Electrical Interlocking and Permissive Logic

How to design interlocks and permissives that prevent unsafe switching: mechanical, key and electrical interlocks, hard-wired versus software logic, bypass rules and testing of blocked paths.

In short. Interlocks stop actions that must never happen, such as two sources closing together or closing onto an earthed bus. Permissives are conditions that must be true before an action. Critical interlocks must not depend on software alone, and each must be tested in the blocked direction.

Types

TypeHow it worksUse
MechanicalPhysical linkage prevents two breakers closingATS, bus ties
Key interlockTrapped keys enforce sequenceMaintenance isolation, bypass
Electrical hard-wiredContacts in the close circuitFast, simple, highly reliable
Software permissivePLC or controller logicFlexible, secondary protection

What must be interlocked

Design rules

  1. Rank hazards. Use independent layers for the severe ones.
  2. Use positive feedback, such as auxiliary contacts that show true breaker position.
  3. Wire for fail-safe: wire break leads to a safe state.
  4. Keep interlocks independent of a single power supply. See control power.
  5. Document each interlock in a table with cause, effect and test.
  6. Control bypass keys under a permit process.

Permissive example

To close a generator breaker onto a live bus: generator voltage and frequency in window, sync check OK, bus not earthed, no lockout, mode permits, breaker ready. Any missing condition blocks the close and shows the reason on the HMI.

Testing

Test not only that the permitted action works but that each blocked action is truly blocked. Test with simulated failures, such as lost feedback and wrong breaker position. See acceptance framework.

Illustrative example

An ATS has a mechanical interlock between its two contactors, backed by an electrical interlock in the close circuit. On a test, removing the mechanical link in a workshop setting shows that the electrical interlock still blocks the second close. The two layers are independent.

Interlock versus permissive

TermMeaningExample
InterlockPrevents an action that is unsafeUtility and generator breakers cannot both close
PermissiveA condition that must be true to allow an actionClose generator breaker only if voltage is in window
Trip / lockoutForces a safe stateProtection trip locks out the breaker from reclosing

Three layers, in order of trust

  1. Mechanical: key interlocks and physical blocks, independent of power.
  2. Hardwired electrical: contacts in series with the close coil.
  3. Software logic: flexible, but not the only guard for safety-critical actions.

Writing the permissive matrix

ActionPermissives
Close generator breaker to dead busGenerator voltage and frequency OK, bus dead, no other source closing, no trip active, automatic or manual mode OK
Close generator breaker to live busSync-check OK, generator healthy
Close tieBoth sides healthy, no bus fault trip, capacity OK
Return to mainsMains stable for the return delay

Testing

Test each permissive by removing it and confirming the action is blocked. Test failure of each input: a lost signal should block, not allow.

Common error

Using a normally closed contact as a healthy signal can fail unsafe when a wire breaks. Design so that loss of signal blocks the action. See breaker interlocking and fail-safe architecture.

The master engineering question

Which single failure, whether of a sensor, a contact, a cable or a program, could allow the action this interlock exists to prevent?

What to send us

Send the one-line diagram and operating sequences. Send your application details.

Questions engineers ask

Are software interlocks acceptable?

As an extra layer, yes. Critical safety interlocks need hard-wired or mechanical backup.

What are key interlocks for?

They enforce operating sequence by trapping keys until each step is done.

Can interlocks be bypassed?

Only under a controlled procedure and with the risk understood.

How often to test interlocks?

At commissioning, after changes and periodically.

This guide gives general principles. Safety interlocks must follow site procedures and standards.