Building an Electrical Load List: kW, kVA and Power Factor

How to build a load list with kW, kVA, power factor, duty and diversity: the columns that matter, where the numbers come from, and how the list feeds generator, UPS and cable sizing.

In short. A load list is the foundation of every sizing decision. It records each load’s rating, voltage, power factor, duty and starting method. Built well, it feeds generator, transformer, UPS and cable sizing. Built badly, every downstream number is wrong.

Core relationships

kW = kVA × power factor
kVA = kW ÷ power factor
kVAr = √(kVA² − kW²)

For a motor, shaft power is not the electrical input. Input kW = shaft kW ÷ efficiency, and kVA = input kW ÷ power factor. A 30 kW motor at 92 per cent efficiency and 0.86 power factor draws about 32.6 kW and 37.9 kVA.

Recommended columns

ColumnWhy it matters
Load name and tagTraceability
Voltage and phasesDistribution design
Rated kW (shaft or output)Starting point
Efficiency and power factorConvert to electrical input
Input kW, kVA, kVArSizing inputs
Duty: continuous, intermittent, standbyDiversity
Starting method and starting currentGenerator and voltage dip
Criticality classUPS, generator and shedding decisions
Source: nameplate, measured or estimatedConfidence

Where the numbers come from

Connected versus running load

Connected load is the sum of all ratings. Running load is what actually draws power at a time. The difference depends on duty cycles, spares and standby units. See maximum demand and diversity.

Worked example (illustrative)

Three loads: a 30 kW motor (eff. 0.92, pf 0.86), 20 kW of lighting and small power (pf 0.95) and a 15 kW heater (pf 1.0). Input kW: 32.6 + 20 + 15 = 67.6 kW. kVA: 37.9 + 21.1 + 15 = 74.0 kVA. Combined pf = 67.6 ÷ 74.0 ≈ 0.91. The method of adding kVA arithmetically is conservative; adding kW and kVAr, then taking the root of the sum of squares, is more accurate. Here kVAr: 19.3 (motor) + 6.6 (lighting) + 0 = 25.9, giving kVA = √(67.6² + 25.9²) ≈ 72.4. The difference is small but grows with many loads.

Keeping the list useful

Building the connected load table

ColumnSourceWhy
Equipment and tagSite survey, drawingsTraceability
Rated kWNameplateStarting point
Efficiency, power factorDatasheetConvert to input kVA
Quantity and dutyOperatorRunning and standby counts
Starting methodPanel inspectionFor motor-start checks
ClassOperator agreementGenerator-backed or not

Worked example (illustrative)

Three pumps of 30 kW, two running and one standby. Motor efficiency 0.92, power factor 0.85. Input kVA each = 30 ÷ (0.92 × 0.85) ≈ 38.4 kVA. Running load = 2 × 38.4 = 76.7 kVA. The standby pump is not counted in running demand but is kept in the connected total for reference.

Pitfalls

Check against reality

Compare the total with the utility bill’s maximum demand or a logged week. A gap above about 15 percent needs explanation.

See load inventory and maximum demand and diversity guide.

Common mistakes

What to send us

Send your load list or the equipment schedule. Send your application details. See also load inventory.

Questions engineers ask

What is the difference between kW and kVA?

kW is real power doing work. kVA is apparent power, the product of voltage and current. They are related by power factor.

Why does power factor matter for sizing?

It changes the kVA the generator or transformer must supply for the same kW.

Should I use nameplate or measured values?

Measured where possible; nameplate gives an upper bound and often overstates actual load.

How do I treat standby equipment?

List it but mark its duty so it is excluded from running load, and include it where it may run during a changeover.

Figures are illustrative. Check the numbers against your own equipment data.