Power-Factor Correction and kVAr Requirement Guide

How to calculate the capacitor kVAr needed to improve power factor, with a worked example, generator and harmonic cautions, and when APFC panels or detuned reactors are needed.

In short. Low power factor means you draw more current than needed for the real power, which raises losses and utility charges. Capacitors supply reactive power locally. The kVAr needed depends on the real load, the present and target power factor. On generators and with harmonics, correction needs extra care.

The calculation

Required kVAr = kW × (tan φ1 − tan φ2)
where φ = arccos (power factor)

Example (illustrative): 500 kW load at 0.80 power factor to be raised to 0.95. tan φ1 = tan(arccos 0.80) = 0.75; tan φ2 = tan(arccos 0.95) = 0.329. Required = 500 × (0.75 − 0.329) ≈ 210 kVAr. A 200 to 225 kVAr bank would be chosen.

Why improve power factor

Fixed or automatic

TypeUse
Fixed capacitorSteady loads, for example at a large motor
Automatic (APFC) panelVariable loads; steps switch in and out under a controller
Detuned (reactor) banksWhere harmonics are present, to avoid resonance
Active compensationFast-changing loads and harmonics

See APFC and power-factor correction.

Cautions with generators

Harmonics and resonance

Capacitors can resonate with the system inductance at a harmonic frequency, amplifying harmonic current. Where drives, UPS or rectifiers are present, use detuned reactors or filters, and check with a harmonic study. See harmonic screening.

Where to place capacitors

Motor capacitors on drives, soft starters or star-delta need special care, and should not be connected in a way that causes self-excitation.

Worked check on a generator (illustrative)

A site’s 500 kW load at 0.8 would need about 625 kVA from the generator. After correction to 0.95, about 526 kVA. The generator’s kVA loading falls by about 16 per cent, but its kW remains the same. Because the engine’s kW limit is unchanged, the benefit is on alternator and cable loading. If the capacitor bank remained connected at light load, the power factor could lead, and the generator voltage rise. Automatic control avoids that.

Capacitor sizing arithmetic

Required kVAr = kW × (tan φ1 − tan φ2), where cos φ1 is the present and cos φ2 the target power factor

Worked example (illustrative)

A 400 kW load at 0.78 power factor: tan φ1 = 0.802. Target 0.95: tan φ2 = 0.329. Required = 400 × (0.802 − 0.329) = 189 kVAr. Choose a 200 kVAr automatic bank in stages (for example 4 × 50 kVAr).

ItemConsideration
HarmonicsUse detuned reactors (such as 7 percent) where drives or UPS exist
StagesEnough steps to follow load without overcorrection
Generator supplyDisconnect or control the bank when on generator
SwitchingContactors rated for capacitor inrush
ProtectionFuses or breakers, discharge devices

Why generator supply is different

Leading current from capacitors can raise generator voltage, destabilise the AVR and trip the loss-of-excitation protection. With light load and a full bank, the generator can see a net leading power factor. Interlock the bank to switch off on generator operation unless the study approves.

Check

Measure present power factor over a representative period, since the average may hide low-load periods that need fewer stages.

See reactive power studies and harmonic risk screening.

Common mistakes

What to send us

Send the load, present power factor and any power-quality data. Send your application details. See also reactive power and power-factor studies.

Questions engineers ask

What target power factor should I use?

Commonly 0.95 to 0.99, depending on tariffs and system. Avoid going leading.

Can I use capacitors on a generator supply?

With care. Control them so the generator is not forced to absorb leading power.

Why are reactors added to capacitors?

To detune the circuit so it does not resonate with system harmonics.

Does power-factor correction reduce the generator size?

It reduces kVA loading but not kW, so the engine limit is unchanged.

Figures are illustrative. Use measured data and a harmonic check for design.