Load Flow and Power Flow Studies Guide

What a load-flow study calculates, the inputs it needs, how to model utility, generators and loads, which cases to run, and how to read voltages, loadings, losses and power factor in the results.

In short. A load-flow study calculates steady-state voltages, currents and power flows in the system for a given set of sources and loads. It shows whether cables and transformers are overloaded, whether voltages are within limits, and how power divides between utility and generators.

What it tells you

Inputs

InputDetail
NetworkSingle-line diagram, cable data, transformer impedance and taps
SourcesUtility voltage and fault level; generator limits for kW, kVAr, voltage setpoint
LoadskW and power factor, by bus, for each case
Control settingsTap positions, AVR modes, capacitor steps

Cases to run

  1. Normal: maximum and minimum load on utility.
  2. Generator supply: loads on the generator alone, including the critical subset.
  3. Contingencies: a transformer or feeder out of service, one generator lost in a parallel plant.
  4. Future: including planned expansion.
  5. Parallel operation: with utility and generator, checking reactive power sharing.

Interpreting the results

Limits of the method

Load flow is steady-state. It does not show motor starting dips, fault currents or transient behaviour, which need other studies. It is only as good as its model: wrong impedances or loads give wrong voltages.

Illustrative example

A site fed by a long cable from a generator room shows a voltage of 94 percent at the farthest board at full load in the load-flow study, below the allowed minimum. Options are a larger cable, a local transformer tap change or a generator voltage setpoint adjustment. The study compares each and finds the tap change enough for normal load, but not for the motor-starting case, which is addressed separately.

What load flow solves

Given the network, the loads and the sources, load flow finds the steady-state voltage magnitude and angle at every bus, and the real and reactive power in every branch. From these come currents, losses and loading percentages.

Inputs and outputs

InputOutput
Source voltage and impedanceBus voltages
Transformer data and tap positionsTransformer loading and tap suitability
Cable lengths and sizesVoltage drop and losses
Load kW and power factorReactive flow, power factor at incomer
Generator output and voltage setpointGenerator loading and reactive share

What to check in results

  1. Bus voltages within the permitted band, commonly plus or minus five percent in service.
  2. No transformer or cable above its rating.
  3. Generator kVA and power factor within its capability.
  4. Losses at the expected level.

Cases to run

Generator-specific point

Under generator supply the lagging power factor seen by the alternator may be lower than on the mains, because capacitor banks and power factor correction can be disconnected or unsuitable. Load flow shows whether the alternator operates inside its reactive capability.

See reactive power studies and cable and voltage drop.

Common mistakes

What to send us

Send the single-line diagram, load list and cable data. Send your application details. See also voltage drop basics.

Questions engineers ask

Is load flow needed for small sites?

Hand calculations may be enough for simple radial systems. Larger or multi-source systems benefit from a model.

What voltage limits apply?

They depend on standards, equipment and the utility agreement. Define them before the study.

Does load flow include harmonics?

No. Harmonics need a separate study.

Can it size a generator?

It checks loading and voltage. Generator sizing also needs starting and transient studies.

This guide gives general principles. Results depend on the accuracy of the model.