Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Transformer Protection Guide for Distribution and Generator Step-Up

How transformers are protected: fuses and overcurrent, differential, REF, Buchholz and temperature devices, inrush and overexcitation, with typical schemes by transformer size and application.

In short. Transformer protection combines electrical elements (overcurrent, earth fault, differential for larger units) with device-level protections (gas, pressure, temperature). The scheme depends on size, importance and whether the transformer connects to a generator.

Protections by type

ProtectionDetects
HV fuse or overcurrentShort circuits and overloads
Earth fault / REFEarth faults in windings. See REF
DifferentialInternal winding faults on larger units. See differential
Buchholz relay (oil-filled with conservator)Gas from faults, oil surge
Pressure relief deviceInternal pressure rise
Winding and oil temperatureOverload and cooling failure
Overexcitation (volts per hertz)High voltage or low frequency

Inrush

Energising a transformer draws a high current for a short time, many times full load, rich in second harmonic. Overcurrent and differential settings need to ride through. Harmonic restraint is common in differential relays. When a generator energises a transformer, the large inrush can also depress generator voltage. See transformer sizing.

Generator step-up and distribution

Design steps

  1. Establish transformer size, vector group, impedance and earthing.
  2. Pick protections by size and criticality.
  3. Set the overcurrent above inrush and below damage curves.
  4. Configure differential with ratio and vector group compensation and inrush restraint.
  5. Wire non-electrical devices to alarm and trip, and test.

Illustrative example

A 2.5 MVA, 11/0.433 kV transformer is protected by an HV breaker with overcurrent and earth-fault relays, a Buchholz relay for oil faults and winding temperature trip. The overcurrent instantaneous element is set above inrush at a multiple of full-load current, and the earth-fault relay is graded with the LV main.

Protection scheme by transformer size

Size or roleTypical protection
Small distribution transformerHV fuse or breaker with overcurrent and earth fault; thermal alarm
Medium transformerOvercurrent, earth fault, REF, Buchholz or pressure relief, winding temperature
Large or critical transformerDifferential, REF, Buchholz, overfluxing, backup overcurrent

Non-electrical protections

Inrush and energisation

Energising can draw inrush of several times rated current. Overcurrent settings must ride through it, while differential relays use harmonic restraint. Sequence energisation on a generator carefully, since inrush also dips generator voltage. See generator sizing.

Overfluxing

High voltage or low frequency raises flux in the core, causing heating. A volts per hertz function protects generator step-up transformers and others at risk.

Setting steps

  1. Obtain the transformer rating, impedance, vector group and tap range.
  2. Calculate full-load, inrush and through-fault currents.
  3. Set overcurrent above load and inrush and below damage curve.
  4. Coordinate with upstream and downstream devices.
  5. Commission with injection tests.

Maintenance

Test relays, oil, bushings and cooling. Thermography and oil analysis can reveal ageing before faults. Keep a record of trips and alarms.

Common mistakes

What to send us

Send transformer nameplate and network data. Send your application details. See also coordination.

Questions engineers ask

What is a Buchholz relay?

A gas-and-oil flow relay on oil-filled transformers that detects internal faults.

When is differential required?

For larger or critical transformers, as set by standards and owner practice.

Why do transformers trip on energisation?

Inrush may exceed settings. Harmonic restraint and settings above inrush address it.

Do dry-type transformers need different protection?

They use temperature sensors in windings instead of oil devices.

This guide gives general principles. Scheme selection needs project data.