DG Set Log Book: Daily, Weekly and Monthly Entries

In short. A DG set log book has three parts: a daily pre-start check that takes five minutes, a running record taken every time the set runs, and weekly and monthly entries covering test runs, fuel reconciliation and condition checks. Kept honestly, it shows trouble weeks before a breakdown — coolant temperature creeping up, battery voltage sagging, fuel use per kWh rising — and gives your service engineer the facts to act on. The formats below are ready to print, with a filled example week showing how to read them.

Who this page is for: operators, electricians and facility supervisors who run DG sets day to day, and managers who want a log that is actually useful, not a register filled in from memory at month end.

Key facts

Why most log books fail, and how to make yours work

Most DG log books we see on service visits are one of two kinds. Some are blank, because nobody was asked to fill them. Others are full of identical numbers in the same handwriting, written at month end. Neither tells anyone anything. A useful log has four habits:

  1. Real readings at the time, by the person who took them, with initials.
  2. Units and normal ranges printed on the sheet, so an abnormal value stands out the moment it is written.
  3. A remarks column that is actually used: leaks seen, alarms, sounds, smells, smoke colour.
  4. A weekly look by a supervisor, who signs the page and acts on trends.

Daily pre-start check (set at rest)

Done once a day for standby sets, or before every start for sets that run daily. It takes about five minutes.

Running record (every run)

Take the readings after 15 minutes on load. On runs longer than four hours, take them again every two hours.

Reading Typical healthy range* What a change means
Oil pressure Steady within the maker’s running band; typically about 2.5–5 bar hot at rated speed (confirm the maker’s band) Falling: oil dilution, low level, worn bearings or a sensor fault
Coolant temperature About 75–95 °C on load Rising: dirty radiator, low coolant, a belt or thermostat fault, or air recirculation
Voltage, line to line (three readings) 415 V ± 2.5% (about 405–425 V), all phases close Low or unequal: AVR, sensing or loading problem
Frequency 50 Hz, steady between about 49.5 and 50.5 Hz Low on load: overload or fuel restriction. Swinging: governor or fuel fault
Phase currents (three readings) Within the rated current; imbalance under about 10% High imbalance: single-phase loads badly distributed
kW and power factor kW 30–80% of rated for most of the time; PF 0.8–0.95 lagging Low PF: motor loads without correction. Leading PF: capacitor bank left on
Battery charging voltage About 13.5–14.4 V (12 V system) or 27–28.8 V (24 V system) Low: alternator or belt fault. High: regulator fault
Exhaust colour Clear to light grey on load Black: overload or air restriction. White: unburnt fuel or coolant. Blue: oil

*Always use the manufacturer’s figures for your engine where they differ. Write the maker’s bands on the printed sheet.

Weekly entries

Monthly entries

Worked example (illustrative): reading one week of a 125 kVA apartment set’s log

The set: 125 kVA, so rated kW = 125 × 0.8 = 100 kW, with a 12 V battery. It runs during power cuts plus a weekly test on Saturday mornings.

Day Hours at start Run (h) Oil (bar) Coolant (°C) V L1/L2/L3 A L1/L2/L3 kW Hz Batt. rest (V) Fuel added (L) Remarks
Mon 4,812.0 2.5 4.1 84 414/415/413 88/72/61 48 50.0 12.7 — Power cut 6–8:30 pm
Tue 4,814.5 0 — — — — — — 12.6 — Pre-start check OK
Wed 4,814.5 3.0 4.0 87 413/414/412 95/74/63 52 49.9 12.5 — Slight oil mist at rocker cover
Thu 4,817.5 0 — — — — — — 12.4 — Pre-start check OK
Fri 4,817.5 1.5 4.0 89 414/414/413 90/73/62 50 50.0 12.3 120 Radiator face dusty
Sat 4,819.0 0.5 4.1 90 414/415/414 92/74/63 51 50.0 12.3 — Weekly test; transfer 8 s
Sun 4,819.5 0 — — — — — — 12.2 — Pre-start check OK

Reading it like a service engineer:

  1. Load: about 50 kW on 100 kW rated, or 50%. That is a healthy level.
  2. Current imbalance on Wednesday: the average is (95 + 74 + 63) ÷ 3 = 77.3 A. The largest deviation is 95 − 77.3 = 17.7 A, giving 17.7 ÷ 77.3 × 100 = 22.8%, well above 10%. The L1 phase carries too much of the common-area load. Action: an electrician redistributes single-phase circuits at the next shutdown.
  3. Coolant temperature: 84, 87, 89, then 90 °C at similar loads. That is a 6 °C creep in one week, and the Friday remark explains it: a dusty radiator face. Action: clean the radiator from the fan side outwards, then watch the next readings.
  4. Battery at rest: 12.7 V falling to 12.2 V over the week. A fully charged 12 V battery rests at about 12.6–12.7 V; 12.2 V is roughly half charge. With a healthy charger on float, the reading should never slide like this. The charger is not keeping up. Action: check the charger output and the battery condition before the set fails to start during the next power cut.
  5. Fuel: about 7.5 hours at about 50 kW = 375 kWh. Fuel drawn, from the day-tank readings, was 104 litres, so 104 ÷ 375 = 0.28 L/kWh. That is within the normal band; keep it as this month’s baseline.
  6. Remark: the oil mist at the rocker cover is minor now, but it is logged with a date, so the next service can deal with the gasket.

Result: three problems found and acted on in one week, none of them yet a breakdown. That is what a log book is for.

When a reading means “stop and call”

Observation Action now
Oil pressure falling, or a low oil pressure alarm Shut down. Check the level. Do not restart repeatedly. Call your service engineer.
Coolant above about 100 °C, or a high-temperature alarm Reduce load or shut down. Do not open the radiator cap hot. Check the fan, belt and radiator face.
Frequency below 49 Hz on load, or black smoke Shed load. The set is likely overloaded or short of fuel or air.
Fuel or oil leak near the exhaust or turbocharger Shut down immediately. Fire risk.
Battery at rest below about 12.2 V (or 24.4 V) Check the charger and the battery today, before the next start is needed.
New knock, rattle or vibration Shut down and inspect. Note when it started and at what load.

Log sheet 1: daily pre-start check and running record

Site Set no. / kVA Rated kW (kVA × 0.8) Month Maker’s oil pressure band (bar) Maker’s coolant band (°C)
           
Date Oil level ✓ Coolant ✓ Fuel (L) Batt. rest (V) Leaks / belts / louvres ✓ Controller AUTO, no alarms ✓ Hours start Hours end Oil (bar) Coolant (°C) V L1/L2/L3 A L1/L2/L3 kW PF Hz Charging V Exhaust colour Fuel added (L) Remarks / alarms Initials
                                         
                                         
                                         
                                         
                                         
                                         
                                         

Log sheet 2: weekly entries

Week ending Test run: kW / minutes AMF transfer time (s) Water drained from separator? (Y/N) Battery terminals and electrolyte ✓ Charger OK ✓ Hoses, mounts, exhaust ✓ Current imbalance (%) Issues and actions Supervisor signature
                   
                   
                   
                   
                   

Log sheet 3: monthly entries

Month Opening fuel (L) Fuel received (L) Closing fuel (L) Fuel used (L) Running hours kWh generated L/kWh Long load run or load bank: kW / minutes Hours since last service Next service due at (hours) Earth pits and cables ✓ Housekeeping and extinguishers ✓ Manager signature
                           
                           
                           

Exceptions and cautions

  • The healthy ranges on this page are typical. Your engine’s maker sets the real bands, and some electronic engines run hotter or at different oil pressures by design. Write the maker’s figures at the top of each sheet.
  • Prime-power and continuous-duty sets that run every day need running readings every two hours, and a shift handover line.
  • Sets with remote monitoring still need a paper or digital log of the physical checks: leaks, belts, louvres and housekeeping are not visible to a sensor.
  • Never bypass a protection to keep a set running because a log entry looks normal. A trip means stop and investigate.

Common mistakes

What to send us

Send photographs of the last two or three weeks of log pages, along with the set’s kVA and hour-meter reading. Our service engineers will read the trends, flag anything that needs attention, and set the service plan by hours. Site staff can also send individual readings or photographs of a gauge, an alarm or a leak to the service engineer as they occur. Use the service enquiry, or WhatsApp 98852 01608. We work across Telangana, Andhra Pradesh and every district within about 300 km of Hyderabad, with project support across India.

Questions engineers ask

What should be recorded in a DG set log book?

Daily pre-start checks (oil, coolant, fuel, battery, leaks, louvres, controller status), running readings on every run (hours, oil pressure, coolant temperature, three voltages, three currents, kW, PF, frequency, charging voltage, exhaust colour), plus weekly test runs and monthly fuel reconciliation.

How often should a standby generator be test run?

Weekly, on load: at least 30 to 40 percent for 30 minutes or more. Add a longer run above 50 percent, or a load-bank test, each month if the building load is light.

How do I calculate the load percentage of my generator?

Divide the measured kW by the rated kW and multiply by 100. For a standard set, rated kW is kVA times 0.8, so a 125 kVA set is rated at 100 kW.

How do I work out current imbalance?

Find the average of the three phase currents, take the largest difference between any phase and that average, divide by the average and multiply by 100. Keep it within about 10 percent.

What fuel consumption is normal for a diesel generator?

Between 50 and 100 percent load, a healthy set typically uses about 0.26 to 0.33 litres per kWh, at the higher end of that band at lighter load. Confirm against the maker’s data for your engine. Track your own figure monthly; a steady rise points to a fuel, air or injection problem, or to fuel going missing.

What battery voltage shows a problem?

A fully charged 12 V starting battery rests at about 12.6 to 12.7 V. Around 12.2 V is roughly half charge and needs attention before the next start. On load, charging voltage should be about 13.5 to 14.4 V.

Is a digital log as good as a paper log?

Yes, if readings are entered at the time by the person who took them, and the physical checks are recorded as well as the controller data. Remote monitoring cannot see a leak, a loose belt or a blocked louvre.

Related pages

Technical content reviewed by D. Srinivas Reddy, Managing Partner and service engineer. Last updated 5 November 2026.