Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Critical-Power Protection and Selectivity

How protection is designed for critical power so a fault clears locally: selectivity, generator and transformer protection, changing fault levels and the common ways protection causes outages.

In short. In a critical-power system, protection must clear faults quickly while taking out as little as possible. That is selectivity. It is harder here than in a simple system because sources change: fault levels differ between utility, generator and island, and settings must work for all of them.

Goals of protection

The source problem

Source stateFault currentProtection concern
Utility connectedHighEquipment ratings, arc-flash energy
Generator onlyLower, decayingRelays may not pick up or may be slow
Inverter or BESS onlyVery limitedOvercurrent protection may fail to detect
Ties closedHighestBreaker ratings and selectivity

See maximum and minimum fault-current studies.

Selectivity methods

See protection coordination and selectivity.

Generator protection specifics

A generator’s fault current falls quickly, and the unit may have voltage-controlled or voltage-restrained overcurrent protection, along with reverse power, loss of excitation, over-frequency and over-voltage functions. Check that the generator can hold a fault long enough to trip downstream devices, via excitation support such as a permanent magnet or a boost circuit. See generator protection relays.

Protection that causes outages

Worked illustration

A downstream feeder breaker and an upstream incomer both have overcurrent settings. On utility supply, the feeder trips first as intended. On generator supply, the fault current is only about three times the generator’s rating and the feeder’s instantaneous setting never picks up, so the upstream breaker trips and the whole board goes. Re-setting for the lower fault level, or adding a sensitive element, restores selectivity. A study with both sources would have shown this.

Verification

Selectivity is continuity

In a critical system, a fault must clear at the lowest possible level. If a final-circuit fault trips the main breaker, the protection works but the system fails.

LevelProtection aim
Final circuitClear the fault, nothing else affected
Distribution boardBack up the circuit device, isolate the board
Main switchboardClear a board fault without losing all boards
Source (UPS, generator)Protect the source, allow fault clearing

Challenges specific to critical power

  1. UPS and inverter sources have low fault current, so downstream devices may not trip quickly. Use fast-acting fuses or breakers sized for the UPS, and check bypass-mode behaviour where the mains-fed fault level is high.
  2. Generators have decaying fault current; check pickup on the decayed value.
  3. Different sources have different fault levels; coordinate for each.
  4. Selectivity tables from the manufacturer help for breakers, backed by a TCC study.

Bypass trap

When the UPS goes to static bypass, the fault level from the mains is much higher than the inverter’s. A downstream device selective on the inverter may not be selective on bypass. Study both.

Verification

Perform the coordination study, apply settings and verify by injection tests. See coordination and selectivity and TCC engineering.

Common mistakes

What to send us

Send the single-line diagram, relay data and fault levels. Send your application details. See also protection study selection.

Questions engineers ask

Why does protection fail to trip on generator supply?

Generator fault current is lower and decays, so settings based on utility levels may not pick up.

What is selectivity?

Only the protective device nearest the fault trips, leaving the rest of the system supplied.

Do I need a coordination study?

For critical systems, yes, covering each source state and tie configuration.

How often should settings be reviewed?

After any change in sources, loads or equipment, and on a periodic schedule.

This guide gives general principles. Settings must come from a coordination study.