Starting kVA

How to calculate motor starting kVA from locked-rotor current or code letter, adjust it for the starting method, and compare it with generator capability.

In short. Starting kVA is the apparent power a motor draws at the instant of starting. For three-phase, starting kVA = 1.732 × V × Istart / 1000, where Istart is the locked-rotor current. A 415 V motor drawing 600 A at start demands about 431 kVA. The figure sizes the starting event; whether a generator survives it depends on the alternator’s motor-starting capability at the acceptable voltage dip and on the load already connected.

What starting kVA measures

When a squirrel-cage motor is switched on, the rotor is stationary and the stator draws locked-rotor current, limited only by the machine’s leakage reactance. That current, multiplied by the supply voltage, is the starting kVA. It is almost entirely reactive, with a power factor typically between 0.2 and 0.4, which is why it stresses the alternator’s voltage far more than it stresses the engine. The engine sees the real power only as the motor accelerates and begins to drive its load.

The quantity is useful because it puts the starting event on the same scale as the generator rating. A 45 kW motor is not a 45 kW problem to the generator; at start it may be a 300 kVA problem. Expressing it in kVA allows a direct comparison with the alternator’s published capability, which manufacturers also state in kVA at a given dip.

The formula and where the current comes from

Starting kVA = (1.732 × V × Istart) / 1000 for three-phase; Starting kVA = (V × Istart) / 1000 for single-phase

Here V is the line-to-line voltage in volts for three-phase or line-to-neutral for single-phase, and Istart is the starting current in amperes. The best source of Istart is the motor data sheet, which gives locked-rotor current either directly or as a ratio to full-load current. IEC motors carry an “Ia/In” figure for this purpose, and NEMA motors carry a code letter that gives locked-rotor kVA per kW of output. Where only the nameplate full-load current is known, a multiple of 6 to 7 is a reasonable screening assumption for standard motors, but high-efficiency IE3 and IE4 motors frequently draw 7 to 9 times full-load current, and that must be checked.

NEMA code letterLocked-rotor kVA per kW of output (approximate)Typical application
F6.7 to 7.5Older standard motors
G7.5 to 8.4Common general-purpose motors
H8.4 to 9.5Many 2-pole and high-efficiency motors
J9.5 to 10.7High-efficiency motors
K10.7 to 12.0Small high-efficiency motors

The code letter table is stated per horsepower in the NEMA standard; the figures above are converted to kW for Indian use and are approximate. For a code G motor of 37 kW, starting kVA is about 37 × 8 = 296 kVA, which agrees well with the locked-rotor current method for a typical machine. Use the manufacturer’s data when the two methods disagree.

Adjusting for the starting method

The formula gives the direct-on-line value. Reduced-voltage starting lowers the current the generator sees, and therefore the effective starting kVA, by a factor that depends on the method. The motor starting guide compares the methods in detail; the multipliers below are the usual screening values.

Comparing with the generator

Alternator manufacturers publish motor-starting capability as the kVA that can be applied in one step from no load for a stated transient voltage dip, usually 20 or 30%, sometimes with a curve for intermediate values. This figure, not the alternator’s continuous rating, is what the starting kVA must be compared against.

For a standard alternator the capability at 30% dip is often around 2.5 to 3 times the continuous rating, which means a DOL motor with starting kVA of about 25% of the set rating can usually be started from no load at a dip near 10%, and a motor at 60 to 70% of set rating will produce a dip near 30%. These are typical relationships and the actual alternator data must be used.

Two corrections matter. If the set already carries load when the motor starts, the available capability is reduced and the dip increases, so the starting kVA must be assessed on top of the existing load. And the dip at the alternator terminals is not the dip at the motor; cable impedance adds more. The voltage dip guide covers the full calculation, and the alternator motor-starting performance page explains why alternators of equal rating differ in capability.

A worked example (illustrative)

A water treatment plant near Vijayawada has a 37 kW borewell pump motor with a nameplate full-load current of 68 A and a data sheet locked-rotor ratio of 6.8. Starting current is 68 × 6.8 = 462 A, and starting kVA at 415 V is 1.732 × 415 × 462 / 1000 = 332 kVA. The plant’s other load when the pump starts is about 80 kVA of lighting, dosing pumps and controls. The total apparent demand during the start is therefore roughly 80 + 332 = 412 kVA, although the two components do not add exactly because their power factors differ; the arithmetic sum is a conservative screening figure.

The plant has been offered a 160 kVA set. On typical data such a set might start about 400 kVA from no load at a 30% dip, and considerably less with 80 kVA already connected, so the 412 kVA event would produce a dip well beyond 30% and most likely an under-voltage trip.

The choices are a soft starter at 3.5 times full-load current, which brings the pump event down to about 171 kVA and a total near 250 kVA, well within the 160 kVA set’s capability at a modest dip, or a set in the 250 kVA class if the pump must remain DOL. The final decision needs the alternator’s actual starting curve and the acceptable dip for the plant’s controls.

Using the motor code letter (illustrative)

Many motors carry a code letter on the nameplate that states their locked-rotor kVA per horsepower. A 30 kW motor is about 40 horsepower. If its code letter corresponds to roughly 5.6 to 6.3 kVA per horsepower, the locked-rotor kVA is about 225 to 250 kVA when started direct on line. This gives a starting figure from the motor itself rather than from a general rule.

Starting power factor and the engine

At the moment of starting, a motor draws mostly reactive current, with a power factor often around 0.3 to 0.4. Of a 240 kVA start, only about 70 to 100 kW is real power that the engine must supply. The alternator and AVR carry the large kVA; the engine carries the smaller kW. This is why a set can have enough engine power but still suffer a deep voltage dip from an alternator that is too small.

Where to find the starting data

SourceWhat it gives
Motor nameplate code letterLocked-rotor kVA per horsepower
Motor data sheetLocked-rotor current and starting power factor
Starter or drive settingsCurrent limit or ramp during start
Site measurementActual starting current and duration

Several motors starting together

If two motors can start at the same moment, their starting kVA add. Control logic that prevents simultaneous starts, or a restart sequence after an outage, keeps the largest single start as the design case.

Checking the result

The calculated starting kVA is compared with the alternator motor starting capability from the maker data, at the allowed voltage dip. If it is too high, the options are a different starter, a larger alternator, or staging the loads.

Common mistakes

What to send us

Send the motor nameplate and, if available, the data sheet showing locked-rotor current or code letter, the starting method and any current-limit setting, the load on the generator at the moment the motor starts, and the generator make, model and alternator type if a set already exists. A photograph of the starter panel and of the generator nameplate is usually enough to begin. Send your application engineering enquiry and we will calculate the starting kVA and compare it with the alternator’s published capability.

Questions engineers ask

How is starting kVA found from a motor code letter?

The code letter gives locked-rotor kVA per horsepower. As an illustration, a 30 kW motor of about 40 horsepower with a code giving roughly 5.6 to 6.3 kVA per horsepower has a locked-rotor demand of about 225 to 250 kVA when started direct on line.

Why does motor starting stress the alternator more than the engine?

At start a motor draws mostly reactive current, with a power factor around 0.3 to 0.4. Of a 240 kVA start only about 70 to 100 kW is real power for the engine, while the alternator and AVR carry the large kVA, causing voltage dip.

Where can motor starting data be found?

From the nameplate code letter for locked-rotor kVA per horsepower, the motor data sheet for locked-rotor current and starting power factor, starter or drive settings for current limit or ramp, and site measurement of actual starting current and duration. Data from the motor itself is always better than a general multiple.

What if the starting kVA exceeds the alternator capability?

Compare the calculated figure with the alternator motor starting capability at the allowed voltage dip from maker data. If it is too high, choose a different starter, a larger alternator, or stage the loads so the motor starts while the set is lightly loaded and the dip is smallest.

Is starting kVA the same as locked-rotor kVA?

For a DOL start, yes; both describe the apparent power at standstill. For reduced-voltage or soft starting, the starting kVA the generator sees is lower than the motor’s locked-rotor kVA by the factor the starting method imposes. Use the starter data sheet to find that factor.

What multiple of full-load current should I assume if I have no data?

Six to seven for older standard motors, and seven to nine for IE3 and IE4 high-efficiency motors. Label the result as an assumption and replace it with data sheet values before selecting a generator. The nameplate code letter, where present, gives the locked-rotor kVA per kW and is a better first figure than a guess.

Can I simply add starting kVA to the running load?

Adding them arithmetically gives a conservative screening figure because the starting current is at a much lower power factor than the running load. Manufacturer sizing software combines them vectorially and will give a slightly lower total. Use the arithmetic sum to screen, then confirm with maker data.

How much starting kVA can a generator handle?

It depends on the alternator, not the kVA rating alone. Typical alternators accept a single step of about 2.5 to 3 times their continuous rating at a 30% dip from no load, and much less if the set is already loaded. Read the manufacturer’s motor-starting curve.

Does starting kVA affect the engine?

Only indirectly. Starting kVA is mostly reactive and loads the alternator and its excitation. The engine responds to the real power as the motor accelerates, which is covered by load acceptance and frequency dip rather than starting kVA. Both checks are needed for every large motor.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.