In short. Kilowatts measure real power, the part that does work. Kilovolt-amperes measure apparent power, the total the alternator must supply. They are linked by power factor: kVA = kW / PF and kW = kVA × PF. A diesel generator is rated in kVA at 0.8 power factor, so a 100 kVA set delivers 80 kW. Converting a load to kVA is the first arithmetic step in sizing, not the last.
Real power, apparent power and the alternator
Real power in kilowatts is what heats an element, turns a shaft or lights a hall. The engine of a generating set supplies real power, and its fuel consumption follows kW almost exactly. Apparent power in kilovolt-amperes is the product of voltage and current regardless of their timing. The alternator, cables, breakers and transformer carry current, so they are rated in kVA. Reactive power in kilovolt-amperes reactive is the difference between the two: current that magnetises motors and transformers and returns to the source every half cycle without doing work.
A generating set is therefore limited twice. The engine limits kW, and the alternator limits kVA. The nameplate quotes both, almost always at 0.8 power factor lagging, because that is a representative industrial mix of motors and resistive load. At 0.8 PF the two limits are reached together. At a higher power factor the engine limit is reached first and the alternator has spare current capacity. At a lower power factor the alternator reaches its thermal limit before the engine is fully loaded.
The conversion formulas
kVA = kW / PF, kW = kVA × PF, PF = kW / kVA
Here kW is real power, kVA is apparent power and PF is the power factor of the load under the operating condition in question, a number between 0 and 1. For a three-phase load the same relationship applies to the total; the line quantities are kVA = 1.732 × V × I / 1000 with V the line-to-line voltage in volts and I the line current in amperes. The generator current guide works through the current side.
| Load | Power factor | Apparent power | Comment |
|---|---|---|---|
| 100 kW | 1.00 | 100 kVA | Resistive heaters, incandescent lighting |
| 100 kW | 0.90 | 111 kVA | Well-loaded motors, corrected plant |
| 100 kW | 0.80 | 125 kVA | Standard generator rating point |
| 100 kW | 0.70 | 143 kVA | Lightly loaded motors, old fluorescent lighting |
| 100 kW | 0.60 | 167 kVA | Motors at low load, welding sets |
The table shows why power factor is not a detail. The same 100 kW of useful work demands two thirds more alternator capacity at 0.6 than at 1.0. The figures are arithmetic and exact; what must be verified on any real site is the power factor itself.
Choosing the right power factor
The most common error is to take the generator’s rated 0.8 and apply it to the load. The load has its own power factor, and the generator rating has nothing to do with it. A hospital with LED lighting, UPS systems and corrected chillers may run above 0.95. A stone crusher with large motors running well below their rating may be at 0.7. Use a measured value from a power analyser or the DISCOM meter wherever it exists, use manufacturer data for individual machines, and only use 0.8 as a stated screening assumption when nothing better is available.
Displacement and true power factor
Displacement power factor is the cosine of the phase angle between fundamental voltage and current. True power factor includes the effect of harmonic distortion, and is always lower where non-linear loads such as drives, rectifiers and LED drivers are present. A UPS may have a displacement power factor near unity while its true power factor is 0.9 or lower. For generator work the true value matters, because the alternator carries the harmonic current whether or not it does useful work. The power factor guide covers measurement.
Leading power factor
Capacitor banks left in service on generator, long lightly loaded cables, and some UPS input filters make the load capacitive, so current leads voltage. A diesel alternator tolerates only a small leading power factor before its automatic voltage regulator loses control and the voltage rises. The load’s kVA may be correct and the set still unstable, so the inventory should flag any capacitor bank and arrange for it to be switched out when on generator.
Worked examples (illustrative)
A workshop has 80 kW of mixed load at a measured 0.8 PF. The apparent power is 80 / 0.8 = 100 kVA, which matches a 100 kVA set on paper. Before accepting that, the largest motor start, derating and growth must be checked.
A data room has 150 kW of IT load through a modern UPS with a true input power factor of 0.95. Apparent power is 150 / 0.95 = 158 kVA. The set must also supply battery recharge current after an outage, often 10 to 25% above the output load until the battery recovers, and must tolerate the UPS’s harmonic current, so the alternator selection will be larger than 158 kVA even though the arithmetic is correct.
A 200 kW motor-heavy plant at 0.9 measured PF is about 222 kVA. The same plant assumed at 0.8 would have been quoted at 250 kVA, a full frame size larger with a correspondingly lower running load percentage. The difference between measuring and assuming is often a frame size.
Reading a generator nameplate
A nameplate reading 125 kVA, 100 kW, 0.8 PF, 415 V, 174 A, 50 Hz tells you the alternator may carry 174 A per phase continuously at rated temperature rise, and the engine may deliver 100 kW of electrical output at the stated rating category and site conditions.
If your load is 100 kW at 0.95 PF, the current is only about 146 A and the alternator is comfortable, but the engine is at its limit. If your load is 95 kW at 0.7 PF, the current is 189 A and the alternator is overloaded even though the engine is not. Always check both limits, which is why the generator sizing guide asks for kW and PF separately rather than a single kVA.
What a low power factor costs in amps and in heat
The formulas above convert between kW and kVA. Holding the useful power fixed and moving the power factor shows what that conversion means physically: every fall in power factor is paid for in current, and current is paid for twice — once in the size of everything it flows through, and again in the heat it makes there.
Take 400 kW of real load at 415 V and vary only the power factor:
| Power factor | Line current | Apparent power the set must supply | Resistive heating, relative to unity |
|---|---|---|---|
| 1.0 | 556 A | 400 kVA | 1.00 |
| 0.9 | 618 A | 444 kVA | 1.23 |
| 0.8 | 696 A | 500 kVA | 1.56 |
| 0.7 | 795 A | 571 kVA | 2.04 |
| 0.6 | 927 A | 667 kVA | 2.78, for exactly the same useful power |
The second column is linear: current goes as one over the power factor. The last column is not: the heat in every cable, joint, breaker and winding goes as the square of the current, so it goes as one over the power factor squared. Falling from 0.8 to 0.6 raises the current by a third and the heating by 78%, for the same 400 kW delivered.
The third column is where a set gets undersized without anyone noticing. A 500 kVA set carries 400 kW at 0.8 power factor with nothing to spare. The same 400 kW at 0.6 needs 667 kVA, so the set is a third overloaded in current while its kilowatt reading shows a comfortable 400. The engine is fine; the alternator, the cable and the breaker are not, and the kW display gives no sign of it. That is why a set has to be judged on its current or its kVA, never on kW alone, wherever the load’s power factor is uncertain.
It also explains why power factor correction on the load side is worth more than it appears on a tariff. Raising a 0.7 load to 0.9 takes the current from 795 to 618 A for the same work, which frees the equivalent of 127 kVA of generator, cable and switchgear capacity, and cuts the resistive losses in all of them by about 40%. Before a larger set is bought for a load that has grown, the power factor of that load is the first figure to check.
One caution runs the other way. Correction capacitors switched in while a site runs on its generator can push the power factor leading, and an alternator is far less tolerant of leading load than of lagging — its voltage control can be lost. Correction designed for the mains needs to be reviewed, and usually switched out or limited, for generator operation.
Common mistakes
- Using the generator’s rated 0.8 as the load power factor, which oversizes resistive or corrected plants and undersizes motor-heavy ones.
- Treating the kVA result as the generator rating, so the largest motor start, harmonic loading and site derating are never applied.
- Dividing motor shaft kW by power factor without allowing for efficiency, which understates electrical demand by 8 to 15%.
- Leaving power factor correction capacitors connected on generator, which can push the set into a leading power factor and cause voltage instability.
What to send us
Send the kW or kVA of your load with the power factor and how it was obtained, whether measured, taken from a bill or assumed, together with a note of any UPS, drives or capacitor banks on the system. If you have a nameplate photograph of an existing generator and a recent electricity bill, include both so the conversion can be checked against real demand. Send your application engineering enquiry.
Questions engineers ask
Why can a low power factor overload a set that shows normal kilowatts?
Because the alternator, cable and breaker are limited by current, and current rises as the power factor falls. A 500 kVA set carries 400 kW at 0.8 power factor with nothing spare. The same 400 kW at 0.6 needs 667 kVA, so the set is a third over its current rating while its kilowatt display shows a comfortable 400, and the heat in every conductor has risen by 78%.
Should power factor correction stay connected when running on a generator?
Usually not without review. Correction sized for the mains can push the load leading once the site is on a generator, and an alternator tolerates leading load far less well than lagging: its voltage control can be lost. Correction designed for utility operation should be checked for generator operation, and is commonly switched out or limited while the set is the source.
How many kW does a 100 kVA generator give?
At the standard rating point of 0.8 power factor, 80 kW. If the load has a higher power factor the engine still limits output to 80 kW; if it has a lower power factor the alternator current limit is reached before 80 kW is delivered.
Why are generators rated in kVA and not kW?
The alternator is a current-carrying machine whose heating depends on amperes, not on useful work, so its capacity is stated in kVA. The engine’s capacity is stated in kW. Both appear on the nameplate, linked by the 0.8 reference power factor. So a 100 kVA set gives 80 kW at 0.8 power factor.
Does a higher power factor let me use a smaller generator?
It reduces the kVA for a given kW, so the alternator can be smaller, but the engine must still produce the full kW. In practice a set is selected on both limits, and at high power factor the engine, not the alternator, decides the size.
Is 0.8 a safe assumption when I do not know the power factor?
It is a reasonable screening value for mixed industrial load and it should be labelled as an assumption. For motor-heavy plants running at part load it may be optimistic, and for modern commercial buildings it is usually pessimistic. Measure before ordering. A few days of logging gives the real figure.
How do I convert single-phase kVA to current?
For single-phase, current in amperes equals kVA × 1000 divided by the voltage. A 10 kVA single-phase load at 230 V draws about 43 A, which is why larger loads are almost always three-phase. The same 10 kVA on three-phase 415 V draws about 13.9 A per phase.
Looking for a specific rating? See the generator full-load current chart for every common size from 7.5 to 3000 kVA at 415 V and 11 kV.