy needed: network time for logs, precision protocols or dedicated time codes for relays.
  • Monitor offsets and alarm on loss of synchronisation.
  • Record a time-quality flag with every event.
  • Use UTC internally to avoid time-zone and daylight-saving errors.

Accuracy needs

UseTypical accuracyTypical method
Alarm and operator logsAbout a secondNetwork time over the plant network
Relay sequence of eventsAbout a millisecondPrecision network time or a dedicated time-code feed
Waveform and phasor comparison across sitesMicrosecondsPrecision time with a satellite reference

Worked example: the trip that seemed backwards (illustrative)

After a board tripped, the combined event list read:

Logged timeDeviceEventClock offset found later
10:15:03.410Incomer relayTrip0 ms (synchronised)
10:15:03.440Feeder relayOvercurrent pickup+90 ms (free-running)
10:15:03.460Feeder relayTrip+90 ms

As logged, the incomer appeared to trip before the feeder even saw the fault, suggesting a faulty incomer. Correcting the feeder relay’s 90 ms offset gives: feeder pickup at 03.350, feeder trip at 03.370, incomer trip at 03.410. The feeder tripped first; the incomer tripped 40 ms later because its short-time delay was off. The real fault was the incomer’s grading setting, not a faulty incomer relay. Once every relay was synchronised and monitored, the next event read correctly at first sight. See protection records.

Do not draw conclusions from a combined event list until you have checked every device’s clock. A single free-running relay can make a correct trip look wrong and a wrong one look correct.

Architecture

  • A master clock referenced to satellite time, with holdover if the reference is lost.
  • Distribution to devices by the method each one supports.
  • A second master clock for critical sites.
  • Offset monitoring and an alarm on loss of synchronisation.

Time quality on records

Each record should say whether the device was synchronised, drifting or free-running when it was written. With that flag, a mismatch is obvious, and old records can still be corrected using a known common event.

Correlation workflow

  1. Collect event lists and disturbance files from all devices.
  2. Check offsets against a known common event.
  3. Build one timeline in UTC.
  4. Find the first event and follow the chain.
  5. Compare with the designed cause and effect. See cause and effect.

Clock audit sheet

Every clock on a textile spinning mill — four 625 kVA sets on two buses, seven protection relays and four generator controllers — audited rather than assumed. The example above corrects one free-running relay after the event and shows what its 90 ms offset did to a trip sequence; this sheet is the audit that finds such an offset before an event needs explaining, across a different and larger plant with four sets, two buses and a coupler. Eight entries, and the last one is the finding — because an audit that only lists the devices with a time input has not audited the plant.

DeviceTime sourceOffset measuredSync alarm wired?Date checked
Master clockSatellite reference, with 12-hour holdoverReference. Holdover drift measured at under 2 ms over 12 hours with the antenna disconnectedYes. Loss of satellite and expiry of holdover alarm separatelyAt commissioning
Bus A incomer relayPrecision time protocol from the master clock+0.2 msYesSix-monthly audit
Bus B incomer relayPrecision time protocol+0.3 msYesSix-monthly audit
Set relays G1 to G4Precision time protocol+0.2 ms to +0.4 ms across the fourYes, one per relaySix-monthly audit
Q5 coupler relayPrecision time protocol+0.3 msYesSix-monthly audit
Plant PLCNetwork time from the master clock+11 msYesSix-monthly audit
SCADA serverNetwork time from the master clock+14 msYesSix-monthly audit
Generator controllers G1 to G4None. This model has no time inputNot measurable against a reference. Their own clocks drifted 4 to 9 minutes over a year, which is under 2 s a dayNo. The controllers cannot report their own sync stateAt commissioning, and re-recorded at every audit as a known gap
     
     

The third column is read against what each device’s records are for, not against a single target. The seven protection relays sit between +0.2 and +0.4 ms, comfortably inside the millisecond that sequence-of-events work needs, so their events can be merged into one list and the order trusted. The PLC and the SCADA server sit at +11 and +14 ms, which would be hopeless for ordering relay events and is entirely adequate for what they actually produce — operator logs and alarm time stamps, where a second is the requirement. Two different accuracies, both correct, and the sheet is what makes that a decision rather than an accident.

Row eight is the audit’s real output. The generator controllers have no time input at all, so there is no offset to correct and no alarm to wire; their internal clocks run free and were found 4 to 9 minutes apart after a year. The consequence has to be understood rather than fixed: events from those controllers cannot be merged into a sequence-of-events list, at any accuracy, and must never be laid alongside relay events as though the two shared a timebase.

What saves the mill is that the set relays are synchronised, and the events that matter for reconstructing a trip — protection operation, trip command, breaker position — are all available from them. The controllers’ own logs are useful for what happened to an engine, in order, and for nothing that requires comparison with another device.

Recording that as a line on the sheet, with “No” in the alarm column and a reason in the source column, is worth more than leaving the row out. A blank is read as “not checked”; this entry is read as “checked, cannot be fixed, here is what it costs you”. The alternative, which is to list only the devices that can be synchronised, produces an audit where every row passes and the plant still cannot explain its own events.

Two practices make the sheet stay true. The holdover figure in row one is measured, not quoted — the antenna was disconnected for twelve hours and the drift read off at the end, because a holdover specification describes a clock in a laboratory and this one lives in a switch room. And every row carries a sync alarm where the device supports one, which turns the audit from a six-monthly snapshot into something continuous: the measurement in the third column is only true on the day it was taken, and the alarm in the fourth is what covers the other 182.

Worked example: how fast a free-running clock drifts (illustrative)

A relay or controller without synchronisation keeps time from its own crystal, which is typically accurate to about 20 parts per million. That sounds tiny, but it adds up quickly.

PeriodWorkingPossible error
One hour20 × 10−6 × 3600 sabout 72 ms
One day20 × 10−6 × 86,400 sabout 1.7 s
One week1.73 × 7about 12 s

Within an hour of losing synchronisation, a relay can already be out by more than the 40 ms that separated the feeder and incomer trips in the example above. That is why synchronisation must be monitored continuously and every event must carry a time-quality flag: a relay that lost its time source yesterday is producing records that look precise and are not.

Distribution methods and what they achieve

MethodTypical accuracy at the deviceSuits
Network time (NTP) on a local networkAbout a millisecond or betterControllers, SCADA servers, logs
Precision time protocol (IEEE 1588) with supporting switchesMicroseconds or betterRelays, merging units, phasor measurement
Dedicated time code, unmodulatedMicrosecondsRelays with a time-code input
Dedicated time code, modulatedAbout a millisecondOlder devices

Use the simplest method that meets each device’s need, and check what each device actually supports before choosing; a precision protocol is wasted on a device that can only accept network time.

When the satellite reference is lost

A master clock with good holdover keeps time from its own oscillator when it loses the satellite signal, typically drifting only a few milliseconds a day, so millisecond event records stay valid for hours. Raise an alarm the moment the reference is lost, record the time, and treat records made after a long holdover with appropriate caution. A second master clock with its own antenna removes this single point of failure for critical plants.

UTC inside, local time on the screen

Store every time stamp in UTC and convert to local time only for display. In India local time is UTC plus five and a half hours, and that half-hour offset is mishandled by some older software that assumes whole hours, producing records 30 minutes out. Keeping all devices on UTC also means a record exported from one system lines up with another without anyone having to remember which device used which offset.

Antenna and installation

The satellite antenna needs a clear view of the sky, a surge protector where its cable enters the building, and a cable route away from power cables. The signal delay in the cable, about 5 nanoseconds per metre, is negligible for millisecond records but is entered in the clock for microsecond work. A clock whose antenna sits under a new rooftop structure, or whose cable was damaged by lightning, fails silently unless its loss-of-reference alarm is wired and watched.

Common mistakes

  • Some devices left free-running.
  • Local time and daylight saving mixed with UTC.
  • No alarm on loss of synchronisation.
  • Network time used where millisecond accuracy is needed.

What to send us

Send the list of relays and controllers, their time settings and any event lists that look inconsistent. WhatsApp 98852 01608 or use the enquiry form.

Evidence note. Accuracy figures are typical values for illustration; device makers’ capabilities govern.

Questions engineers ask

How fast does a free-running relay clock drift?

A typical crystal is accurate to about 20 parts per million, so an unsynchronised device can drift about 72 ms in an hour, about 1.7 s in a day and about 12 s in a week. Within an hour it can be out by more than the gap between two trips, which is why synchronisation must be monitored and every event flagged with its time quality.

Which time synchronisation method gives millisecond accuracy?

Network time on a local network typically gives about a millisecond or better, enough for controllers, SCADA and logs. Relays needing better use the precision time protocol with supporting switches, or an unmodulated dedicated time code, both giving microseconds. A modulated time code gives about a millisecond. Match the method to what each device supports.

Is NTP enough?

For operator logs, controllers and SCADA servers, usually yes: on a local network it typically achieves about a millisecond or better. For relay sequence-of-events that must be graded to the millisecond, or for waveform and phasor comparison, use the precision time protocol or a dedicated time code, and monitor each device offset against the master clock.

What is holdover?

The ability of a master clock to keep accurate time from its own oscillator after it loses its satellite reference. A good clock drifts only a few milliseconds a day in holdover, so records stay usable for hours. The loss of reference must be alarmed at once, and records made after a long holdover treated with care.

Why UTC?

Because it never changes with seasons or locations, so records from every device line up without conversion errors. Local time, India Standard Time at UTC plus five and a half hours, is applied only for display. The half-hour offset is mishandled by some older software, which is another reason to keep UTC inside every system.

How do I check sync?

Compare each device time with the master clock continuously where the device reports its offset or synchronisation status, and alarm when the offset exceeds the accuracy the device needs or synchronisation is lost. Audit all devices periodically with a clock audit sheet, and record a time-quality flag with every event so poor time is visible later.

This guide gives general principles. Confirm device capabilities.