Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Utility + DG + UPS + BESS System Studies Guide

How to study a combined utility, diesel generator, UPS and battery system: operating modes, transitions, step response, fault behaviour, harmonics and control hierarchy for reliable power.

In short. When utility, generator, UPS and battery storage share a site, each can help or harm the others. The study defines every operating mode and transition, then tests voltage, frequency, fault current, harmonics and control behaviour in each. The weakest transition usually decides reliability.

Sources and their roles

SourceStrengthLimit
UtilityStiff, low cost energyOutages and sags
Diesel generatorLong-duration energyStart delay, step limits, higher impedance
UPSNo-break for critical loadsShort battery time, rectifier harmonics
BESSFast response, peak supportLimited energy, limited fault current

Modes and transitions to study

  1. Normal utility supply.
  2. Utility loss, UPS on battery, generator start.
  3. Generator takes load, UPS rectifier restarts.
  4. Return to utility with retransfer, open or closed.
  5. BESS peak shaving, islanded operation and grid support.
  6. Failure cases: generator fails to start, ATS fails, UPS bypass, BESS trips.

What to check in each mode

Control hierarchy

Only one source should set frequency in an island. Two grid-forming sources fighting for it cause oscillation. Define which is grid-forming, which follow, and what the fallback is.

Illustrative example

A data hall has two UPS systems, two generators and a battery system for peak shaving. The study finds that on generator, the UPS rectifier input distortion is high and the battery inverter, set as grid-forming, competes with the generator governor. The fix sets the generator as the leader in island mode, the battery as follower, and adds a soft-walk-in on the UPS rectifier.

Four sources, four behaviours

SourceRoleStrengthLimit
UtilityPrimary energyStrong fault level, low costOutages, voltage events
Diesel generatorLong-duration backupDuration limited only by fuelStart delay, weak source
UPSInstant ride-throughNo breakBattery minutes, low fault current
BESSEnergy shifting, peak support, longer ride-throughFast responseEnergy limited, converter limits

The UPS protects the instant; the generator protects the duration.

Studies in scope

  1. Sequence of operation during mains failure: time from loss to generator on bus, and battery energy used meanwhile.
  2. UPS input behaviour on generator supply, including walk-in, input power factor and harmonics.
  3. BESS control mode (grid-following or grid-forming) and interaction with the generator.
  4. Fault levels and protection in each combination.
  5. Retransfer and recharge loading.

Battery energy check (illustrative)

A 400 kVA, 0.9 PF UPS carrying 300 kW needs about 300 kW × 10 min ÷ 60 = 50 kWh from the battery during a 10 minute generator start window, plus efficiency losses. If the generator starts in 15 seconds, the battery need is tiny and the margin large; if a generator fails to start, the UPS autonomy is the time to shut down safely.

Interaction hazards

See UPS and nonlinear loads and ATS study.

Common mistakes

What to send us

Send the one-line diagram and the operating philosophy. Send your application details. See also ATS service.

Questions engineers ask

Can a battery replace a generator?

Only for the duration its energy allows. Long outages still need a source of energy.

Why does the UPS cause trouble on generator?

Rectifier harmonics and large steps stress the generator.

What is grid-forming?

A source that sets voltage and frequency for the island.

Is a closed-transition retransfer worth it?

It avoids a second outage, but needs synchronising checks and protection.

This guide gives general principles. Integrated systems need a project-specific study.