Electrical FMEA and Single-Point-of-Failure Analysis

How to run an electrical FMEA: boundary, components, failure modes, effects, detection, ranking, single points of failure and the actions that close them.

In short. FMEA asks of each component: how can it fail, what happens next, how would we know and how bad is it? A single point of failure is any item whose failure alone stops the load. The study finds them, ranks them and assigns actions before an outage does it for you.

Method

  1. Set the boundary. The system, modes of operation and what counts as loss of function.
  2. List components from the single-line diagram, controls, auxiliaries and services.
  3. List failure modes for each: fails to start, fails to open or close, false trip, loses signal, loses supply.
  4. Describe local and system effects.
  5. Detection. Alarm, test, inspection or none.
  6. Rank. Severity, likelihood and detectability, using a consistent scale.
  7. Actions. Remove the failure, add redundancy, add detection, add procedure or accept with reason.
  8. Verify. Test the fix and re-rank.

Typical worksheet

ItemFailure modeEffectDetectionAction
Starting batteryLow chargeSet fails to startMonthly testDual battery, charger monitoring
Fuel transfer pumpFailsDay tank runs dryLevel alarmStandby pump, hand pump
Control supplyLoss of DCNo breaker controlDC fail alarmRedundant supplies
ATSFails to transferLoad not suppliedTest on loadBypass, redundant ATS

Commonly hidden single points

Illustrative example

A site with two generators believes it has full redundancy. FMEA shows both sets take their start signal through one controller and one 24 V supply. A failure of that supply stops both starts. Adding a second supply with diode isolation and a manual start path closes the gap.

How an electrical FMEA is built

For each component or function, list how it can fail, what happens as a result, how it would be detected and what protects against it. Score the risk and act on the highest.

ColumnContent
ItemFor example, ATS controller
Failure modeFails to transfer; transfers falsely; locks up
EffectLoad loses supply; sources paralleled out of phase
CauseControl power loss; wiring fault; software fault
DetectionAlarm; periodic test; none
Severity, occurrence, detection scoresTypically 1 to 10 each
Risk priority number (RPN)Severity × occurrence × detection
ActionRedundancy, supervision, procedure

Single points of failure to look for

  1. One DC supply for control and tripping.
  2. One fuel line, filter or day tank.
  3. One transfer switch for the whole critical load.
  4. Shared cable route or cable tray.
  5. One controller or one communications path.
  6. One key person or one set of spares.

Example (illustrative)

Failure mode: starter battery cannot crank. Effect: no generator start on mains failure. Detection: charger alarm only. Score high. Action: dual battery banks with separate chargers, battery load test schedule and voltage drop alarm.

Outcome

A ranked action list, design changes and test routines. See battery starting systems and protection failure modes.

Common mistakes

What to send us

Send drawings and failure history. Send your application details. See also reliability engineering.

Questions engineers ask

Who should take part?

Design, operations and maintenance staff together, since each sees different failures.

How often should it be repeated?

After changes and at planned intervals.

FMEA or FMECA?

FMECA adds a numeric criticality ranking. Use whichever fits your need.

Is it only for new designs?

No. It is very useful on existing sites.

This guide gives general principles. Rankings should reflect your site’s consequences.