Local, Remote, Automatic and Supervisory Control Philosophy

How to define control modes for generators, breakers and transfer systems: who may operate, mode priority, handover rules, lockouts and the safeguards that keep manual work safe.

In short. A control philosophy states, for each device, who can operate it in each mode, which mode wins when they disagree and how the plant moves between modes safely. Without it, operators and automation can issue conflicting commands at exactly the wrong time.

The four modes

ModeWho commandsTypical use
Local manualPerson at the equipmentMaintenance, testing, emergency
Local automaticDevice controllerStandby, AMF, protection
RemoteOperator through SCADA or HMIControl room operation
Supervisory automaticPlant controller or EMSDispatch, sequencing, scheduling

Priority rules

  1. Protection and emergency stop override all modes.
  2. Local manual overrides remote and supervisory, so a person at the equipment is never surprised.
  3. Remote overrides supervisory automatic, with an alarm.
  4. Supervisory automatic works within permissives set by device controllers.

Mode changes

Safety and maintenance

Lock-out and isolation must work independently of the mode. A remote start command should be impossible while a maintenance lock is applied. See interlocking and permissives.

Authority at the boundary of the plant

Decide who owns decisions at the points where a person, a controller and a utility meet. For example, utility instructions on export or parallel operation may limit what the plant controller can do. See interconnection studies.

Illustrative example

A technician selects manual on a generator for a test. The control room, unaware, tries to start the set for a scheduled run. Because the philosophy blocks remote commands in local manual and displays “LOCAL” on the mimic, the command is refused with an alarm, and the technician is not at risk.

Four ways to control the same breaker

ModeWhere the command comes fromTypical use
Local (at device)Push button or selector at the panelMaintenance, commissioning, emergency
Remote (manual)Operator at HMI or control roomPlanned switching
AutomaticProgrammed logic responds to conditionsMains failure, load changes
SupervisoryHigher system sets targets or schedulesEnergy dispatch, demand limits

Rules for a clean philosophy

  1. Only one mode is active per device at a time.
  2. Mode changes are deliberate, logged and visible.
  3. Local mode blocks remote and automatic commands, and raises an alarm so that a unit left in local is not forgotten.
  4. A return to automatic after maintenance follows a checklist, with the controller confirming healthy status.

Bumpless transfer between modes

Switching from manual to automatic should not cause a jump in output. The controller picks up the present state and then adjusts.

Common failure

A generator left in manual after a test, so the next mains failure finds no automatic start. The remedy is a persistent alarm, an automatic return timer where safe, and a pre-event checklist.

See control hierarchy and interlocking and permissive logic.

The master engineering question

At this moment, in this mode, who has the authority to operate this device, and does everyone who could be affected know it?

What to send us

Send your operating modes and any site safety rules. Send your application details.

Questions engineers ask

Should remote start always be possible?

Only when permissives and safety conditions allow it, and never against a local lockout.

What if the control room loses communication?

The plant should continue in local automatic, as defined.

Who may change modes?

Authorised persons only, with access control and a log.

How do I stop a set staying in manual?

Add a standby-not-ready alarm and test AUTO state in routine checks.

This guide gives general principles. Mode rules should match site safety procedures.