Reactive Power and Power-Factor Studies Guide

How to study reactive power: kW, kVAr and kVA relationships, power-factor targets, capacitor sizing, effects on generators and transformers, and the risks of leading power factor and resonance.

In short. Reactive power does no useful work but loads cables, transformers and alternators. A study finds where kVAr is needed, how much correction is justified, and what happens on generator supply, where too much capacitance can cause leading power factor and unstable voltage.

Relationships

kVA² = kW² + kVAr²

kVAr needed = kW × (tan φ₁ − tan φ₂)

Improving power factor from φ₁ to φ₂ reduces current for the same kW, easing loading and losses.

Why it matters

EquipmentEffect of low power factor
Utility supplyPenalties and higher demand charges
Cables and transformersHigher current, losses and voltage drop
GeneratorkVA limits the alternator even when engine kW is spare

Study steps

  1. Measure or estimate load kW and power factor by operating scenario, including light load.
  2. Set targets for the utility and for generator operation.
  3. Size correction in steps so power factor does not overshoot at low load.
  4. Check harmonics and resonance before adding capacitors. See resonance analysis.
  5. Check generator operation with capacitors connected, since leading power factor can reduce excitation margin and risk loss of control. See harmonics for related topics.

Generator cautions

Correction methods

Illustrative example

A 600 kW load at 0.78 power factor needs to reach 0.95. The kVAr required is 600 × (0.802 − 0.329), about 284 kVAr. The study chooses a 300 kVAr detuned bank in steps and adds an interlock that disconnects it on generator supply, because light-load operation could push the generator toward leading power factor.

Power factor in one triangle

kVA² = kW² + kVAr²; power factor = kW ÷ kVA

Reactive power (kVAr) is the magnetising current for motors and transformers. It loads cables and transformers but does no useful work.

Capacitor sizing example (illustrative)

A 500 kW load at 0.80 power factor has kVAr = 500 × tan(cos⁻¹ 0.80) = 500 × 0.75 = 375 kVAr. To reach 0.95: target kVAr = 500 × 0.329 = 164 kVAr. Capacitor required = 375 − 164 = 211 kVAr.

Generator interaction

IssueConsequence
Low lagging power factor on generatorAlternator limited by field heating; kW capacity falls below nameplate
Capacitor banks left connected on generator supplyLeading power factor, risk of overvoltage, AVR instability, loss of excitation trip
Switching capacitors against light loadResonance with harmonic sources

Design points

  1. Disconnect or automatically control capacitor banks when on generator supply.
  2. Use detuned reactors where harmonics are present.
  3. Check the alternator’s capability curve at the study’s operating points.
  4. Consider utility penalties and incentives for power factor on the grid side.

Study results should show the power factor at the incomer under mains and generator supply, and capacitor stage switching logic.

See harmonic filter application and kW and kVAr sharing.

Common mistakes

What to send us

Send load profile and bill data. Send your application details.

Questions engineers ask

Why can’t the generator use capacitors?

Over-correction can cause leading current and voltage instability.

What is detuning?

Series reactors move the resonance below troublesome harmonics.

What target power factor is right?

Choose based on tariff, equipment and safe margin, not the highest number.

Does low power factor reduce generator kW?

The engine kW is unchanged, but alternator kVA may limit useful kW.

Values are illustrative. Confirm with measured data.