Motor and Feeder Protection Guide

How motors and feeders are protected: overload, locked rotor, short circuit, earth fault, unbalance and undervoltage, with starter types, relay settings and generator-supply considerations.

In short. A motor circuit needs protection against short circuit (fuse or breaker), overload (thermal or electronic relay), and increasingly against locked rotor, phase loss, unbalance, earth fault and undervoltage. Feeders need overcurrent and earth-fault protection coordinated with the board. On generator supply, starting currents and voltage dips need extra care.

Motor protection functions

FunctionPurpose
Short-circuitFuse or instantaneous trip set above starting current
Thermal overloadModels heating from running current, with trip class matched to the starting time
Locked rotor / stallTrips when starting current persists beyond the safe time
Phase loss / unbalancePrevents single-phasing damage. See unbalance protection
Earth faultDetects insulation failure. See earth-fault protection
UndervoltagePrevents restart or stalling at low voltage
Temperature (RTD, PTC)Winding and bearing monitoring on larger motors

Starter and relay choices

Feeder protection

Feeder circuits need overcurrent for short circuit and overload, earth-fault protection and coordination with the upstream device. Cables must be protected within their thermal limit. See cable protection.

On generator supply

Setting steps

  1. Take motor nameplate data: full-load current, starting current and time, stall time, service factor.
  2. Set the overload to motor full-load current and choose the trip class.
  3. Set the short-circuit element above starting current peaks.
  4. Set the locked-rotor time below the motor’s stall withstand.
  5. Check coordination with upstream feeder devices.

Illustrative example

A 90 kW pump motor starts in 6 seconds with a starting current of about six times full load. The overload relay is set to full-load current with a trip class that permits the 6-second start, the locked-rotor element is set shortly beyond the start time, and the short-circuit element is above the peak starting current. On generator supply, the voltage dip prolongs the start, so the stall timer is checked against the longer start.

Motor protection functions

HazardProtection
OverloadThermal model or inverse-time overload
Locked rotor or stallStall protection with start-time supervision
Short circuitInstantaneous overcurrent, with setting above starting current
Earth faultEarth-fault element, often with core-balance CT
Phase loss or unbalanceNegative-sequence or phase-failure function
Frequent startsStart-count and cooling-time limit
UndervoltageRelease and restart logic

Starting current and settings

Direct-on-line starting draws roughly 6 to 8 times full-load current for a few seconds. Instantaneous settings must sit above this, typically with margin for asymmetry, while thermal protection must tolerate the start but trip on a stall. See motor starting.

Feeder protection on a generator supply

A generator offers lower fault current than the utility, so instantaneous elements may not pick up on a remote fault. Check feeder settings against generator-only fault level and confirm discrimination with upstream devices. See coordination.

Restart after supply transfer

When power returns after a transfer, many motors restart together and demand a large inrush. Stagger restarts through timers or sequencers.

Practical checklist

  1. Confirm motor nameplate data and starting method.
  2. Set thermal class to the motor’s thermal limits.
  3. Check CT ratio against full-load current for accuracy.
  4. Test overload, earth fault and stall functions.

Common mistakes

What to send us

Send the motor schedule and starter details. Send your application details.

Questions engineers ask

What is a trip class?

A measure of how long an overload relay allows the starting current before tripping.

Why does a motor trip on generator but not on grid?

The generator has higher voltage dip and different fault characteristics. Longer starts and undervoltage can trip it.

Is a fuse or a breaker better for motors?

Both work. Fuses limit current well, breakers reset and offer adjustability. Use what the design needs.

Do small motors need all these functions?

No. Scale protection to motor size and criticality.

This guide gives general principles. Check motor data for settings.