Behind-the-Meter Generation

Learn how behind-the-meter generators, batteries and CHP can cut demand charges or add capacity, and how to model savings against your own DISCOM tariff.

In short. Behind-the-meter generation is any generator, battery or solar plant on the customer side of the utility meter, run for purposes beyond emergency backup: cutting maximum demand charges, supplementing a constrained DISCOM connection, running CHP, or keeping a process alive through poor grid supply. It should start from the electricity bill, the load curve and the cost of an outage, not from an equipment choice, and its savings must be modelled for the specific tariff before they are promised.

What sits behind the meter

The utility’s energy meter marks the billing boundary. Everything on the customer’s side, including diesel and gas gensets, solar PV, battery storage and CHP plants, is behind the meter. A standby generator that only runs during outages is technically behind the meter too, but the term usually refers to plant that runs deliberately while the grid is available, to change what the site buys from the DISCOM. In Telangana and Andhra Pradesh the motives are usually high demand charges for HT consumers, a sanctioned load that cannot be raised quickly, poor supply quality on rural feeders, or a heat demand that makes CHP attractive.

Start with the business problem

The wrong first question is gas or diesel. The right one is which economic or operational constraint the site is solving. The possible objectives are distinct and lead to different designs.

ObjectiveWhat the plant doesTypical technologyKey data needed
ResilienceCarries critical load through outages and poor supplyDiesel or gas gensets with ATS, BESS for ride-throughOutage history, critical load list, cost of interruption
Peak managementRuns during demand peaks to cap billed maximum demandBESS, fast-starting gensets in parallelFifteen or thirty minute demand profile, tariff structure
Capacity supportSupplies load above the sanctioned grid connectionPrime gensets, BESS, solarSanctioned load, connection upgrade cost and timeline
Energy cost reductionGenerates energy below the grid tariffSolar, gas CHPTariff per kWh, fuel price, operating hours
Combined heat and powerProduces electricity and useful heatGas engines with heat recoveryHeat demand profile, gas supply

Diesel generation is rarely cheaper per kWh than an industrial grid tariff, so diesel behind the meter is usually justified by resilience or capacity, not by energy cost. Gas CHP and solar are the technologies that can lower the energy bill itself. Peak management is mostly a battery job now, as described under peak shaving.

The load profile decides the size

A serious assessment uses interval data from the DISCOM meter or a site logger over at least several weeks, ideally a year. From it come the base load, the maximum demand and how often it occurs, the operating hours, and the shape of the daily curve. Overlay the outage history and the tariff structure: fixed demand charges per kVA, energy charges, time of day rates where they apply, and power factor incentives or penalties. A plant that only needs to shave 200 kVA from a peak lasting forty minutes a day needs a very different solution from one that must supply 2 MW for twelve hours.

Annual saving = (ΔMD × D × 12) + (E_gen × (T − C_gen))

ΔMD is the reduction in billed maximum demand in kVA, D is the monthly demand charge per kVA, E_gen is the annual energy generated in kWh, T is the grid energy tariff per kWh avoided, and C_gen is the cost per kWh of generating it including fuel and maintenance. Worked example (illustrative): a plant reduces billed demand by 300 kVA. At a demand charge of D per kVA per month the saving is 300 × D × 12, or 3600 × D a year.

It also generates 150,000 kWh from a gas engine; if its gas cost per kWh is G and the grid tariff is T, the energy saving is 150,000 × (T − G). The demand saving dominates, which tells you that a battery may serve this site better than an engine. Use the actual tariff order and fuel quotations; these numbers only show the method.

Parallel or non-parallel

Behind the meter does not mean isolated. A non-parallel scheme separates the generator from the grid with an ATS or interlocked breakers, so a part of the load moves to the generator while the rest stays on the grid. It needs no utility approval for interconnection but cannot reduce demand smoothly or share load. A parallel scheme synchronises the generator with the grid and controls its output against the site import.

It allows peak shaving, base loading and CHP operation, but introduces synchronising equipment, interface protection including loss of mains, reverse power and directional overcurrent, fault level checks on the existing switchgear, metering and DISCOM approval in line with CEA connectivity rules. The engineering detail is in utility paralleling. Export to the grid is a further step with its own regulatory requirements and should not be assumed possible.

Technology choices and their trade-offs

Engines

Diesel sets give resilience and capacity at low capital cost but high running cost, and their emissions under CPCB IV+ and state consent conditions limit long-hour use in some locations. Gas engines suit long running hours, especially with heat recovery, as described for trigeneration and CHP.

Batteries and solar

A BESS responds in milliseconds, suits short peaks and provides ride-through, but its energy is limited by its kWh rating. Solar lowers daytime energy purchases but does nothing at night or in an outage without storage. Combinations are covered under hybrid power systems, and larger multi-engine plants under gas engine power plants.

Worked example: a gas engine at a process plant (illustrative)

A food processing plant draws 1.2 MW during two production shifts and about 400 kW at night, and also uses steam and hot water throughout the day. A 1 MW gas engine running in parallel with the grid during the shifts would carry most of the daytime load, with the grid supplying the balance and the night load. Heat recovered from the engine jacket water and exhaust feeds the hot water system and part of the steam demand.

The sizing logic is to match the engine to the steady part of the daytime load rather than the peak, so it runs near its best efficiency for long hours. Running the engine at night at 40% load would reduce its efficiency and wear it faster for little benefit, so the plan keeps the grid for the night load.

Why heat recovery often decides the business case

A gas engine converts roughly 40% of the fuel energy into electricity. Most of the rest leaves as heat in the jacket water and exhaust. Where a site can use that heat for process water, steam or absorption cooling, the overall use of fuel energy can rise to around 80%. Without a use for the heat, the comparison is electricity against electricity, and the margin over grid supply is usually much smaller.

Metering and verifying the savings

Without this metering, nobody can prove whether the plant is performing as planned, and problems such as falling efficiency or poor heat use go unnoticed.

Risks to plan for

RiskEffectTypical response
Gas supply interruption or pressure dropEngine stops or deratesGrid as back-up, or diesel standby for critical loads
Change in grid tariff or gas priceSavings shrink or growSensitivity check before investment
Reduced heat demandLower overall efficiencySize heat recovery to the steady demand
Long maintenance outagesLost savings during downtimePlanned overhauls in low-production periods
Grid connection rule changesAltered parallel operation termsTrack regulatory updates for the connection

Availability and maintenance

A behind-the-meter engine earns its return only while it runs. Gas engines need regular spark plug, valve and oil service, and major overhauls at intervals set by running hours. Planning these in low-demand periods, holding critical spares and monitoring the engine remotely keep availability high and protect the savings the project was built for.

Common mistakes

What to send us

Send twelve months of electricity bills, any interval meter data, the sanctioned load and contract demand, the outage log, and a list of critical loads with their consequence of interruption. Add nameplate details of existing generators, UPS and solar, and a single line diagram if you have one. Use the application engineering enquiry and we will model the options against your tariff before recommending equipment.

Questions engineers ask

How should a behind-the-meter gas engine be sized?

To the steady part of the daytime load rather than the peak, so it runs near its best efficiency for long hours. In the illustrative process plant, a 1 MW engine carries most of a 1.2 MW shift load, while the grid supplies the balance and the 400 kW night load.

Why does heat recovery matter for on-site gas generation?

A gas engine converts roughly 40% of fuel energy into electricity, and most of the rest leaves as heat. Using that heat for process water, steam or absorption cooling can raise overall fuel use to around 80%, which is often what makes the project worthwhile.

How are behind-the-meter savings verified?

Meter gas into the engine, electricity out and heat delivered to the process, keep grid import records from before and after the project, log hours, starts, trips and downtime, and review the figures monthly against the business case so falling efficiency or poor heat use is caught early.

What risks affect a behind-the-meter generation project?

Gas supply interruption or low pressure, changes in grid tariffs or gas prices, reduced heat demand, long maintenance outages and changes in grid connection rules. Each needs a planned response, such as grid or diesel back-up, sensitivity checks, heat recovery sized to steady demand and planned overhauls.

Can a diesel generator reduce my electricity bill?

Rarely through energy cost, because diesel generation usually costs more per kWh than an industrial grid tariff. It can reduce demand charges if run briefly at peaks in parallel with the grid, but a battery often does that more cheaply. Diesel behind the meter is mainly justified by resilience and capacity.

Do I need DISCOM approval to run a generator in parallel with the grid?

Yes. Parallel operation requires an interconnection approval, a protection scheme with loss of mains and reverse power functions, and appropriate metering. Non-parallel operation through an ATS or interlocks generally does not need interconnection approval, though the generator itself still needs the usual statutory clearances. Confirm both in writing before work starts.

What is the difference between behind-the-meter and captive generation?

Behind the meter describes physical position on the customer side of the billing meter. Captive generation is a regulatory status under the Electricity Act and its rules, with ownership and consumption conditions, and can include plant located away from the site. A behind-the-meter plant may or may not qualify as captive.

How much data is needed to size behind-the-meter generation?

At minimum several weeks of interval demand data covering normal operation, plus twelve months of bills to capture seasonal variation and maximum demand events. A year of fifteen minute data is ideal. Sizing from connected load alone almost always oversizes the plant. Logged data shows the real peaks, base load and their timing.