Protection Coordination Study Workflow Guide

A step-by-step workflow for a protection coordination study: data collection, one-line verification, fault levels, device curves, margins, setting recommendations, verification and documentation.

In short. A coordination study chooses settings so that, for any fault, the device nearest the fault trips first and the rest wait, while cables and equipment are protected. The workflow runs from verified data through fault levels and curves to documented settings and field verification.

Workflow

  1. Scope and criteria. Decide the boundary, standards, grading margins and objectives. See setting philosophy.
  2. Collect data. Single-line diagram, device types and models, existing settings, CT ratios, cable and transformer data, motor data.
  3. Verify on site. Compare nameplates and settings to the drawings. See inputs and validation.
  4. Fault levels. Maximum and minimum for each operating mode. See maximum and minimum.
  5. Load and inrush data. Full-load, starting, transformer inrush and cold-load pickup currents.
  6. Equipment damage curves. Cable thermal limits, transformer damage curves, motor stall and starting curves, generator damage curves.
  7. Plot curves. Time-current curves of devices from load to source. See TCC engineering.
  8. Set devices. Starting from the load end, set each device with margin above downstream devices and below damage curves.
  9. Resolve conflicts. Change devices, add zone interlocking or differential, or accept partial selectivity with a recorded reason.
  10. Review modes. Repeat for utility, generator and parallel.
  11. Document. Settings tables, curves, assumptions and notes.
  12. Implement and verify. Apply settings, test by injection, and record as-left values.

Deliverables

Grading margins

Margins reflect the downstream device’s clearing time, the upstream relay’s tolerance and overshoot. Use manufacturer data and the philosophy document rather than a fixed rule.

Typical findings on generator sites

Illustrative example

A site with a main breaker and eight feeders trips the main when any feeder faults. The study finds the main’s short-time delay is zero and its pickup is below the feeder fault level. Setting a short-time delay and a higher pickup restores selectivity, and the study checks that the delay still protects the busbar and the upstream cable.

A coordination study in eight steps

  1. Obtain the verified single-line diagram and device data.
  2. Collect equipment damage curves: transformer, cable, motor and generator.
  3. Run load flow and short-circuit studies for load, inrush, maximum and minimum faults.
  4. Plot device curves on a common current base.
  5. Set the device nearest the load first, then work towards the source.
  6. Apply time margins between devices, commonly 0.2 to 0.4 seconds depending on device type.
  7. Check each setting against the damage curve and the minimum fault.
  8. Record settings and issue relay files.

Data you must have

DataWhy
Device make, model, curve familyCurves differ between makers
CT ratiosConvert primary to secondary settings
Transformer inrushAvoid false trips on energisation
Generator decrement curveVerify pickup on decayed fault current

Operating scenarios

Coordinate for every state that matters: mains, generator, parallel. A setting that is selective on the mains may lose selectivity on the generator because the fault current is much lower.

Deliverables

See TCC engineering and coordination and selectivity.

Common mistakes

What to send us

Send relay and breaker data. Send your application details. See also coordination and selectivity.

Questions engineers ask

How long does a coordination study take?

It depends on size and data quality. Data collection and verification often take longer than calculations.

Can I coordinate without software?

For simple radial systems, yes with manufacturer curves. Larger systems benefit from software.

Is full selectivity required?

For critical loads, it is the goal. Partial selectivity may be acceptable elsewhere with documented reasons.

When should the study be updated?

After changes in sources, loads, protection devices or settings.

This guide gives general principles. Settings must be verified on site.