In short. An APFC panel adds capacitors to keep your power factor close to unity on the grid. On generator supply, especially at light load, those same capacitors can push the power factor leading. The generator’s voltage regulator loses control, voltage rises or swings, and the set trips. The usual cure is simple: switch the capacitors off, or limit them, whenever the generator is supplying the load.
Who this page is for: For plant electrical and maintenance teams: find out whether your capacitor bank is tripping your generator, and fix it.
Key facts
- Generators are designed to supply lagging (inductive) loads. Leading power factor is outside their comfortable range.
- The problem is worst at light load, when capacitor kVAr is large compared with the actual load.
- Symptoms include over-voltage, voltage hunting, alternator alarms and tripping soon after changeover.
- A DG-ON signal from the changeover or AMF panel can switch the APFC off automatically.
What happens, step by step
- On mains, the APFC panel switches capacitor steps in to cancel the lagging current of your motors.
- Power fails and the load moves to the generator. Some capacitor steps are still connected.
- The load on the generator is lighter than usual, or motors have not restarted yet. The capacitors now supply more reactive power than the load needs — the power factor becomes leading.
- Leading current raises the alternator’s voltage. The automatic voltage regulator cuts back excitation to compensate.
- If excitation is pushed too low, the regulator loses control: voltage swings, the set becomes unstable, and over-voltage or excitation protection trips it.
Symptoms to look for
- Set trips a few seconds or minutes after taking load, but runs fine with the APFC switched off
- Voltage on the generator panel higher than normal, or swinging
- Power-factor meter showing leading (capacitive) on DG supply
- Repeated AVR or alternator faults with no clear engine cause
- Lamps flickering or electronics failing during generator operation
Fixes that work
| Fix | How it works | When to use |
|---|---|---|
| Disable APFC on DG supply | A DG-ON contact from the AMF or changeover panel switches all capacitor steps off when the generator is supplying | Most sites — simplest and most reliable |
| Separate DG setting in the APFC relay | Many relays accept a second input to change the target or limit steps on generator supply | Large plants that still want some correction on DG |
| Correct step sizes | Smaller first steps avoid over-correcting at light load | Panels with oversized steps |
| Detuned reactors | Reactors in series with capacitors prevent resonance with harmonics from drives and UPS | Sites with VFDs, UPS or other electronic loads |
| Fixed capacitors removed or switched | Fixed capacitors on motors or transformers stay connected on DG; they must be switched with the load | Older installations |
Harmonics make it worse
Drives, UPS systems and LED lighting create harmonic currents. Capacitors can resonate with them, drawing excess current, overheating and failing. A generator has a higher internal impedance than the grid, so harmonic distortion is usually worse on DG supply. If your site has many electronic loads, detuned capacitor banks are worth the extra cost.
A service engineer’s view
When a DG set “trips for no reason” in a factory, the APFC panel is one of the first things to check. The quickest test is to run the set on the same load with the capacitors switched off. If the problem disappears, the fix is in the wiring between the panels, not in the engine.
What you get from us
- Diagnosis of DG tripping, hunting and over-voltage problems
- DG-ON interlock wiring between AMF, changeover and APFC panels
- AVR checks and replacement
- Advice on step sizes and detuned capacitor banks
How much leading kVAr can an alternator actually absorb?
Every alternator has a capability chart: a map of the kW and kVAr it can supply. On the lagging side the limit is field-winding heat — more lagging kVAr needs more excitation current. On the leading side the limit is quite different. Leading current through the stator aids the rotor’s magnetic field (armature reaction works in the same direction), so the regulator must reduce excitation to hold voltage. There is a floor: the regulator cannot reduce field current below zero, and long before that the set becomes unstable.
For a typical stand-alone industrial set, the usable leading region is small — often in the order of 10–30% of rated kVA as leading kVAr. Light load is the danger point not because this limit shrinks, but because the load’s own lagging kVAr, which offsets the capacitors, is then smallest. The actual figure comes from the alternator’s own capability chart, which is worth asking for whenever capacitors will remain on DG supply.
Self-excitation: when the regulator has nothing left to cut
If enough capacitance is connected, the alternator can hold up its voltage with almost no field current at all. Residual magnetism produces a small voltage; that voltage drives leading current into the capacitors; the leading current strengthens the field; the voltage rises further. It settles only where the alternator’s magnetisation curve meets the capacitors’ voltage–current line — which can be well above 415 V. The regulator has already reduced excitation to its minimum and cannot intervene. This is why some sets show over-voltage even with the AVR apparently “off”.
Capacitor kVAr rises with voltage
Capacitor output rises with the square of voltage. A bank rated 200 kVAr at 415 V delivers 200 × (440 ÷ 415)² ≈ 225 kVAr at 440 V. So as leading power factor pushes voltage up, the capacitors produce even more leading kVAr — a self-reinforcing loop rather than a self-correcting one.
Reconnection and discharge time
Capacitors need time to discharge after switching off — commonly up to about a minute through their discharge resistors. If the changeover transfers load to the DG while steps are still charged, or the APFC relay re-inserts them too quickly, the set sees a sharp current transient at the moment of closing. A DG-ON interlock should therefore switch steps off before the DG breaker closes, not after.
Worked kVAr calculation
Illustrative case. A 500 kVA set (rated at 0.8 power factor: 400 kW, 300 kVAr lagging). The alternator chart allows an assumed 100 kVAr leading. During the day on mains, the APFC has switched in four 50 kVAr steps (200 kvar). An evening outage arrives during a shift change; only 80 kW of load remains, at 0.85 lagging.
Net kVAr on DG = 49.6 − 200 ≈ 150.4 kVAr leading
kVA = √(80² + 150.4²) ≈ 170.4 kVA → pf = 80 ÷ 170.4 ≈ 0.47 leading
The set is lightly loaded in kW, yet the 150 kVAr leading is half as much again as the 100 kVAr the alternator can tolerate. Voltage rises, the capacitors give more kVAr, and the set trips. With the DG-ON interlock, all four steps drop out and the set sees 80 kW at 0.85 lagging — comfortably inside its chart.
If the plant wants some correction on DG, the rule is simple: capacitor kVAr left connected must stay below the load’s own lagging kVAr at the lowest load the set can drop to before the relay has time to remove steps. At 300 kW and 0.8 lagging (225 kvar), four 50 kVAr steps leave 25 kVAr lagging and a power factor of 300 ÷ √(300² + 25²) ≈ 0.997 lagging — acceptable. At the 80 kW night load, not even one 50 kVAr step can be allowed, because 50 kVAr exceeds the 49.6 kVAr the load needs.
The Indian angle
- kVAh billing: where tariffs bill on kVAh, sites push APFC targets to unity and run aggressive step settings — ideal on mains, risky on DG.
- Evening and night outages: outages often come at shift change or on the night shift, exactly when kW is low and capacitor steps are still in from the daytime load.
- Panel heat: APFC panels in un-ventilated rooms at 45 °C ambient run hotter still inside. Capacitors lose capacitance as they age, so staff sometimes force extra steps in manual mode — and forget them.
- Monsoon: lower air-conditioning load in the rains reduces lagging kVAr, so a step arrangement that was safe in May can lead in August.
Light-load audit worksheet
Record these with the set on its lowest normal load — typically late evening or a holiday — to see how close it runs to the leading region.
| Item | Reading |
|---|---|
| DG rating (kVA) and rated power factor | |
| Alternator leading kVAr limit from its capability chart | |
| Lowest load on DG (kW) and time it occurs | |
| Power factor at that load (lag / lead) | |
| APFC steps connected at that moment (number × kvar) | |
| Fixed capacitors on motors or transformers (kvar) | |
| DG voltage at that load (V) — compare with set value | |
| AVR excitation reading or indicator, if available | |
| Does the DG-ON signal reach the APFC relay? (tested yes/no) | |
| APFC relay mode found (auto / manual) |
Decision table: what the readings mean
| Finding | Interpretation | Recommended step |
|---|---|---|
| Lagging pf on DG at all loads, steps all off | Interlock working | No change; retest after any panel modification |
| Leading pf only at the lowest load | Steps or fixed capacitors exceed load kVAr at light load | Interlock all steps on DG, or limit steps by a second relay setting |
| Leading pf with steps off | Fixed capacitors, UPS input filters or long cables still connected | Trace and switch fixed capacitors with their loads; review UPS filter settings |
| Voltage high, AVR excitation at minimum | At or near self-excitation | Treat as urgent: remove capacitance on DG before further running |
| Trip at the moment of changeover | Charged steps switched on to the DG, or re-inserted too fast | Drop steps before the DG breaker closes; check relay reconnection delay |
Alternator and regulator checks that go with this audit are covered on the AVR & excitation service page; the arithmetic above can be repeated with the power-factor calculator.
Common mistakes
- Leaving the APFC panel in automatic on generator supply.
- Blaming the AVR for over-voltage trips that only happen at light load with capacitors connected.
- Fitting motor-terminal capacitors without checking how they behave on generator supply.
- Ignoring harmonics, which overload capacitors and add to nuisance trips.
What to send us
Send the set’s kVA, the APFC panel size and number of steps, how the panel is switched on generator supply, the alarm or trip shown, the load and power factor at the time, and the time of day the trips occur. Use the application engineering enquiry, or WhatsApp the details and photographs.
Questions engineers ask
Why does my generator trip when the APFC panel is on?
On generator supply, capacitors in the APFC panel can push the power factor leading, especially at light load. The generator’s voltage regulator then loses control, voltage rises or swings, and protection trips the set.
Should the APFC panel be switched off on DG supply?
On most sites, yes. A DG-ON signal from the AMF or changeover panel can switch all capacitor steps off automatically whenever the generator is supplying the load.
What is leading power factor?
It is when the current leads the voltage, which happens when capacitive reactive power exceeds the inductive needs of the load. Generators are designed for lagging power factor and become unstable when it goes leading.
Can harmonics cause capacitor and generator problems?
Yes. Drives, UPS systems and LED lighting create harmonics that can resonate with capacitors. Detuned capacitor banks with series reactors prevent this.
Can you fix this without changing the generator?
Usually, yes. Most cases are fixed by wiring an interlock between the generator panel and the APFC panel, or by changing the APFC settings.
Related pages
Technical content reviewed by D. Srinivas Reddy, Managing Partner and service engineer. Last updated 3 November 2026.