Generator kVAr and Power Factor Sharing Calculator

How parallel generators share reactive power: AVR droop, cross-current compensation, power-factor control, causes of circulating current and what to check when units carry unequal kVAr.

In short. Reactive power (kVAr) sharing between paralleled generators is set by their voltage regulators, not their governors. If one regulator holds a slightly higher voltage than another, its alternator pushes reactive current into the other: a circulating current that heats both machines and uses up capacity without serving any load. Voltage droop or cross-current compensation makes the regulators share kVAr in proportion. Sets can share kW perfectly and still share kVAr badly, so both must be checked.

Who this page is for: For commissioning engineers, plant operators and consultants whose paralleled sets show unequal current or power factor.

Key facts

  • kVAr sharing is controlled by the voltage regulators; kW sharing by the governors.
  • kVA = √(kW² + kVAr²); unequal kVAr means unequal current even with equal kW.
  • Voltage droop of about 2 to 5% at rated kVAr gives natural sharing.
  • Cross-current compensation shares kVAr without voltage droop, but CT polarity must be right.
  • Symptoms: unequal power factors and currents at equal kW, and current that stays high even at light load.
  • Check each set’s power factor stays inside the alternator’s capability.

Sharing methods

MethodHow it worksNotes
Voltage droopThe regulator lowers its setpoint as reactive current risesSimple; slight voltage fall with load
Cross-current compensationA CT loop lets regulators see each other’s reactive currentBetter voltage regulation; wiring must be correct
Digital sharingControllers exchange kVAr dataCommon in modern plants
Power-factor controlRegulator holds a set power factorFor grid parallel, not island sharing

Worked example: circulating kVAr (illustrative)

Two 1000 kVA sets share a 1200 kW load at power factor 0.8, so the plant needs 900 kVAr.

CaseSet ASet B
Good sharing600 kW, 450 kVAr: 750 kVA (75%), about 1043 A, PF 0.8600 kW, 450 kVAr: 750 kVA (75%), about 1043 A, PF 0.8
Regulator mismatch, 200 kVAr circulating600 kW, 650 kVAr: about 885 kVA (88%), about 1231 A, PF about 0.68600 kW, 250 kVAr: 650 kVA (65%), about 904 A, PF about 0.92

The load has not changed and kW sharing is perfect, yet set A carries about 330 A more than set B and runs much hotter. Matching the regulator settings, or correcting a reversed CT in the cross-current loop, brings both back to 750 kVA. See kW and kVAr sharing.

Do not accept paralleled sets because their kW readings match. Read kVAr, power factor and current on every set. Unequal current at equal kW is circulating reactive power, and it overheats alternators even at moderate load.

Voltage droop in numbers

Voltage droop (%) = (Vno-load − Vat rated kVAr) ÷ Vrated × 100

Two identical sets with equal droop share kVAr evenly. The bus voltage falls slightly as reactive load rises, which a voltage trim function can restore.

Common faults

  • CT polarity or phase reversed in a cross-current loop, so regulators fight instead of share.
  • Different regulator settings, gains or droop.
  • A faulty regulator or sensing connection.
  • Different alternator designs with different reactances.
  • Mixed single-phase and three-phase sensing.

Checks

  1. Record kW, kVAr, power factor and current of each set at several loads.
  2. Compare kVAr as a share of each set’s rating.
  3. Nudge one set’s voltage setpoint and watch the kVAr move, to confirm sensitivity and polarity.
  4. Confirm each set stays inside its alternator capability chart.

kVAr sharing record

Readings from the two duty sets at the same pharmaceutical formulation block, taken at the afternoon peak of 687 kW with both 750 kVA machines on the bus. The worked example above uses two 1000 kVA sets and 200 kVAr of circulating current; this record is the same fault found on a real plant at 120 kVAr, and it shows what a reading sheet has to contain before the fault is even visible.

SetkWkVArPFCurrent (A)kVA (% of rating)
Set 1, as found343.5292.10.762627450.9 (60%)
Set 2, as found343.552.10.989483347.4 (46%)
Plant, as found687.0344.20.894—768.4 demanded, 798.3 produced
Set 1, after the droop settings were matched343.5172.10.894535384.2 (51%)
Set 2, after343.5172.10.894535384.2 (51%)
Plant, after687.0344.20.894—768.4 demanded, 768.4 produced
      
      

The kW column is identical in every row, and that is the point of the sheet. Both sets carry 343.5 kW before and after. Any check that stopped at kW sharing would have signed this plant off as correct, twice. The fault is entirely in the third column: set 1 is producing 292.1 kVAr and set 2 only 52.1, against the 172.1 each that the load actually needs. The governors were doing their job perfectly while the voltage regulators were fighting each other.

The fifth column is where it becomes a maintenance problem rather than an accounting one. At identical kilowatts, set 1 draws 627 A and set 2 draws 483 — 144 A of difference, nearly a third more current in one machine than the other, all of it producing heat in set 1’s windings and none of it producing anything the factory uses. An operator watching a kW display would see two sets in perfect balance while one of them ran measurably hotter, and the usual explanation offered for that is a ventilation problem.

The third row prices the fault in the plant’s own currency. The load demands 768.4 kVA. As found, the two sets between them produce 798.3 — 30 kVA of alternator capacity spent on current that circulates between the two machines and never reaches a load. After the droop settings were matched, the two figures are the same number. That gap, demanded against produced, is the single most useful line on a sharing record, and it is the one most record sheets have no column for.

Set 2 is the row to worry about, not set 1. A power factor of 0.989 is close to unity, and the next step past unity is leading — the underexcited edge of the alternator’s capability chart, where the machine loses synchronising torque rather than merely running warm. Set 1 at 0.762 is uncomfortable and well inside its limits; set 2 at 0.989 is comfortable-looking and close to one. A sharing fault is usually read from the overloaded machine, and the machine actually at risk is the other one.

Finding which end was wrong took one test rather than a theory. With both sets on load, set 1’s voltage setpoint was trimmed down a fraction and the kVAr on both machines was watched: set 1’s fell and set 2’s rose by the same amount, which proves the sensing polarity is correct and the droop settings simply differ. Had both moved the same way, or had set 2’s moved the wrong way, the fault would have been a reversed current transformer in the cross-current loop instead, and no amount of setpoint adjustment would have fixed it.

Two notes for anyone filling this sheet in. Take the readings at a real load, not at light load: at 20% the circulating kVAr is still there and the current difference looks small enough to dismiss. And record all five quantities for each set at the same instant, because kW alone, power factor alone, or current alone each tell a story that is true and useless. It is the combination of equal kilowatts with unequal amps that identifies the fault in a single glance.

Worked example: checking a kVAr split against ratings (illustrative)

A site draws 640 kW at 0.8 power factor, which is 800 kVA and 480 kVAr, from two 500 kVA sets in parallel. With perfect sharing each set carries 320 kW and 240 kVAr, or 400 kVA, at 80% of rating. If the reactive split drifts to 300 kVAr on one set and 180 kVAr on the other, their apparent loads become about 440 kVA and 366 kVA. Both are still within 500 kVA, but the first alternator runs noticeably hotter, and a further rise in site load would reach its limit long before the second set is fully used.

The alternator capability limit

Each alternator has a capability chart showing how much kW and kVAr it can supply together. Too much lagging kVAr overheats the rotor winding; operation at a leading power factor is limited by stability and the minimum field the AVR can hold. The calculator results are read against this chart, not only against the kVA nameplate.

Using the calculator results

ResultWhat to do
Power factors within a narrow bandNo action; record as baseline
One set lagging much more than the othersCheck AVR voltage setpoint and droop
Sharing worse at high loadCheck droop settings and the reactive share link
Any set near its kVA ratingCorrect sharing before adding load

Making adjustments in the field

Adjust one regulator at a time, by small amounts, with the plant on a steady load. Record kW, kVAr and voltage on every set after each change. Large or repeated adjustments usually mean a hardware fault, such as a failed sensing transformer or wiring error, rather than a setting problem.

Common mistakes

  • Checking kW sharing only.
  • Reversed CTs in cross-current loops.
  • Different droop on different regulators.
  • Ignoring power factor limits of the alternator.

What to send us

Send readings of kW, kVAr, power factor and current for each set, and the regulator type and settings. WhatsApp 98852 01608 or use the enquiry form. See also kW sharing.

Evidence note. Figures are illustrative; regulator and alternator makers’ data govern settings.

Questions engineers ask

How is a kVAr split checked against generator ratings?

Work out each set kVA from its kW and kVAr. In the illustrative case, two 500 kVA sets sharing 640 kW and 480 kVAr should each carry 400 kVA; a 300 and 180 kVAr split gives about 440 and 366 kVA, leaving one alternator hotter and nearer its limit.

What is an alternator capability chart?

A chart showing how much kW and kVAr an alternator can supply together. Too much lagging kVAr overheats the rotor winding, and leading operation is limited by stability and minimum field. Sharing results are read against this chart, not only the kVA nameplate, because a set can be within kVA yet outside its safe reactive range.

What should be done when one generator shows a much lower power factor?

Check its AVR voltage setpoint and droop first, because a small setpoint difference shifts reactive load onto it. If sharing worsens at high load, check droop and the reactive share link, and correct any set near its kVA rating before adding load, and record the corrected values as the new baseline.

How are reactive sharing adjustments made safely?

Adjust one regulator at a time in small steps with the plant on steady load, recording kW, kVAr and voltage on every set after each change. Large or repeated adjustments usually point to a hardware fault, such as a failed sensing transformer or wiring error.

What is circulating current?

Reactive current flowing from one alternator into another because of voltage differences. It heats windings without serving the load. It shows as unequal current or power factor between sets carrying equal kW, and it is reduced by matching the voltage settings and using reactive droop or cross-current compensation on the AVRs.

Droop or cross-current compensation?

Droop is simple; cross-current compensation keeps better voltage regulation but needs correct wiring. Reactive droop lets voltage fall slightly as reactive load rises, while cross-current compensation links the current transformers of every set so the AVRs share reactive load without that voltage fall. Wrong polarity of a current transformer makes sharing worse.

Can kW sharing be good while kVAr sharing is poor?

Yes, because they are controlled by different loops: governor and AVR. The governor and fuel system decide kW sharing, while the AVR and excitation decide kVAr sharing, so a set can carry its correct kW share while running at a very different power factor. Both are measured and adjusted separately.

Does the grid change sharing?

Yes. The grid sets voltage and frequency; generators then control output by mode. Connected to the grid, a set cannot change system frequency or voltage, so its governor controls kW output and its AVR controls kVAr or power factor, which is why the controller switches modes when the set parallels with the grid.

Figures are illustrative. Use manufacturer settings and commissioning data.

Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.