Maximum and Minimum Fault-Current Studies Guide

Why both extremes of fault current are studied: how to build each case, which assumptions differ, how results set equipment duty and protection sensitivity, and generator-only conditions.

In short. The maximum case finds the highest fault current so equipment is not overstressed. The minimum case finds the lowest credible fault current so protection still operates and trips fast enough. Both are needed, and on generator-supplied systems the minimum case is often the critical one.

Assumptions that differ

ItemMaximum caseMinimum case
Sources in serviceAll possible, including parallel generators and utilityWeakest credible combination (for example, a single generator)
Utility fault levelMaximumMinimum
Voltage factorMaximumMinimum
MotorsIncludedExcluded
Conductor resistanceAt low temperatureAt operating temperature
Transformer impedanceLower toleranceUpper tolerance
Fault typeUsually three-phaseUsually phase-to-phase or phase-to-earth
Fault resistanceZeroMay include arc or contact resistance

How the results are used

Generator-only conditions

When the utility is lost, a single generator may supply the whole site. Fault current is then only a few times the generator rating and decays. Breakers and relays sized for the utility’s thousands of amps may take seconds, or fail, to clear a fault. This is the most common gap found in studies of standby systems. See generator contribution.

Workflow

  1. Define the operating configurations that could occur, including maintenance states.
  2. Identify the weakest and strongest configurations.
  3. Calculate each fault type at each bus in each case.
  4. Compare the maximum results with equipment ratings.
  5. Compare the minimum results with protection pickup and time requirements.
  6. Resolve conflicts: for example, a setting that suits both cases, or a second setting group.

Illustrative example

A distribution board shows a maximum fault current of 25 kA with the utility and a generator in parallel and about 3.5 kA with the generator alone. A feeder breaker with an instantaneous setting of 4 kA would operate in the first case but not the second, where the cable could overheat before the long-time element trips. The study recommends a lower setting under generator supply and a check of cable withstand.

Two studies, two purposes

StudyAssumptionsAnswers
MaximumHighest utility level, all generators and motors on, minimum impedance tolerance, voltage factor 1.05 to 1.10Is the equipment strong enough?
MinimumLowest utility level, only essential sources, longest cable lengths, hot conductor resistance, voltage factor 0.95 to 1.0Will protection detect and clear the smallest fault?

Worked comparison (illustrative)

A 415 V board shows 28 kA maximum with utility and generator in parallel, and 3.2 kA minimum with the generator alone. A breaker with an instantaneous setting of 6 kA clears the maximum fault but never trips instantly on the minimum. The long-time or short-time function must then clear the fault, which may take seconds. The study exposes this before it happens.

Details for the minimum case

  1. Use conductor resistance at fault temperature, which is higher than at 20 degrees C.
  2. Include arc resistance for arcing earth faults.
  3. Consider the far end of long feeders.
  4. Check earth-fault loop impedance for the disconnection time required.

Using the results

See coordination workflow and overcurrent protection.

Common mistakes

What to send us

Send the single-line diagram and source data. Send your application details. See also short-circuit study architecture.

Questions engineers ask

Which case is more important?

Both. One protects equipment; the other makes sure protection works.

Why exclude motors in the minimum case?

They may not be running, and their contribution is brief, so excluding them gives a conservative lower value.

What if one setting cannot cover both?

Use setting groups, additional elements or different devices.

Does the minimum case include arc resistance?

It can, in some methods, since arcs reduce current.

This guide gives general principles. Cases should follow the chosen standard.