In short. A resistive load bank draws real power at unity power factor and exercises the engine, fuel system and cooling, but leaves the alternator at only 80% of its current rating. A reactive bank adds inductive load so the set runs at its rated 0.8 power factor, exercising the alternator windings, AVR and excitation at full duty. Capacitive banks are specialised tools for leading power factor problems. Engine performance needs resistive; alternator and paralleling performance needs resistive plus reactive.
What each type is, electrically
A resistive bank is a set of heating elements, usually stainless steel grids or coils, switched in steps and cooled by a fan. Current and voltage are in phase, every kilowatt drawn is dissipated as heat, and the generator sees a power factor of 1.0. An inductive bank is a set of iron-cored reactors that draw current lagging the voltage by 90 degrees. They absorb kVAr but almost no kW, so they load the alternator with current and demand excitation from the AVR while asking little of the engine.
A capacitive bank uses capacitors to draw current leading the voltage, which an alternator experiences as a reduction in required excitation and, if large enough, as a loss of voltage control. Combined banks package resistive and inductive elements together with controls that hold a chosen power factor while the total load is stepped. The load bank rental page lists the types we supply and their step resolutions.
What each type stresses in the generator
| Component | Resistive bank at rated kW | Resistive plus inductive at rated kVA and 0.8 PF | Capacitive load |
|---|---|---|---|
| Engine | Full rated load, full fuel rate, full exhaust temperature | Same full load; kVAr adds negligible mechanical load | Negligible |
| Cooling system | Full heat rejection tested | Full heat rejection plus alternator heating | Negligible |
| Alternator stator | About 80% of rated current | 100% of rated current and temperature rise | Current rises with kVAr; over-voltage risk |
| AVR and exciter | Moderate field current | Full rated field current, rated exciter duty | Field current driven towards zero; control may be lost |
| Governor and transient response | Fully tested on kW steps | Fully tested, with voltage dip at closer to real conditions | Not relevant |
| Paralleling and load sharing | kW sharing only | kW and kVAr sharing both exercised | Leading PF sharing in special cases |
When resistive alone is enough
Most routine generator testing in India is done with resistive banks, for good reasons. The engine is the component most likely to deteriorate from light running, and a resistive bank at 50 to 100% of rated kW is what raises cylinder temperatures, burns off carbon and confirms that the radiator copes in summer.
Resistive banks are compact, widely available for hire from a few kW to several MW and simple to connect. For annual AMC exercise runs, post-overhaul run-in, fuel consumption checks and proving that a new set delivers its kW rating with acceptable temperatures and pressures, a resistive bank answers the question. The load bank sizing guide explains how to choose the kW capacity and step sizes for these tests.
When reactive load is necessary
A resistive test leaves one fifth of the alternator’s current rating and much of the excitation system’s duty untested. Three situations make that gap unacceptable. The first is acceptance of a new or rewound alternator, where winding temperature rise at rated current and AVR performance at rated field current are the quantities being bought. The second is commissioning of a paralleling plant, where kVAr sharing, cross-current compensation and voltage droop can only be adjusted and proven with real reactive load on the bus.
The third is an installation whose load runs at low power factor, such as a plant of lightly loaded induction motors, where the generator will spend its life at 0.75 to 0.85 and should be proven there. In each case the test runs the set to full kVA at 0.8 lagging, and the readings of interest are stator temperature, field current, voltage regulation at each step and the division of kVAr between sets. The kW and kVAr load sharing page explains why the reactive division must be proven separately from the real-power division, and the alternator temperature rise and insulation page explains what the stator temperature reading should be compared against.
Capacitive and leading power factor
Capacitive banks have a narrow but important use. A facility with large UPS systems, LED lighting with input filters, long cable runs or fixed power factor correction capacitors can present a leading power factor to a generator at light load, especially at night when motors are off and the capacitors remain connected. An alternator supplying leading kVAr needs less excitation, and below a certain point the AVR reaches minimum output and loses control of voltage, which then rises.
The limit is given on the alternator’s capability curve. When a site reports high voltage on generator at night or AVR instability with the UPS running, a capacitive bank reproduces the condition under control and establishes how much leading kVAr the set tolerates. The UPS and non-linear loads page covers the wider interaction between generators and electronic loads.
Interpreting the result
A load bank test is evidence for the conditions tested and nothing more. A set that passes a resistive test at rated kW has a proven engine and cooling system and an alternator proven only to 80% current. A set that passes a combined test at 0.8 power factor has a proven alternator and excitation system as well, but has not been shown to handle UPS harmonics, transformer inrush or its largest motor start unless those were separately applied.
The report should state the bank type, power factor at each step, ambient temperature, step durations and readings, so that a later reviewer knows what was and was not demonstrated. A report that says only that the set was tested at 100% is of little use.
Related photographs and videos
What a resistive-only test leaves unproven, in numbers
The sections above explain which parts of the set each type of bank stresses. Putting numbers to the commonest case — a 500 kVA set tested on a 400 kW resistive bank — shows exactly how much of the machine an annual resistive test actually examines, and how much it does not.
| Part of the set | Rated duty | On 400 kW at unity power factor | Proven? |
|---|---|---|---|
| Engine output | 400 kW | 400 kW | Yes, fully |
| Fuel, cooling and exhaust systems | Full load | Full load | Yes, fully |
| Alternator stator current | 696 A | 556 A, 80% of rated | Partly |
| Stator heating | Rated rise | About 64% of rated, because heating goes as current squared | Not at rated temperature |
| Rotor field and exciter | Rated excitation at 0.8 lagging | Far below it: unity load needs much less field | No |
| Regulator under reactive load | Holding voltage with a lagging load | Never asked to | No |
The pattern is clean: a resistive test proves the engine and the systems that serve it, and examines the alternator at a fraction of its duty. That is not a flaw in the test, which is the right annual check for most standby sets. It is a limit on what the result can be used to claim. A report that says the set was “tested at full load” after a resistive test has proved full engine load and roughly two thirds of the alternator’s heating duty.
The rows that matter are the field and the regulator, because they fail in ways a resistive test cannot reveal. A deteriorating rotor winding, a weak exciter diode or a regulator that has drifted all pass at unity load, where little field is asked for, and show only when a real lagging load arrives — typically a motor start or a block of transformer load during an outage. A set that passes every resistive test for years and then cannot hold voltage on its first real event is usually showing exactly this.
The practical rule follows from the table. A resistive test once a year, with a combined resistive and reactive test at commissioning, after any alternator work, and at intervals on sets whose loads are largely motors or transformers. The reactive test is the only one that takes the stator to rated current and the field to rated excitation together, which is the condition the alternator was built for.
Common mistakes
- Accepting a rewound alternator on the strength of a resistive test, which never brings the new windings to rated current or temperature.
- Attempting to set up kVAr sharing between paralleled sets with resistive load only, so the AVR adjustments are made blind and fail on the first real low power factor load.
- Connecting a capacitive bank without checking the alternator’s leading power factor limit, driving the AVR to minimum and producing an over-voltage that damages the test equipment.
- Running the reactive elements without enough resistive load alongside, so the engine idles under a heavy alternator current and the readings bear no relation to service conditions.
What to send us
Send the generator and alternator nameplate photographs, the reason for the test, whether sets will be paralleled during it, the typical power factor of the site load if known, and a description of any voltage or AVR symptom you are trying to reproduce. A photograph of the proposed connection point and the space available outdoors helps us choose the bank. Use the generator and load bank rental enquiry and we will recommend resistive, combined or capacitive equipment.
Questions engineers ask
How much of the alternator does a resistive load bank test actually prove?
Less than the phrase full load suggests. A 500 kVA set on a 400 kW resistive bank carries 556 amps against a rated 696, which is 80% of rated current and, because heating goes as current squared, about 64% of rated stator heating. The engine is proved fully. The rotor field and the regulator are hardly asked to work at all, because a unity power factor load needs far less excitation than the 0.8 lagging load the set is rated for.
Why can a set pass every resistive test and still fail to hold voltage in an outage?
Because the faults that cause it only show under lagging load. A deteriorating rotor winding, a weak exciter diode or a drifted regulator all pass at unity power factor, where little field is needed, and appear when a motor start or a block of transformer load arrives. A combined resistive and reactive test at commissioning and after alternator work is the only routine check that takes the stator and the field to rated duty together.
Is a resistive load bank test enough for an annual generator check?
For a standby set with a healthy alternator, yes. The annual run is mainly to exercise the engine at meaningful load, confirm cooling in summer conditions and clear carbon from light running, all of which a resistive bank does well. A combined test is worth adding every few years or whenever the alternator or AVR has been serviced.
Why does the generator datasheet give kVA at 0.8 power factor?
Because industrial loads are mostly inductive and 0.8 lagging is the standard rating condition for alternators under IS and IEC practice. The engine supplies the kW and the alternator supplies the kVA, so a 500 kVA set carries a 400 kW engine. A test at 0.8 power factor loads both to their rating at the same time.
Can a reactive load bank be used on its own without resistive load?
It can be connected, but the result is not representative. The alternator carries current while the engine runs almost unloaded, so temperatures, governor behaviour and voltage regulation all differ from service. Reactive load should be applied together with resistive load to hold the intended power factor.
How much leading power factor can a generator accept?
It depends on the alternator’s capability curve, but many standard machines become unstable somewhere between 0.9 and 0.95 leading at light load, and the limit tightens as load falls. Sites with large UPS capacity or fixed capacitor banks should confirm the figure with the alternator manufacturer or by a controlled test.
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 19 October 2026.