Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Restricted Earth-Fault Protection Guide

How restricted earth-fault protection detects winding earth faults in generators and transformers: high and low impedance schemes, CT needs, stability and setting checks.

In short. Restricted earth-fault protection compares the neutral current with the sum of the phase currents. It trips only for earth faults inside the protected winding, is fast and sensitive, and stays stable for faults outside. It needs matched CTs and careful setting.

Principle

For an external fault, current entering the winding through the phase CTs equals the current leaving through the neutral CT, so the relay sees almost nothing. For an internal earth fault, the currents do not balance, and the relay operates. Because only earth faults in the winding are covered, it is “restricted”.

Where it is used

It is added to differential protection because it detects low-level winding earth faults that differential may miss, especially when the neutral is resistance earthed. See differential protection.

Schemes

SchemeFeatures
High impedanceVoltage-operated relay with stabilising resistor; needs matching CTs of the same ratio and good knee-point voltage
Low impedance (biased)Numerical relay with bias; tolerates CT differences, more flexible

Setting and design points

Commissioning checks

  1. Verify CT ratios, polarity and wiring.
  2. Measure CT magnetising curves for high-impedance schemes.
  3. Do primary injection to confirm operation and stability. See injection testing.
  4. Record settings.

Illustrative example

A 1,500 kVA generator with its neutral earthed through a resistor that limits earth-fault current to a few hundred amps is protected with REF. The relay is set to detect a small percentage of the limited current. Primary injection through the neutral confirms it operates, and an external-fault test confirms that it remains stable.

How restricted earth fault works

REF compares the current entering a star-connected winding on the phase conductors with the current flowing in the neutral-to-earth connection. For a fault outside the winding, the two balance and the relay does not operate. For a fault inside the winding, current flows in the neutral that is not balanced by the phase currents, and the relay operates.

Operating quantity = | I(phases, residual) + I(neutral) | with CT polarity arranged so external faults cancel

Why use it

Applications

EquipmentRole of REF
Transformer star windingDetects winding earth faults, complements differential
Generator statorDetects earth faults in the stator winding where earthing limits current

Implementation points

  1. CTs on the phases and neutral should be of the same ratio and matched characteristics.
  2. High-impedance REF uses a stabilising resistor and a voltage-setting; low-impedance numerical REF uses algorithms. Choose one approach and design for it.
  3. CT knee-point voltage must be adequate for the stability setting.
  4. Wiring and polarity errors cause wrong operation; confirm by primary injection.

See differential protection and CTs and VTs.

Commissioning tests

Common mistakes

What to send us

Send generator or transformer data and earthing arrangement. Send your application details. See also earth-fault protection.

Questions engineers ask

Why use REF as well as differential?

REF is more sensitive to low-level earth faults near the neutral, which differential may not detect.

What is a stabilising resistor?

A resistor in a high-impedance scheme that keeps the relay stable for external faults.

Can REF protect a delta winding?

No. It applies to earthed star windings.

Does it work with a solidly earthed neutral?

Yes, and it is still useful, though differential covers more.

This guide gives general principles. Scheme design needs CT data and a study.