In short. A generator’s kVA rating times 0.8 gives the real power it can carry in kW, but the right size depends on two things: the running load it must carry, and the largest motor it must start. As rough guides, a 15 kVA set runs a large home with three ACs and a borewell pump, a 62.5 kVA set a branch office or small workshop, a 125 kVA set the common services of a mid-size apartment complex, and a 500 kVA set a hospital, mall section or medium factory. The chart below shows what each common rating from 7.5 to 3000 kVA typically runs, and the largest motor it can usually start.
Who this page is for: For homeowners, building managers and buyers who want a first idea of the generator size they need before a proper load calculation.
Key facts
- Real power available = kVA × 0.8. A 125 kVA set carries 100 kW.
- Size so that the normal running load is about 70 to 80% of the set’s kW.
- The largest motor started direct-on-line is often what decides the size.
- As a rough guide, a set can start a direct-on-line motor rated at about 10% of its kVA (in kW), and a star-delta motor of about 30%.
- UPS, VFDs and other electronic loads may need a larger alternator.
- Use this chart for a first idea; confirm with a load list or the size calculator.
Quick answers: what each size typically runs
- 15 kVA: a large home or villa with three ACs and a borewell pump
- 25 kVA: a large villa, a small commercial floor or a bank branch
- 30 kVA: a bank branch or office with several ACs and an ATM
- 62.5 kVA: a branch office, small nursing home or small workshop
- 125 kVA: an apartment complex’s common services, or a medium workshop
- 250 kVA: a gated community’s common services or a mid-size hospital
- 500 kVA: a hospital, mall section, IT floor plate or medium factory
- 1000 kVA: a large factory, tower or campus, often as two sets
Typical cases only. The right size comes from your own loads and largest motor.
Generator size chart, 7.5 to 3000 kVA
What each common rating typically runs, and the largest induction motor it can usually start with the set lightly loaded. Click a rating to link straight to its row.
| Rating (kVA) | kW at 0.8 PF | Typically runs | Largest DOL motor (kW, approx.) | Largest star-delta motor (kW, approx.) |
|---|---|---|---|---|
| 7.5 | 6 | A small home or shop: lights, fans, fridge, computers and one 1.5-ton AC or a 1 HP pump | 0.75 | – |
| 10 | 8 | A home with two ACs, or a small office or clinic | 0.75 | – |
| 15 | 12 | A larger home or villa with three ACs and a borewell pump; a small shop or office floor | 1.5 | 3.7 |
| 20 | 16 | A villa with four ACs; a small restaurant or office | 1.5 | 5.5 |
| 25 | 20 | A large villa or small commercial floor; a bank or insurance branch | 2.2 | 7.5 |
| 30 | 24 | A bank branch or office with several ACs, computers and an ATM | 2.2 | 7.5 |
| 40 | 32 | A small hotel floor, school block or small workshop | 3.7 | 11 |
| 50 | 40 | A showroom or small hospital floor without imaging | 3.7 | 15 |
| 62.5 | 50 | A branch office, small nursing home, supermarket or small workshop | 5.5 | 18.5 |
| 82.5 | 66 | A mid-size office, nursing home or small factory line | 7.5 | 22 |
| 100 | 80 | An apartment block’s common services; a small factory | 7.5 | 30 |
| 125 | 100 | Common services and limited flat backup for a mid-size apartment complex; a small hospital; a medium workshop | 11 | 37 |
| 160 | 128 | A larger apartment complex’s common load; a hotel; a cold store | 15 | 45 |
| 200 | 160 | A mid-size factory, mall section or hospital with lifts and pumps | 18.5 | 55 |
| 250 | 200 | A gated community’s common services, a mid-size hospital or a factory with several motors | 22 | 75 |
| 320 | 256 | A large apartment complex, a commercial building, or an industrial unit | 30 | 90 |
| 380 | 304 | A large commercial building or process plant section | 37 | 110 |
| 500 | 400 | A hospital, mall section, IT floor plate or medium factory | 45 | 132 |
| 625 | 500 | A large hospital or commercial tower; a process plant | 55 | 160 |
| 750 | 600 | A large factory, data room or commercial campus | 75 | 200 |
| 1000 | 800 | Large factories, towers and campuses; often two smaller sets instead | 90 | 250 |
| 1250 | 1000 | Large plants and campuses; usually paralleled with other sets | 110 | 355 |
| 1500 | 1200 | Multi-building campuses, large hospitals, data facilities | 132 | 450 |
| 2000 | 1600 | Industrial plants and data centres, usually as part of a multi-set plant | 200 | 560 |
| 2500 | 2000 | Large industrial and data-centre plants | 250 | 710 |
| 3000 | 2400 | Among the largest sets built for 415 V; very large plants, where 11 kV sets are often preferred | 250 | 800 |
Motor figures assume the set is lightly loaded when the motor starts, a transient reactance of about 0.25 per unit and a voltage dip limit of about 15%. Soft starters and VFDs allow larger motors. Sets of 10 kVA and below are often single-phase and suit only small direct-on-line motors. For current, breaker and fuel at each rating, see the full-load current chart, the breaker and cable size chart and the DG fuel consumption chart.
How to use the chart
- Add up the loads that must run together during an outage, in kW. Air conditioners use about 1.2 to 1.8 kW per ton when running.
- Divide by 0.75 so that the set runs at about 75% of its rating, then divide by 0.8 to get kVA.
- Find the largest motor and its starter, and check it against the motor columns.
- Take the larger of the two answers and pick the next standard rating up.
- Confirm with a load list in the generator size calculator.
Worked examples (illustrative)
A villa in Hyderabad
Lights, fans, fridge and electronics about 2 kW, three 1.5-ton ACs about 6 kW, a 1.5 HP borewell pump about 1.1 kW: about 9 kW running. 9 ÷ 0.75 ÷ 0.8 ≈ 15 kVA. The 1.1 kW pump is within the 1.5 kW direct-on-line figure for 15 kVA. A 15 kVA set fits; 20 kVA gives room for a fourth AC.
A 200-flat apartment complex
Common services (lifts, pumps, lighting, STP) about 90 kW running, plus limited backup of about 0.3 kW per flat, 60 kW: about 150 kW. 150 ÷ 0.75 ÷ 0.8 = 250 kVA. The largest motor is a 15 kW pump on direct-on-line start, well inside the 22 kW figure for 250 kVA. A 250 kVA set fits. See generators for apartments and gated communities.
A workshop with a large motor
The running load is only 40 kW, which suggests an 82.5 kVA set. But a 30 kW motor on direct-on-line start needs a 320 kVA set by the motor column. Fitting a star-delta starter brings that down to about 100 kVA, and a soft starter or VFD further still. The starter, not the running load, decides the size here.
Do not choose a generator from the chart alone when the site has large motors, lifts, UPS systems or VFDs. These loads can trip or stall a set that looks big enough on paper. Have the size checked against the actual load list.
Loads that need a larger set than the chart suggests
| Load | Why | What to do |
|---|---|---|
| Direct-on-line motors, pumps and motors | Starting current is 5 to 7 times running current | Check the motor columns; use star-delta, soft starters or VFDs |
| UPS and VFD-heavy sites | Harmonic currents heat the alternator and distort the voltage | Choose a larger alternator. See non-linear loads |
| Lifts | Repeated starting and regenerative braking | Allow for simultaneous starts and check regeneration |
| Hot summer afternoons | AC load peaks and engine rating falls in high ambient | Size on summer load and check derating. See ambient temperature derating |
| Fire pumps and life-safety loads | Must run whatever else is on | Size for them in full, with no diversity |
Signs that a set is the wrong size
| Too small | Too large |
|---|---|
| Lights dip sharply and lifts or drives trip when a large motor starts | The set runs at a small fraction of its rating for most of its hours |
| Overload or high-temperature alarms on hot afternoons | Oily black streaks at the exhaust outlet from wet stacking |
| Frequency sags and slow recovery after each load step | More fuel per unit of energy than a correctly loaded set would use |
| Loads must be shed by hand before the set will take them | Higher purchase, service and space requirements than the site needed |
Either way, the cure starts with measured load data, not another guess. A week of readings on the incoming supply shows the real running load and its peaks.
Allowing for future load
A building that will add loads within a few years can take a rating one step up, or keep the chosen size and leave space, a foundation and a switchboard connection for a second set. The second route avoids years of light running while the load grows. See stationary generator installations.
Quick sizing worksheet
| Load | Running kW | Runs during outage? (yes or no) | Starter type |
|---|---|---|---|
| Total running kW, and the largest motor |
Questions buyers ask
How do I measure the real load of my building before sizing?
Log the incoming supply for about a week, covering a hot afternoon and the busiest working hours, and note the peak kW, the steady running kW and the biggest motor starts. Where logging is not possible, list every load that must run during an outage with its kW and starter type, and note which run together.
Should I size a generator for future load?
Allow sensible growth, not every load the building might one day have. Where large additions are firmly planned within a few years, take one rating step up or leave space, a foundation and a switchboard connection for a second set, which avoids years of light running while the load grows.
What size generator do I need for my home?
Add the running kW of what must work during a power cut. A home with three 1.5 ton ACs, a borewell pump, fridge, lights and fans runs at about 9 kW, which needs about a 15 kVA set. Add about 2 kW per extra AC, and check that the pump motor is within the direct on line figure for the chosen rating.
How many ACs can a 25 kVA generator run?
A 25 kVA set carries 20 kW. At about 75% loading that is 15 kW, roughly six or seven efficient 1.5-ton inverter AC units with lights and fans, depending on their efficiency and whether they start together. Older fixed speed ACs draw a high current at each start, so staggering their restart after an outage helps.
What can a 62.5 kVA generator run?
About 50 kW at full rating, so roughly 37 kW of comfortable running load: a branch office, a small nursing home, a supermarket or a small workshop, with direct on line motors up to about 5.5 kW and star delta motors up to about 18.5 kW. Larger motors need a soft starter, a drive or a bigger set.
What size generator is needed for a 100-flat apartment?
For common services such as lifts, pumps, lighting and the sewage plant, plus limited backup to each flat, typically about 125 to 160 kVA. Full backup of every flat air conditioning needs far more. Size from the actual load list, check the largest pump and lift starts, and allow for lifts starting together after an outage.
What is the biggest motor a 125 kVA generator can start?
About 11 kW direct on line with the set lightly loaded, about 37 kW with a star delta starter, and more with a soft starter or a variable frequency drive. If other loads are already running, or the motor drives a heavy load such as a loaded conveyor, the safe figure is lower and the voltage dip should be checked.
Should I choose a bigger generator to be safe?
Only moderately. A set that runs below about 30% load for long periods wastes fuel, builds carbon and suffers wet stacking, and costs more to buy and service. Size for the real running load and the largest motor start with sensible growth, not for every load in the building, and plan a second set if large additions are expected.
Evidence note. Typical uses and motor figures are indicative. Final sizing needs the site’s load list, its largest motors and their starters, and the selected set’s data sheet.
Generators by rating
- Under 15 kVA generators
- 15–50 kVA generators
- 50–125 kVA generators
- 125–250 kVA generators
- 250–500 kVA generators
- 500–1000 kVA generators
- 1000–2000 kVA generators
- 2000 kVA and above generators
Technical content reviewed by D. Srinivas Reddy, Managing Partner and Service Engineer, Reddy Generators. Last updated 8 November 2026.