ACB, MCCB, MCB and Protection Device Selection Guide

How to choose between air, moulded-case and miniature breakers and fuses: ratings, breaking capacity, trip units, selectivity and what suits generator duty.

In short. Choose the device by current, breaking capacity at the installed point, trip characteristics and the need to coordinate with devices upstream and downstream. Breaking capacity must exceed the maximum fault level at that point, including the contribution of generators and motors.

Device families

DeviceTypical rangeTypical use
ACBLarger currents, high short-time withstandIncomers, couplers, generator breakers
MCCBMedium currentsFeeders, motors, sub-distribution
MCBSmall currentsFinal circuits, controls
FusesWide range, fast current limitingMotor circuits, back-up, switch-fuse

Key ratings

Selection steps

  1. Calculate load current and apply derating.
  2. Find the maximum fault level at the device location. See fault-level engineering.
  3. Choose a device with a breaking capacity above this level.
  4. Choose the trip unit to give the settings range for coordination.
  5. Check selectivity with neighbouring devices. See coordination and selectivity.
  6. Check cable protection by the device.

Generator-specific points

Illustrative example

A feeder to a 160 kW motor group has a load current near 300 A and a fault level of 30 kA at the board. An MCCB with an electronic trip unit and a breaking capacity above 36 kA is chosen. Its short-time setting is set to allow downstream devices to trip first. On generator supply the fault current is lower, and the setting is verified to still trip within the time the cable can withstand.

Selecting a breaker: the parameters

ParameterMeaning
Rated current (In)Continuous current at a stated ambient
Rated voltageSystem voltage the device is designed for
Breaking capacity (Icu, Ics)Maximum fault current the breaker can interrupt; service value Ics is the more meaningful for repeated duty
Short-time withstand (Icw)Ability to carry fault current for a time, for selectivity
Trip unitThermal-magnetic or electronic with adjustable settings
Poles and neutral rating3P, 4P, with a neutral sized for harmonics where needed

Choosing between types

Check against the fault level

The breaker’s breaking capacity must exceed the prospective fault current at its location. Compute the fault level from both utility and generator sources and use the higher. See fault-level engineering.

Generator incomers

Generator breakers are selected for the generator’s rated current, the lower fault level and its decaying shape. Choose a trip unit that will actually trip at the generator’s fault current, and check coordination with downstream devices.

Derating and installation

  1. Ambient temperature inside enclosures higher than outside; apply derating.
  2. Terminal temperature limits for cable size.
  3. Grouping in a board raises temperature.
  4. Altitude and humidity per maker.

Maintenance considerations

Draw-out ACBs allow testing and replacement without long shutdowns. Moulded-case devices are usually replaced rather than repaired. Record trip tests and operation counters.

Common mistakes

What to send us

Send the single-line diagram and fault data. Send your application details. See also fault current basics.

Questions engineers ask

When do I need an ACB rather than an MCCB?

For higher currents and where high short-time withstand is needed for selectivity, such as incomers and couplers.

What is breaking capacity?

The maximum fault current the device can interrupt safely at a given voltage.

Why four-pole breakers?

To switch the neutral when changing between sources, which supports correct earth-fault protection.

Do fuses still have a role?

Yes, for fast current limiting and motor circuits, often with a contactor and relay.

This guide gives general principles. Check manufacturer data for ratings.