Legacy Switchgear Modernisation and Retrofit Guide

Options for ageing switchgear: condition assessment, retrofit breakers, relay replacement, partial and full replacement, outage planning, safety and the decision factors for each route.

In short. Old switchgear may still carry load but can lack spares, safety features and protection capability. Start with a condition and risk assessment, then choose between refurbishing, retrofitting breakers or relays, partial replacement or full replacement, planning outages carefully.

Signs it is time to act

Condition assessment

  1. Review drawings, history, loads and fault level.
  2. Inspect visually, with thermography, partial discharge where applicable.
  3. Test breakers, insulation, contact resistance and protection.
  4. Assess busbar and enclosure condition.
  5. Rank risks by consequence and likelihood.

Options

OptionDescriptionConsiderations
RefurbishmentClean, repair, replace worn partsLowest cost, limited by obsolescence
Retrofit breakersReplace breaker elements with modern ones in existing cubiclesNeeds compatible dimensions and approvals
Relay replacementNumerical relays replace electromechanicalAdds functions and records; wiring changes
Partial replacementReplace critical sections or panelsStaged outages
Full replacementNew switchgearHighest cost and outage, best long-term result

Planning the work

Illustrative example

A 30-year-old generator panel has obsolete relays and a breaker with no spare parts. The decision is to replace the relays with a multifunction numerical relay, retrofit the breaker element, keep the enclosure and busbar after inspection, and add a sync-check relay. The work is done in a weekend outage with a temporary generator supplying the critical load.

Why modernise

Older switchgear may lack spares, use electromechanical relays, offer limited breaking capacity for today’s fault levels and provide no data. Replacement of everything is expensive, so retrofit options matter.

Options

OptionScopeNotes
Relay upgradeReplace old relays with numerical onesBetter protection and records, panel stays
Breaker retrofitReplace breaker with a modern unit in the existing cubicleNeeds a compatible design and type-test support
Panel refurbishmentReplace busbar insulation, clean, re-torqueExtends life where the structure is sound
Full replacementNew switchboardBest when fault rating or structure is inadequate

Assessment steps

  1. Check present and future fault level against equipment rating.
  2. Inspect condition, history and availability of spares.
  3. Review protection adequacy and coordination.
  4. Plan outage and staging so critical loads remain supplied.

Practical hazards

Retrofit work often involves live adjacent sections. Plan isolation, safe procedures and temporary supply. Generators on site can support loads during the work. See upgrade and replacement planning.

After retrofit

Re-run protection studies, commission fully and update drawings and labels. See testing and commissioning.

Common mistakes

What to send us

Send drawings, photos and history. Send your application details. See also upgrade and replacement planning.

Questions engineers ask

Is retrofit cheaper than replacement?

Usually, up front. Whole-life cost and risk should be compared.

Can new breakers fit old cubicles?

Often with retrofit kits, but verify design approvals and ratings.

Do I need a new study after retrofit?

Yes, because ratings, settings and fault levels may change.

How can I keep power on during the work?

With staged outages and temporary supplies.

This guide gives general principles. Decisions need inspection and testing of your switchgear.